BS 7629-1-2015 Electric cables Specification for 300 500 V fire resistant screened fixed installation cables having low emission of smoke and corrosive gases when affected by fire .pdf
《BS 7629-1-2015 Electric cables Specification for 300 500 V fire resistant screened fixed installation cables having low emission of smoke and corrosive gases when affected by fire .pdf》由会员分享,可在线阅读,更多相关《BS 7629-1-2015 Electric cables Specification for 300 500 V fire resistant screened fixed installation cables having low emission of smoke and corrosive gases when affected by fire .pdf(34页珍藏版)》请在麦多课文档分享上搜索。
1、BSI Standards PublicationBS 7629-1:2015Electric cables Specificationfor 300/500 V fire resistant,screened, fixed installationcables having low emissionof smoke and corrosivegases when affected by firePart 1: Multicore cablesPublishing and copyright informationThe BSI copyright notice displayed in th
2、is document indicates when the documentwas last issued. The British Standards Institution 2015Published by BSI Standards Limited 2015ISBN 978 0 580 85384 5ICS 13.220.99; 29.060.20The following BSI references relate to the work on this document:Committee reference GEL/20/17Draft for comment 14/302952
3、04 DCPublication historyFirst published April 1997Second edition November 2008Third (current) edition August 2015Amendments issued since publicationDate Text affectedBS 7629-1:2015 BRITISH STANDARDContentsForeword ii1 Scope 12 Normative references 13 Terms and definitions 24 Voltage designation and
4、fire resistance categories 35 Conductors and drain wire 56 Insulation 57 Identification of cores 68 Laying-up 79 Screen 810 Sheath 811 Cable marking and additional information 912 Schedule of tests 1113 Test conditions 1314 Routine tests 1315 Sample tests 1416 Type tests 16AnnexesAnnex A (informativ
5、e) Guide to selection, installation and operation 17Annex B (normative) Method of test for continuity of tinned coatings ofwires 20Annex C (normative) Method of test for voltage withstand 20Annex D (normative) Method of test for bending characteristics 21Annex E (normative) Method of test for resist
6、ance to impact 21Annex F (normative) Method of test for shrinkage of sheath on cable duringheat treatment 22Annex G (informative) Notes on type tests 23Bibliography 26List of figuresFigure 1 Lay up diagram of multi-core auxiliary cables (7-core, 12-coreand 19-core) 7Figure 2 Example of the marking a
7、s used on the outer sheath of the cable 10Figure E.1 Chisel-edged intermediate piece for test for resistance to impact 22List of tablesTable 1 Maximum permitted voltages against rated voltage of cable 4Table 2 Dimensions of 2-core, 3-core and 4-core cables 4Table 3 Dimensions of multi-core auxiliary
8、 cables 5Table 4 Identification of cores in multicore cables 6Table 5 Schedule of tests 12Summary of pagesThis document comprises a front cover, an inside front cover, pages i to iv,pages 1 to 26, an inside back cover and a back cover.BRITISH STANDARD BS 7629-1:2015 The British Standards Institution
9、 2015 iForewordPublishing informationThis British Standard is published by BSI Standards Limited, under licence fromThe British Standards Institution, and came into effect on 31 August 2015. It wasprepared by Subcommittee GEL/20/17, Low voltage cables, under the authorityof Technical Committee GEL/2
10、0, Electric cables. A list of organizationsrepresented on these committees can be obtained on request to their secretary.SupersessionThis British Standard supersedes BS 7629-1:2008, which will be withdrawnon 31 August 2016.Relationship with other publicationsThis new edition of BS 7629-1 takes accou
11、nt of the publication ofBS 5266-1:2011 and BS 5839-1:2013 and their increased fire testing requirements.Information about this documentThis is a full revision of the standard and introduces the following principalchanges.a) The marking arrangements are updated and clarified.b) Test methods are updat
12、ed to reflect the latest CENELEC harmonization.c) This new edition takes account of: BS EN 50395 (replacing Annex E of BS 7629-1:2008) on electrical tests; BS EN 50396 (replacing Annex B of BS 7629-1:2008) on thicknessmeasurement; BS EN 60332-1-2 (replacing BS EN 50265-2-1) on flame propagation of a
13、single cable; BS EN 62230 (replacing BS EN 50356 and BS 5099) on spark testing.Product certification/inspection/testing. Users of this British Standard are advisedto consider the desirability of third-party certification/inspection/testing ofproduct conformity with this British Standard. Users seeki
14、ng assistance inidentifying appropriate conformity assessment bodies or schemes may ask BSI toforward their enquiries to the relevant association.WARNING. This British Standard calls for the use of substances and/orprocedures that can be injurious to health if adequate precautions are nottaken. It r
15、efers only to technical suitability and does not absolve the userfrom legal obligations relating to health and safety at any stage.Use of this documentIt has been assumed in the preparation of this British Standard that theexecution of its provisions will be entrusted to appropriately qualified ande
16、xperienced people, for whose use it has been produced.Presentational conventionsThe provisions of this standard are presented in roman (i.e. upright) type. Itsrequirements are expressed in sentences in which the principal auxiliary verb is“shall”.Commentary, explanation and general informative mater
17、ial is presented insmaller italic type, and does not constitute a normative element.BRITISH STANDARDBS 7629-1:2015ii The British Standards Institution 2015Contractual and legal considerationsThis publication does not purport to include all the necessary provisions of acontract. Users are responsible
18、 for its correct application.Compliance with a British Standard cannot confer immunity from legalobligations.BRITISH STANDARD BS 7629-1:2015 The British Standards Institution 2015 iiiBRITISH STANDARDBS 7629-1:2015This page deliberately left blankiv The British Standards Institution 20151 ScopeThis B
19、ritish Standard specifies requirements and test methods for theconstruction and performance of cables which: have thermosetting insulation and a rated voltage of 300/500 V; provide resistance to fire (circuit integrity), including with mechanical shockand with water, as measured by performance in a
20、standard test or tests; emit limited amounts of smoke and corrosive gases when burned asmeasured by a standard test; and are primarily intended for use in emergency lighting, fire detection and firealarm system circuits.The circuit integrity performance under fire conditions is assessed on the basis
21、 oftests which measure resistance to fire with mechanical impact and water spray(Categories: Standard 30, Standard 60 and Enhanced 120).NOTE 1 BS 5266-1 and BS 5839-1 give recommendations and guidance on thefactors to be taken into account in the planning, design, installation, commissioningand main
22、tenance of emergency lighting, fire detection and fire alarm systems forbuildings, respectively.It is applicable to 2-core, 3-core and 4-core circular cables with an uninsulatedfull size circuit protective conductor, and 7-core, 12-core and 19-core circularmulti-core auxiliary cables with an uninsul
23、ated drain wire of not less than0.5 mm2. All cables contain a metallic layer, which provides electrostaticscreening.The cables are suitable for operation at a maximum sustained conductortemperature of 70 C and for a maximum short-circuit conductor temperatureof 250 C (for a maximum period of 5 s).NO
24、TE 2 Annex A gives recommendations for the selection, installation andoperation of cables, Annex B gives the method of test for continuity of tinnedcoating of wires, Annex C gives the method of test for voltage withstand, Annex Dgives the method of test for bending characteristics, Annex E gives the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS762912015ELECTRICCABLESSPECIFICATIONFOR300500VFIRERESISTANTSCREENEDFIXEDINSTALLATIONCABLESHAVINGLOWEMISSIONOFSMOKEANDCORROSIVEGASESWHENAFFECTEDBYFIREPDF

链接地址:http://www.mydoc123.com/p-546930.html