1、BRITISH STANDARD BS 7713:1993 IEC 944:1988 Guide for the maintenance of silicone transformer liquidsBS 7713:1993 This British Standard, having been prepared under the directionof the Cables and Insulation Standards Policy Committee, was published underthe authority of the Standards Board and comes i
2、ntoeffect on 15November1993 BSI 10-1999 The following BSI references relate to the work on this standard: Committee reference CIL/10 Draft for comment 85/32912 DC ISBN 0 580 22582 8 Committees responsible for this British Standard The preparation of this British Standard was entrusted by the Cables
3、and Insulation Standards Policy Committee (CIL/-) to Technical Committee CIL/10 upon which the following bodies were represented: Association of Consulting Engineers Chemical Industries Association Electricity Industry in United Kingdom ERA Technology Ltd. Health and Safety Executive Institute of Pe
4、troleum Transmission and Distribution Association (BEAMA Ltd.) The following bodies were also represented in the drafting of the standard, through subcommittees and panels: British (AC) Capacitor Manufacturers Association (BEAMA Ltd.) British Cable Makers Confederation British Lubricants Federation
5、Ltd. National Association of Waste Disposal Contractors Amendments issued since publication Amd. No. Date CommentsBS 7713:1993 BSI 10-1999 i Contents Page Committees responsible Inside front cover National foreword ii 1 Scope 1 2 Tests and their significance 1 3 Frequency of examination of silicone
6、liquid in service 2 4 Sampling 2 5 Testing procedures 2 6 Classification of silicone transformer liquid in service 2 7 Treatment of silicone transformer liquid in Group2 3 8 Handling materials 3 List of references Inside back coverBS 7713:1993 ii BSI 10-1999 National foreword This British Standard h
7、as been prepared under the direction of the Cables and Insulation Standards Policy Committee. It is identical with IEC944:1988 Guide for the maintenance of silicone transformer liquids, published by the International Electrotechnical Commission (IEC). IEC944:1988 was prepared by IEC Technical Commit
8、tee No. 10, Fluids for electrotechnical applications. The United Kingdom participation in the drafting was provided by Technical Committee CIL/10, Fluids for electrotechnical applications. WARNING NOTE. This British Standard calls for the use of substances that may be injurious to health if adequate
9、 precautions are not taken. It refers only to technical suitability and does not absolve the user from legal obligations relating to health and safety at any stage. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible f
10、or their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Cross-reference International Standard Corresponding British Standard IEC 836:1988 BS 7704:1993 Specifications for silicone liquids for electrical purposes (Implements CENELEC
11、HD565S1) (Identical) Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages1 to 4, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendmen
12、t table on the inside front cover.BS 7713:1993 BSI 10-1999 1 1 Scope This standard is a guide to the maintenance of silicone liquids in transformers with rated voltages up to35kV and is intended to assist the equipment operator in assessing the quality of the liquid during use in the equipment and m
13、aintaining it in serviceable condition. Methods for reconditioning silicone transformer liquid are outlined. It deals only with silicone liquids used in equipment where liquid sampling is practicable and which has not previously been filled with any other liquid. 2 Tests and their significance There
14、 are several tests which can be applied to silicone transformer liquids to determine their suitability for further use or whether corrective action is necessary. The appropriate method of test is indicated by cross-reference to the relevant clause in IECPublication836, Section2 Test methods. 2.1 Col
15、our and appearance Cloudiness or visible solid particles indicate that the materials should be dried and/or filtered. A modification of the colour indicates contamination, and electrical tests should be carried out. 2.2 Density Changes in density normally indicate contamination by other liquids. 2.3
16、 Kinematic viscosity The viscosity of silicone transformer liquid rarely changes even after long periods of service. A value outside the normal values given in Section3 of IECPublication836 indicates contamination by other substances or possibly severe and prolonged overheating. 2.4 Flash-point Fire
17、-point Diminution of the flash-point or fire-point is normally due to contamination by other liquids. It may also occur as the result of severe degradation of the liquid, suggesting a fault in the transformer. In the latter case, other properties could also be affected. 2.5 Water content A value abo
18、ve that specified indicates undesirable operating conditions and the need for corrective action, such as circulating the liquid through a suitable drier and replacing drying tubes where fitted. 2.6 Breakdown voltage A reduced value may be due to the presence of water or to particulate contamination
19、of the liquid. Remedial treatment of the liquid should be considered. 2.7 D.C. resistivity A reduced value suggests contamination by water or soluble impurities. Remedial treatment of the liquid should be considered. 2.8 Dielectric dissipation factor An increased value may well indicate degradation
20、of the silicone liquid or contamination by water or other impurities. Remedial treatment of the liquid should be considered. Property Clause Colour and appearance 8 Density 9 Kinematic viscosity 10 Flash-point 11 Fire-point 12 Water content 16 Breakdown voltage 19 D.C. resistivity 20 Dielectric diss
21、ipation factor 20BS 7713:1993 2 BSI 10-1999 3 Frequency of examination of silicone liquid in service It is not possible to specify a frequency of examination which meets all service conditions. For air-breathing transformers, a simple visual inspection should be carried out at six-month intervals to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS77131993GUIDEFORTHEMAINTENANCEOFSILICONETRANSFORMERLIQUIDS 变压器 硅油 维护 指南 PDF

链接地址:http://www.mydoc123.com/p-546995.html