CLC TR 50646-2015 Railway Application - Fixed Installations - Specification for reversible d c substations.pdf
《CLC TR 50646-2015 Railway Application - Fixed Installations - Specification for reversible d c substations.pdf》由会员分享,可在线阅读,更多相关《CLC TR 50646-2015 Railway Application - Fixed Installations - Specification for reversible d c substations.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、BSI Standards PublicationRailway Application FixedInstallations Specification forreversible d.c. substationsPD CLC/TR 50646:2015National forewordThis Published Document is the UK implementation of CLC/TR 50646:2015.The UK participation in its preparation was entrusted by TechnicalCommittee GEL/9, Ra
2、ilway Electrotechnical Applications, to SubcommitteeGEL/9/3, Railway Electrotechnical Applications Fixed Equipment.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions ofa contract.
3、Users are responsible for its correct application. The British Standards Institution 2016.Published by BSI Standards Limited 2016ISBN 978 0 580 88380 4ICS 29.280Compliance with a British Standard cannot confer immunity fromlegal obligations.This Published Document was published under the authority o
4、f theStandards Policy and Strategy Committee on 31 January 2016.Amendments/corrigenda issued since publicationDate Text affectedPUBLISHED DOCUMENTPD CLC/TR 50646:2015TECHNICAL REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CLC/TR 50646 December 2015 ICS 29.280 English Version Railway Application - Fix
5、ed Installations - Specification for reversible d.c. substations Applications ferroviaires - Installations fixes - Spcification pour sous-stations rversibles courant continu Bahnanwendungen - Ortsfeste Anlagen - Spezifikation rckspeisefhiger Unterwerke fr Gleichstrombahnen This Technical Report was
6、approved by CENELEC on 2015-10-26. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lit
7、huania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnisc
8、he Normung CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2015 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members. Ref. No. CLC/TR 50646:2015 E PD CLC/TR 50646:2015CLC/TR 50646:2015 (E) 2 Contents Page European foreword . 4 Introd
9、uction 5 1 Scope 6 2 Normative references . 6 3 Terms, definitions and abbreviations . 6 3.1 Terms and definitions . 6 3.2 Abbreviations 7 4 General . 8 4.1 Application of reversible substation . 8 4.2 Energy efficiency analysis . 8 4.3 System architecture 8 4.4 Braking safety . 10 5 Standard perfor
10、mances 10 5.1 General recommendations . 10 5.2 Performance of the system 10 5.2.1 Power rating 10 5.2.2 Energy efficiency 10 5.2.3 Harmonics and reactive power compensation 10 5.2.4 Additional recommendations. 11 5.2.5 Safety 11 5.2.6 Availability . 11 6 Constraints 11 6.1 Climatic environment 11 6.
11、2 Electromagnetic compatibility . 11 6.3 Harmonic content 11 6.4 Interfaces with operational environment 11 6.4.1 General . 11 6.4.2 Installation . 11 6.4.3 Power supply and distribution 12 6.4.4 Monitoring 12 6.4.5 Rolling stock 12 6.4.6 Operation . 12 7 Functional aspects 12 7.1 General . 12 7.2 E
12、nergy regeneration . 13 7.3 Power quality . 13 7.3.1 General . 13 7.3.2 Substation voltage and load balancing 14 7.3.3 Harmonic compensation 14 7.3.4 Reactive power optimization 14 7.4 Protection functions . 14 7.5 Automatic converter configuration . 15 7.6 Substation control and monitoring . 15 7.7
13、 Centralized control function 16 8 System simulation and equipment sizing 16 8.1 General . 16 8.2 Energy consumption computation 17 PD CLC/TR 50646:2015CLC/TR 50646:2015 (E) 3 8.3 Rating of equipment . 17 9 Further standardization needs 18 Bibliography 20 PD CLC/TR 50646:2015CLC/TR 50646:2015 (E) 4
14、European foreword This document (CLC/TR 50646:2015) has been prepared by CLC/SC 9XC “Electric supply and earthing systems for public transport equipment and ancillary apparatus (Fixed installations)”. Attention is drawn to the possibility that some of the elements of this document may be the subject
15、 of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CENELEC by the European Commission and the European Free Trade Association. PD CLC/TR 50646:2015CLC/TR 50646:2015 (E) 5 Introduc
16、tion This document originates from the Technical Specification issued by UIC/UNIFE on the same topic, and was offered as a CENELEC Technical Report. The purpose of this Technical Report is to provide recommendations for reversible DC substations. Reversible substations are capable of feeding the tra
17、in regenerative braking energy (up to 100 %) back to the AC high voltage distribution network, while maintaining the capability of exchanging energy between trains on the DC line. A substantial amount of energy can be saved for DC systems which operate electric trains fitted with regenerative brakin
18、g, on commuter services or operating on steep gradient lines. The system receptivity can be improved by feeding the excess regenerative braking energy to the upstream AC network (e.g. AC railway network or national grid) at a higher voltage level. This document provides recommendations if DC Reversi
19、ble Traction Substations are installed to improve line receptivity of DC power supply networks. This document is suitable for newly manufactured traction substations as well as for upgrading and renewal of existing lines. This technical recommendation aims at improving the energy efficiency of the D
20、C transport system, reducing energy consumption, and contributing to a greener environment. PD CLC/TR 50646:2015CLC/TR 50646:2015 (E) 6 1 Scope This Technical Report provides recommendations for DC reversible substations. These recommendations apply to systems and components that facilitate the flow
21、 of energy to and from the upstream AC grid including their related interfaces. These recommendations provide the necessary functions for the recovery of braking energy. It is intended to be used in fixed electrical installations with nominal voltage not exceeding 3 000 V DC which supply electrical
22、power to vehicles used in public guided transport systems, i.e. railway vehicles, tramway vehicles, underground vehicles and trolley-buses It is intended to provide an overview of state-of-the-art applications, define the minimum recommendations that are presently available, and provide functional r
23、ecommendations to be applied to these substations. This document focuses mainly on the substation converters and the traction transformers. Other devices such as switchgear - if they are the same as in classic substations - are not addressed here. Moreover this specification addresses performance, c
24、onstraints, validation and acceptance criteria for the implementation of reversible substations. This document provides the minimum recommendations to be fulfilled. However, due to the different possible solutions and different types of existing technologies, this document does not provide technical
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CLCTR506462015RAILWAYAPPLICATIONFIXEDINSTALLATIONSSPECIFICATIONFORREVERSIBLEDCSUBSTATIONSPDF

链接地址:http://www.mydoc123.com/p-629539.html