CEN TR 15601-2012 Hygrothermal performance of buildings - Resistance to wind - driven rain of roof coverings with discontinuously laid small elements - Test methods《建筑的温湿性能 带不连续铺设小.pdf
《CEN TR 15601-2012 Hygrothermal performance of buildings - Resistance to wind - driven rain of roof coverings with discontinuously laid small elements - Test methods《建筑的温湿性能 带不连续铺设小.pdf》由会员分享,可在线阅读,更多相关《CEN TR 15601-2012 Hygrothermal performance of buildings - Resistance to wind - driven rain of roof coverings with discontinuously laid small elements - Test methods《建筑的温湿性能 带不连续铺设小.pdf(28页珍藏版)》请在麦多课文档分享上搜索。
1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationHygrothermal performance of buildings Resistance towind-driven rain of roof coverings with discontinuouslylaid small elements Test methodsPD CEN/TR 15601:2012National forewordThi
2、s Published Document is the UK implementation of CEN/TR 15601:2012.The UK participation in its preparation was entrusted to Technical CommitteeB/540, Energy performance of materials components and buildings.A list of organizations represented on this committee can be obtained onrequest to its secret
3、ary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. The British Standards Institution 2012Published by BSI Standards Limited 2012ISBN 978 0 580 57913 4ICS 91.120.10; 91.120.30Compliance with a British Standard
4、 cannot confer immunity fromlegal obligations.This Published Document was published under the authority of theStandards Policy and Strategy Committee on 30 April 2012.Amendments issued since publicationAmd. No. Date Text affectedPUBLISHED DOCUMENTPD CEN/TR 15601:2012TECHNICAL REPORT RAPPORT TECHNIQU
5、E TECHNISCHER BERICHT CEN/TR 15601 March 2012 ICS 91.120.10; 91.120.30 English Version Hygrothermal performance of buildings - Resistance to wind - driven rain of roof coverings with discontinuously laid small elements - Test methods Performance hygrothermique des btiments - Rsistance la pluie batta
6、nte de couvertures en petits lments poss en discontinu - Mthodes dessai Wrme- und feuchteschutztechnisches Verhalten von Gebuden - Widerstand von Dacheindeckungen aus kleinformatigen, berlappend gedeckten Dachelementen gegen Schlagregen - Prfverfahren This Technical Report was approved by CEN on 7 F
7、ebruary 2012. It has been drawn up by the Technical Committee CEN/TC 89. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg,
8、Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2012 CEN All rig
9、hts of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. CEN/TR 15601:2012: EPD CEN/TR 15601:2012CEN/TR 15601:2012 (E) 2 Contents Page Foreword 3Introduction .41 Scope 52 Normative References .53 Terms and definitions .54 Symbols and units .65 Principle
10、66 Test specimens 66.1 Test specimen samples 66.2 Dimensions of the test specimen .66.3 Number of sets of tests .76.4 Preparation of test specimen .77 Apparatus .77.1 General 77.2 Suction chamber 77.3 Fan system .87.4 Rain generating installation 87.5 Run-off water 97.6 Observation and measurement o
11、f leakage .98 Test procedure .98.1 General 98.2 Test conditions . 108.2.1 General . 108.2.2 Wind speed modification for roof pitch 108.2.3 Run-off water . 119 Evaluation and expression of test results . 1510 Test report . 15Annex A (Informative) Examples of wind-driven rain apparatus 17Annex B (Info
12、rmative) Derivation of the rainfall rate on a pitched roof 22Annex C (Normative) Use of test results . 23Bibliography . 24PD CEN/TR 15601:2012CEN/TR 15601:2012 (E) 3 Foreword This document (CEN/TR 15601:2012) has been prepared by Technical Committee CEN/TC 89 “Thermal performance of buildings and bu
13、ilding components”, the secretariat of which is held by SIS. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. PD CEN/TR 15601:2012CEN/T
14、R 15601:2012 (E) 4 Introduction The extent to which roof coverings can resist water penetration from the combination of wind and rain, commonly referred to as wind driven rain, is important for the design of roofs. This CEN Technical Report describes a method of test to determine the performance of
15、the roof covering against wind driven rain. The combined action of wind and rain varies considerably with geographical location of a building and the associated differences in the rain and wind climate. Wind-rain climate zones are specified for: Northern Europe Coastal, Central Europe and Southern E
16、urope. Each climate zone is divided into four wind-rain sub-tests (including a deluge condition). This Technical Report does not contain information on the level of acceptable performance. The use of test results is given in Annex C. In case of reference should be made to testing according to this d
17、ocument the word “shall“ is used at the appropriate places. PD CEN/TR 15601:2012CEN/TR 15601:2012 (E) 5 1 Scope This Techncial Report describes a method of test for determining the resistance of pitched roof coverings to wind-driven and deluge rain. The test method is applicable to discontinuously l
18、aid unsealed small roof covering elements such as clay tiles, concrete tiles, slates, fibre cement slates and stones. NOTE The test method may be adapted for fittings. 2 Normative References This document contains no normative references. 3 Terms and definitions For the purposes of this document, th
19、e following terms and definitions apply. 3.1 test specimen assembled array of elements for testing over which water leakage is to be observed or measured, excluding perimeter elements with sealed joints 3.2 set of tests consisting of sub-tests B and D, (and optionally subtests A and C), for an appro
20、priate climate zone, roof pitch and laying specification Note 1 to entry: The sub-tests A, B, C and D are defined in Clause 8. 3.3 reference leakage rate leakage rate of 10 g/m2/5 min, 5-minutes being the duration of a single test step in the sub-test PD CEN/TR 15601:2012CEN/TR 15601:2012 (E) 6 4 Sy
21、mbols and units Symbol Quantity Unit f wind speed factor relating u and us- Iuturbulence intensity % L Simulated additional rafter length above the test specimen m Rhrainfall rate on a horizontal plane mm/h Rrorun-off rate l/min Rtrainfall rate on the roof surface mm/h u wind speed approaching the r
22、oof m/s utterminal velocity of rain drops m/s gStandard deviation of the turbulent fluctuations in the wind speed m/s Mean wind speed approaching the roof m/s uswind speed over test specimen m/s W the effective width of the test specimen m roof pitch Degree angle of incidence of rain Degreeo5 Princi
23、ple A test specimen is fitted into the wind-driven rain apparatus, the external surface of the test specimen is exposed to wind and continuously sprayed with water, and run-off water is continuously applied at the top of the specimen. At the same time an air pressure difference between the upper and
24、 lower surfaces of the test specimen is increased or decreased in specific steps. Water leakage through the test specimen, which can occur at certain air pressure differences, is observed and measured. 6 Test specimens 6.1 Test specimen samples Samples for the test specimen shall comply, where relev
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CENTR156012012HYGROTHERMALPERFORMANCEOFBUILDINGSRESISTANCETOWINDDRIVENRAINOFROOFCOVERINGSWITHDISCONTINUOUSLYLAIDSMALLELEMENTSTESTMETHODS

链接地址:http://www.mydoc123.com/p-592145.html