BS 764-1990 Specification for automatic change-over contactors for emergency lighting systems《紧急照明系统用的自动转换接触器规范》.pdf
《BS 764-1990 Specification for automatic change-over contactors for emergency lighting systems《紧急照明系统用的自动转换接触器规范》.pdf》由会员分享,可在线阅读,更多相关《BS 764-1990 Specification for automatic change-over contactors for emergency lighting systems《紧急照明系统用的自动转换接触器规范》.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 764:1990 Specification for Automatic change-over contactors for emergency lighting systems UDC 621.316.53BS764:1990 This British Standard, having been prepared under the directionof the Power Electrical Engineering Standards Policy Committee, was published underthe authority of t
2、he BoardofBSI and comes intoeffecton 31 May 1990 BSI 10-1999 First published December 1937 Second edition July 1954 Third edition May 1990 The following BSI references relate to the work on this standard: Committee reference PEL/10 Draftannounced in BSI News November 1989 ISBN 0 580 17995 8 Committe
3、es responsible for this British Standard The preparation of this British Standard was entrusted by the Power Electrical Engineering Standards Policy Committee (PEL/-) to Technical Committee PEL/10, upon which the following bodies were represented: ASTA Certification Services Association of Manufactu
4、rers Allied to the Electrical and Electronic Industry (BEAMALtd.) British Gas plc ERA Technology Ltd. Electrical Contractors Association Electrical Installation Equipment Manufacturers Association (BEAMA Ltd.) Electricity Supply Industry in England and Wales Electronic Components Industry Federation
5、 GAMBICA (BEAMA Ltd.) Health and Safety Executive Institution of Electrical Engineers Amendments issued since publication Amd. No. Date of issue CommentsBS764:1990 BSI 10-1999 i Contents Page Committees responsible Inside front cover Foreword ii 1 Scope 1 2 Definitions 1 3 Characteristics 1 4 Design
6、, construction and marking 2 5 Tests 5 Appendix A Methods for measurement of temperature 8 Appendix B Information to be supplied to the manufacturer with enquiry and/or order 8 Figure 1 Diagram of typical circuit for test for making and breaking capacity 7 Table 1 Minimum contact force 3 Table 2 Lim
7、its of temperature rise for contacts and conductors 4 Table 3 Limits of temperature rise for coils 5 Publications referred to Inside back coverBS764:1990 ii BSI 10-1999 Foreword This new edition of BS 764 has been prepared under the direction of the Power Electrical Engineering Standards Policy Comm
8、ittee. It introduces technical changes to bring the standard up-to-date and includes references to new materials to eliminate the use of asbestos and asbestos products. This new edition does not reflect a full review of the standard which will be undertaken in due course. This British Standard repla
9、ces BS 764:1954 which is withdrawn. Assessed capability. Users of this British Standard are advised to consider the desirability of assessment and registration of a suppliers quality systems against the appropriate Part of BS 5750 by a third party certification body. A British Standard does not purp
10、ort to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front c
11、over, pages i and ii, pages1 to 8, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover.BS764:1990 BSI 10-1999 1 1 Scope This British Standard speci
12、fies d.c. and single-phase a.c. automatic double-pole change-over contactors for low voltages up to 250 V employed in conjunction with storage batteries or other alternative source of supply, to provide a means of automatically changing the current supplied to safety lights from the normal source to
13、 the alternative source when the normal source fails, and of reconnecting the safety lights to the normal source when this source is restored. This standard does not apply to three-phase a.c. automatic change-over contactors. NOTE 1Appendix B lists information to be supplied to the manufacturer with
14、 the enquiry and/or order. NOTE 2The titles of the publications referred to in this standard are listed on the inside back cover. 2 Definitions For the purposes of this British Standard, the following definitions apply. 2.1 automatic change-over contactor a complete apparatus for effecting automatic
15、 change-over of the safety lights from the normal supply to the alternative supply when the normal supply fails, and for returning the safety lights to the normal supply when this supply is restored. The return operation may be effected through the agency of a relay which, if employed, is an integra
16、l part of the contactor 2.2 safety lights lights which are normally connected to normal supply and are changed over to the alternative supply when the normal supply fails, e.g. the safety lights specified under the Cinematograph Regulations 2.3 main contactor apparatus constructed in accordance with
17、 this specification, excepting the relay if employed. Where the complete automatic change-over contactor is intended, this is made clear in relevant clauses 2.4 relay a voltage dependent relay, the function of which is to cause the main contactor to change from the emergency to the normal position w
18、hen the main supply voltage has recovered to a particular value 2.5 contactor coil the shunt connected coil energized from the normal supply, which causes the main contactor either to change to, or to remain in, the normal position 2.6 relay coil the shunt connected coil, energized from the normal s
19、upply, which causes the relay contacts to move to one of their two positions 2.7 load carrying contacts contacts on the main contactors which in either normal or emergency conditions carry the current for supplying the safety lights 2.8 “silver” contact a contact composed of or faced with not less t
20、han0.4064 mm of fine silver or other material of equivalent performance 2.9 normal position of main contactor the position of the main contactor when it is connecting the safety lights to the normal supply 2.10 emergency position of main contactor the position of the main contactor when it is connec
21、ting the safety lights to the emergency supply 2.11 dust-protecting enclosure an enclosure constructed to prevent the ready ingress of dust 3 Characteristics 3.1 Rating The complete apparatus shall be rated in terms of its current-carrying capacity and voltage and also in terms of frequency if a.c.
22、3.2 Sizes The following current ratings shall apply: a) 15 A at 30 V; b) 15 A, 30 A, 60 A and 100 A at voltages not exceeding 250 V. Where a total load in excess of 100 A applies, it should be divided over two or more separate circuits, each controlled by an independent automatic change-over contact
23、or.BS764:1990 2 BSI 10-1999 4 Design, construction and marking 4.1 General principles The apparatus shall operate on the principle that the contacts of the main contactor are closed to the normal position by an electro-magnet or electro-magnets, energized from the normal supply, the direct pull of w
24、hich is the only force preventing the main contactor from closing to its emergency position under the action of gravity or springs, or both. Every operating spring used shall be so fitted that in the event of breakage, it shall not foul the mechanism and shall not come into contact with live parts.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS7641990SPECIFICATIONFORAUTOMATICCHANGEOVERCONTACTORSFOREMERGENCYLIGHTINGSYSTEMS 紧急 照明 系统 自动 转换 接触器

链接地址:http://www.mydoc123.com/p-546933.html