DLA A-A-55461 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE HOSPITAL GRADE 20-AMPERE.pdf
《DLA A-A-55461 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE HOSPITAL GRADE 20-AMPERE.pdf》由会员分享,可在线阅读,更多相关《DLA A-A-55461 D-2009 INTERRUPTER GROUND FAULT TWO-POLE THREE-WIRE HOSPITAL GRADE 20-AMPERE.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Beneficial comments, recommendations, additions, deletions, clarifications, etc., and any data which may improve this document should be sent to: Defense Supply Center, Columbus, ATTN: DSCC-VAT, P.O. Box 3990, Columbus, OH 43218-3990, or email to mailto:CircuitProtectdscc.dla.mil. Since contact info
2、rmation can change you may want to verify the currency of the address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 5925 INCH-POUND A-A-55461D 30 January 2009 SUPERSEDING A-A-55461C October 1, 2003 COMMERCIAL ITEM DESCRIPTION INTERRUPTER, GROUND FAULT, TWO-P
3、OLE, THREE-WIRE HOSPITAL GRADE, 20-AMPERE The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SCOPE. This commercial item description (CID) covers the general requirements for a 20-ampere hospital grade ground fault interrupter.
4、 Ground fault interrupters covered by this CID are intended for commercial/industrial applications. 2. CLASSIFICATION/PART OR IDENTIFICATION NUMBER (PIN). This CID uses a classification system that is included in the PIN as shown in the following example (see 7.1). AA55461 - S B I CID number Termina
5、tion style (see table I) (S) for screw terminals. (W) for wire leads. Color code (B) Brown (I) Ivory (R) Red (G) Gray (W) White Indicator light (I) for indicator light. Blank for no indicator light. 3. SALIENT CHARACTERISTICS. 3.1 Interface and physical dimensions. Ground fault interrupters supplied
6、 to this CID shall be as specified herein and shall meet the requirements of UL 943 for class A ground fault interrupters and the hospital grade requirements as called out in UL 498 (see figure 1). 3.2. Ampere rating. The ampere rating shall be 20 amperes maximum. 3.3 Voltage rating. The voltage rat
7、ing shall be 125 V ac maximum. 3.4 Frequency rating. The frequency rating shall be 60 Hz. 3.5 Trip threshold. This ground fault interrupter shall trip when a fault current to ground is 4-6 mA minimum. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A
8、-A-55461D 2 NOTES: 1. Dimensions are in inches. 2. Unless otherwise specified, tolerance is .005 inch (0.13 mm). 3. Location of test button, reset button, and the indicator light is optional. FIGURE 1. Configuration and dimensions. Inches mm 1.229 31.22 1.800 45.72 2.780 70.61 3.280 83.33 3.812 96.8
9、2 4.200 106.68 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-55461D 3 3.6 Dimensions. Dimensions shall conform to NEMA standard WD 6 (reference NEMA configuration 5-20R) (see figure 1). 3.7 Termination style. The termination style shall be eith
10、er screw terminals or wire leads. 3.8 Wire size. The maximum wire size the screw terminal connectors shall accept is number 10 American Wire Gauge (AWG). The minimum wire size of the wire shall be number 14 AWG. 3.9 Wire lead length. The free length of the wire leads shall be 4 inches (101.6 millime
11、ters) minimum. The free length of the ground lead shall be 6 inches (152.4 millimeters) minimum. 3.10 Indicator light. If a yellow indicator light is provided, when lighted it shall indicate the “tripped” condition of the circuit interrupter; when unlighted it shall indicate power availability to th
12、e receptacle. 3.11 Marking. Ground fault interrupters or their unit package supplied to this CID shall be marked with the manufacturers (MFRs) standard commercial PIN and the ground fault interrupters shall bear the appropriate UL listing mark. (NOTE: The part number marked on the unit pack shall be
13、 the CID PIN.) 3.12 Recycled, recovered, or environmentally preferable materials. Recycled, recovered, or environmentally preferable materials should be used to the maximum extent possible provided that the material meets or exceeds the operational and maintenance requirements, and promotes economic
14、ally advantageous life cycle costs. 3.13 Workmanship. Ground fault interrupters shall be processed in such a manner as to be uniform in quality and shall be free from other defects that will affect life, serviceability, or appearance. 4. REGULATORY REQUIREMENTS. The offeror/contractor is encouraged
15、to use recovered materials to the maximum extent practicable, in accordance with 23.403 of the Federal Acquisition Regulation (FAR). 5. PRODUCT CONFORMANCE PROVISIONS. 5.1 Product conformance. The products provided shall meet the salient characteristics of this CID, conform to the producers own draw
16、ings, specifications, standards, and quality assurance practices, and be the same product offered for sale in the commercial market. The Government reserves the right to require proof of such conformance. 5.2 Market acceptance. The following market acceptance criteria are necessary to document the q
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAAA55461D2009INTERRUPTERGROUNDFAULTTWOPOLETHREEWIREHOSPITALGRADE20AMPEREPDF

链接地址:http://www.mydoc123.com/p-686795.html