《BS 6400-3-2007 Specification for ninstallation exchange nrelocation and removal nof gas meters with a nmaximum capacity not nexceeding 6 m3 h – nPart 3 Low and medium pressure n(3r.pdf》由会员分享,可在线阅读,更多相关《BS 6400-3-2007 Specification for ninstallation exchange nrelocation and removal nof gas meters with a nmaximum capacity not nexceeding 6 m3 h – nPart 3 Low and medium pressure n(3r.pdf(46页珍藏版)》请在麦多课文档分享上搜索。
1、BS 6400-3:2007Specification for installation, exchange, relocation and removal of gas meters with a maximum capacity not exceeding 6 m3/h Part 3: Low and medium pressure (3rd family gases)ICS 91.140.40NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDPublishing an
2、d copyright informationThe BSI copyright notice displayed in this document indicates when the document was last issued. BSI 2007ISBN 978 0 580 53714 1The following BSI references relate to the work on this standard:Committee reference GSE/30Draft for comment 06/30086669 DCPublication historyFirst pu
3、blished November 2007Amendments issued since publicationAmd. no. Date Text affectedBS 6400-3:2007 BSI 2007 iBS 6400-3:2007ContentsForeword iii1 Scope 12 Normative references 23 Terms and definitions 24 Planning and exchange of information 65 Competency 76 Design 77 Installation 218 Gas tightness tes
4、ting and purging 259 Commissioning of the meter installation 2610 Notices 2711 Meter exchange and/or replacement of other gas fitting 3012 Meter relocation 3013 Meter removal 3214 Records 3315 Post installation checks 33AnnexesAnnex A (normative) Sizing of meters 34Annex B (normative) Operational pr
5、essure limits 35Bibliography 37List of figuresFigure 1 Arrangements of a meter installation (symbols to BS 1553-1) 9Figure 2 Connections on 6 m3/h metal case meter 16Figure 3 Connections on 6 m3/h plastic case meters intended for semi-concealed installation 17Figure 4 Typical meter installation noti
6、ces 29List of tablesTable 1 Minimum proximity distances for meter housings and relief valve vent pipe tips (MP installations) 14Table A.1 Diversity factors of appliances for meter sizing 34Table B.1 Operational pressure limits for a regulator conforming to BS EN 13785 which supplies MP (sometimes re
7、ferred to as first stage) 35Table B.2 Operational pressure limits for MP regulator conforming to BS EN 13785 which supplies LP (sometimes referred to as the second stage regulator when used in a three stage system) 35Table B.3.1 Operational pressure limits for a MP or LP regulator conforming to BS E
8、N 13785 which supplies the gas appliance where the downstream equipment has a MOP of 150 mbar 36Table B.3.2 Operational pressure limits for a MP or LP regulator which supplies the gas appliance where the downstream equipment has a MOP of 75 mbar 36Summary of pagesThis document comprises a front cove
9、r, an inside front cover, pages i to iv, pages 1 to 38, an inside back cover and a back cover.BS 6400-3:2007ii BSI 2007 This page deliberately left blank BSI 2007 iiiBS 6400-3:2007ForewordPublishing informationThis British Standard is published by BSI and came into effect on 30 November 2007. It was
10、 prepared by Technical Committee GSE/30, Gas installations (1st, 2nd and 3rd family gases). A list of organizations represented on this committee can be obtained on request to its secretary.SupersessionThis part of BS 6400, along with parts 1 and 2, supersedes BS 6400:1997, which is withdrawn.Relati
11、onship with other publicationsThe standard is issued in three parts: Part 1: Low pressure (2nd family gases); Part 2: Medium pressure (2nd family gases); Part 3: Low and medium pressure (3rd family gases).Terminology within this part might not necessarily be consistent with BS 6400-1 and BS 6400-2,
12、which uses terminology that is consistent with the natural gas industry.Information about this documentThis new edition represents a full revision of BS 6400:1997, and: uses more up-to-date gas industry terminology; reflects changes in structure, practices and product availability in the gas industr
13、y; provides additional information on the installation, exchange, relocation and removal of gas meters with a maximum capacity not exceeding 6 m3/h supplied from low and medium pressure 3rd family gas systems.Hazard warningsUse of this documentIt has been assumed in the preparation of this British S
14、tandard that the execution of its provisions will be entrusted to appropriately qualified and experienced people, for whose use it has been produced.Presentational conventionsThe provisions of this standard are presented in roman (i.e. upright) type. Its requirements are expressed in sentences in wh
15、ich the principal auxiliary verb is “shall”.Commentary, explanation and general informative material is presented in smaller italic type, and does not constitute a normative element.WARNING. This British Standard calls for the use of substances and/or procedures that can be injurious to health if ad
16、equate precautions are not taken. It refers only to technical suitability and does not absolve the user from legal obligations relating to health and safety at any stage.BS 6400-3:2007iv BSI 2007Contractual and legal considerationsAttention is drawn to the following statutory regulations.a) The Gas
17、Safety (Installation and Use) Regulations 1998 1.b) The Gas Safety (Installation and Use) Regulations (Northern Ireland) 2004 2.c) The Gas Safety (Application) Order (Isle of Man) 1996 3.d) The Gas Meters (Information on Connection and Disconnection) Regulations 1996 4.e) The Gas Safety (Management)
18、 Regulations 1996 5.f) The Gas Safety (Management) Regulations (Northern Ireland) 1997 6.g) The Gas (Meters) Regulations 1983 (as amended) 7.h) The Building Regulations 2000 (as amended) 8.i) The Building (Scotland) Regulations 2004 (as amended) 9.j) The Building Regulations (Northern Ireland) 2000
19、(as amended) 10. k) The Measuring Instruments (EEC Requirements) (Gas Volume Meters) Regulations 1988 (as amended) 11.l) The Measuring Instruments (Gas Meters) Regulations 2006 12m) The Dangerous Substances and Explosive Atmospheres Regulations 2002 13.This publication does not purport to include al
20、l the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations. BSI 2007 1BS 6400-3:20071 ScopeThe standard specifies requirements for the installation, exchange, relocation and removal of c
21、redit or prepayment diaphragm and ultrasonic gas meters with a maximum capacity not exceeding 6 m/h.NOTE 1 For the purposes of this standard, installation includes design, inspection and commissioning. It is recognized that each of these tasks can be performed by the same person.This part of BS 6400
22、 is applicable to meter installations:a) supplied with 3rd family gases either:1) from low pressure service pipework with a maximum operating pressure not exceeding 75 mbar and a design maximum incidental pressure of 350 mbar; or2) from medium pressure service pipework with a maximum operating press
23、ure exceeding 75 mbar but not exceeding 2 bar and a design maximum incidental pressure of 2.7 bar;b) only fitted downstream of the emergency control valve;c) that utilizes a meter regulator downstream of the emergency control valve;d) where all gas fittings subjected to medium pressure have been pre
24、-assembled and where strength and gas tightness testing has been undertaken on the regulator assembly at the factory;e) where the operating pressure at the outlet of the meter is nominally 37 mbar.Installation pipework is specified in BS 5482-1 and LPGA Code of Practice 25 14.Service pipework (inclu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS640032007SPECIFICATIONFORNINSTALLATIONEXCHANGENRELOCATIONANDREMOVALNOFGASMETERSWITHANMAXIMUMCAPACITYNOTNEXCEEDING6M3H

链接地址:http://www.mydoc123.com/p-546022.html