《DIN 4102-11-1985 Fire behaviour of building materials and building components pipe encasements pipe bushings service shafts and ducts and barriers across inspection openings termin.pdf》由会员分享,可在线阅读,更多相关《DIN 4102-11-1985 Fire behaviour of building materials and building components pipe encasements pipe bushings service shafts and ducts and barriers across inspection openings termin.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、Fire behaviour of building materials and building components Pipe encasements, pipe bushings, service shafts and ducts, and barriers across inspection openings; terminology, requirements and testing euth Verlag GrnbH. Berlin 30, has exclusive sale rights for German Standards (DIN-Normen) DIN 4 102 P
2、art 1 1 Engl. Price group 08.86 Sales No. O107 - DIN 4102 Part 11 Brandverhalten von Baustoffen und Bauteilen; Rohrummantelungen, Rohrabschottungen, Installationcschchte und -kanale sowie Abschlsse ihrer Revisionsffnungen; Begriffe, Anforderungen und Prfungen In keeping with current practice in stan
3、dards published b y the International Organization for Standardization (KO), a comma has been used throughout as the decimal marker. DIN 4102 is divided into the followings Parts: DIN 41 02 Part 1 Fire behaviour of building materials and building components; building materials; terminology, requirem
4、ents and testing DIN 4102 Part 2 Fire behaviour of building materials and building components; building components; terminology, requirements and testing DIN 4102 Part 3 Fire behaviour of building materials and building components; fire walls and non-loadbearing outer walls; terminology, requirement
5、s and testing DIN 4102 Part 4 Fire behaviour of building materials and building components; summary and use of classified building materials, building components and special building components DIN 4102 Part 5 Fire behaviour of building materials and building components; fire barriers, barriers in l
6、ift wells and glazings resistant against fire; terminology, requirements and testing DIN 41 02 Part 6 Fire behaviour of building materials and building components; ventilation ducts; terminology, requirements and testing DIN 41 02 Part 7 Fire behaviour of building materials and building components;
7、roofing; terminology, requirements and testing DIN 4102 Part 8 (at present at the stage of draft) Fire behaviour of building materials and building components; small scale test furnace DIN 4102 Part 11 Fire behaviour of building materials and building components; pipe encasements, pipe bushings, ser
8、vice shafts and ducts and barriers across inspection openings; terminology, requirements and testing Standards dealing with the fire behaviour of sealing compounds used for cable passages through building components and specifying methods of testing the reliability of electric cables in a fire situa
9、tion are in course of preparation. Dimensions in mm Contents Page 1 Scope and field of application 2 2 Concepts 2 2.1 Fire resistance time 2 2.2 Measures taken to prevent the spread of fire along pipes (pipe bushings) . 2 2.3 Serviceshafts 2 2.4 Serviceducts 2 2.5 Barriers across inspection openings
10、 2 3 Verification of fire resistance classes 2 3.1 Verification on the basis of fire tests 2 3.2 Classification into fire resistance classes 3 4 Pipe encasements and pipe bushings 3 4.1 Requirements . 3 4.2 Testing 3 4.2.1 Sampling . 3 4.2.2 Test furnace 3 4.2.3 Type and size of specimens and test a
11、rrangement 3 4.2.4 Procedure 3 4.2.4.1 Fire test with minimum exposure to fire . 3 4.2.4.2 Fire test based on the standard temperature-time curve 4 4.2.4.3 Fire test with exposure. to smouldering fire. . 4 Page 5 Service shafts and ducts, barriers across inspection 5.1 Requirements . 4 4 5.2.1 Test
12、furnace 4 5.2.2 Type and size of specimens and test 5.2.3 Procedure 4 5.3 Testing of service ducts . 4 5.3.1 Test furnace 4 5.3.2 Type and size of specimens and test 5.3.3 Procedure 4 5.4 Testing of barriers across inspection openings . 4 5.4.1 5.4.2 Procedure 5 openings 4 5.2 Testing of service sha
13、fts . arrangement 4 arrangement 4 Type and size of specimens and test arrangement 4 6 Test certificate 5 Standards referred to 11 Other relevant documents 11 Explanatory notes .12 Continued on pages 2 to 12 Page 2 DIN 4102 Part 11 Fire resinance class Fire resistance class of service shafts and Fire
14、 resistance for measures against ducts and barriers time, in min the spread of fire along pipes across their inspection open i ngs - R 30 I 30 E 30 R 60 I 60 2 60 R 90 I 90 2 90 R 120 I120 2 120 1 Scope and field of application This standard defines concepts relating to fire protection and specifies
15、 requirements and tests for measures taken to prevent the spread of fire along service shafts and ducts, and along pipes, including any pipe insulating layers and sheathing. Pipe encasements and pipe bushings, service shafts and ducts shall be so designed as to prevent the spread of fire and smoke t
16、hrough floors and walls during the fire resistance time specified in table 1. The protective measures evaluated in accordance with this standard do not cover the risk of fire spread due to the passage of heat along pipes. The risk of damage as a consequence of the thermal elongation or shortening of
17、 the pipes is dealt with only in respect of the structure of the specimens. The testing of service ducts as specified in this standard does not cover the risk of damage caused by falling pipe and cable supports or ducts, nor does it include an assessment of the reliability of the pipes and cables la
18、id inside them, such as emergency power supply lines. ) In addition, this standard does not deal with the possibility of the leakage of dangerous liquids or gases as a result of the destruction of pipes under fire conditions. This standard does not apply to the testing of sealing compounds for cable
19、 bushings2) nor to the testing of ventilation shafts and fire dampers for preventing the spread of fire along ventilation ducts (see DIN 4102 Part 6). However, this does not exclude the use of service shafts assigned to fire resistance classes I 30 to I 120 and tested as specified in this standard a
20、s fire resistant encasements for vertical ventilation ducts with fire dampers made of sheet steel in accordance with DIN 18017 Parts 1 t03). This standard does not deal with methods of testing cable ducts covered by DIN VDE 0604 Parts 1 to 3 (at present at the stage of draft), trunking for undergrou
21、nd cable ducts covered by DIN VDE 0634 Part 2 (at present at the stage of draft) nor with pipes used for the convey- ance of shavings, or used as laundry chutes or for waste disposal. 2 Concepts 2.1 Fire resistance time The fire resistance time is the minimum length of time, in minutes, during which
22、 fire and smoke is prevented by protective measures from spreading along pipes or service shafts and ducts and through barriers across inspection openings in fire tests carried out as specified in sub- clauses 4.2.4.2, 5.2.3,5.3.3 or 5.4.2 using the standard Table I. Fire resistance classes R and I
23、*) temperature-time curve. The fire resistance classes given in table 1 are differentiated according to the fire resistance time. 2.2 Measures taken to prevent the spread of fire along pipes (pipe bushings) The provision of pipe bushings is to be regarded as a measure serving to prevent the spread o
24、f fire along pipes. The bushings are installed at points at which pipes pass through a building component for which fire resistance req u i rernents ex ist. The provision of pipe encasements (complete or partial encasements) or the concealing of pipes under plaster shall also be regarded as a measur
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DIN4102111985FIREBEHAVIOUROFBUILDINGMATERIALSANDBUILDINGCOMPONENTSPIPEENCASEMENTSPIPEBUSHINGSSERVICESHAFTSANDDUCTSANDBARRIERSACROSSINSPECTIONOPENINGSTERMINPDF

链接地址:http://www.mydoc123.com/p-656892.html