《BS 6231-2006 Electric cables - Single core PVC insulated flexible cables of rated voltage 600 1000 V for switchgear and controlgear wiring《电缆 开关装置和控制装置配线用额定电压600 1000V的单芯聚氯乙烯(PVC)绝.pdf》由会员分享,可在线阅读,更多相关《BS 6231-2006 Electric cables - Single core PVC insulated flexible cables of rated voltage 600 1000 V for switchgear and controlgear wiring《电缆 开关装置和控制装置配线用额定电压600 1000V的单芯聚氯乙烯(PVC)绝.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Electric cables Single core PVC insulated flexible cables of rated voltage 600/1000 V for switchgear and controlgear wiringICS 29.060.20NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDBS 6231:2006IncorporatingCorrigendum No. 1Publishing and copyright information
2、The BSI copyright notice displayed in this document indicates when the document was last issued.ISBN 0 580 48589 7The following BSI references relate to the work on this standard:Committee reference GEL/20/17Draft for comment 05/30138592 DCPublication historyFirst published, as BS 1231, July 1945Sec
3、ond edition, November 1958Third edition, February 1963Fourth edition, as BS 6231, August 1969Fifth edition, May 1978Sixth edition, December 1981Seventh edition, October 1990Eighth edition, August 1998Ninth edition, July 2006BS 6231:2006Amendments issued since publicationAmd. no. Date Text affected16
4、677Corrigendum No. 1September 2006 Change reference to 8.1 in 10.4 and Table A.1, change temperature to 90 C in Table 2 BSI 2006 BSI 2006 iBS 6231:2006ContentsForeword ii1 Scope 12 Normative references 13 Terms and definitions 14 Voltage designation 25 Conductors 26 Insulation 27 Identification 38 C
5、able marking 39 Routine tests for finished cables 410 Sample tests for finished cables 411 Type tests for finished cables 5AnnexesAnnex A (normative) Schedule of tests 8Annex B (normative) Measurement of insulation thickness 9Annex C (normative) Test conditions 9Annex D (normative) Method of test fo
6、r voltage withstand 9Bibliography 10List of tablesTable 1 PVC insulated flexible cable - Type BK 6Table 2 PVC insulated flexible cable - Type CK 7Table A.1 Schedule of tests 8Summary of pagesThis document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 10, an inside back c
7、over and a back cover.ii BSI 2006BS 6231:2006ForewordPublishing informationThis British Standard was published by BSI and came into effect on 15 July 2006. It was prepared by Subcommittee GEL/20/17, Low voltage cables, under the authority of Technical Committee GEL/20, Electric cables.Supersession T
8、his British Standard supersedes BS 6231:1998, which is withdrawn.Information about this documentThis new edition of BS 6231 retains requirements in respect of cable types BK and CK only. Requirements for other types have been withdrawn as they are no longer considered to be market relevant.The other
9、 principal changes introduced in this edition are to call up CENELEC harmonized test methods in place of earlier national methods.Product certification/inspection/testing Users of this British Standard are advised to consider the desirability of third-party certification/inspection/testing of produc
10、t conformity with this British Standard. Users seeking assistance in identifying appropriate conformity assessment bodies or schemes may ask BSI to forward their enquiries to the relevant association.WARNING. This British Standard calls for the use of procedures that can be injurious to health if ad
11、equate precautions are not taken. It refers only to technical suitability and does not absolve the user from legal obligations relating to health and safety at any stage.Presentational conventionsThe provisions of this standard are presented in roman (i.e. upright) type. Its requirements are present
12、ed in sentences in which the principal auxiliary verb is “shall”.Commentary, explanation and general informative material is presented in smaller italic type, and does not constitute a normative element.Contractual and legal obligationsThis publication does not purport to include all the necessary p
13、rovisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations. BSI 2006 1BS 6231:20061 ScopeThis British Standard specifies construction and performance requirements, and gives methods of test, for single c
14、ore, non-sheathed electric cables of rated voltage 600/1000 V that have PVC insulation. The types of cable specified in this standard are as follows:Type BK - for a maximum conductor temperature of 70 C (see Table 1);Type CK - for a maximum conductor temperature of 90 C (see Table 2).These cables ar
15、e intended for use in the wiring of switch, control, metering, relay and instrument panels of power switchgear, and for such purposes as internal connections in rectifier equipment and its motor starters and controllers. They are intended for use at alternating voltages not exceeding 600 V to earth,
16、 and direct voltages not exceeding 1000 V to earth. When installed in the equipment they are suitable for wiring circuits for which the prescribed alternating test voltage does not exceed 4 kV r.m.s. for 1 min. A summary of the tests applicable to the cables is given in Annex A.2 Normative reference
17、sThe following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.BS 4727-2: Group 08, Glossary of electrotechnical
18、, power, telecommunication, electronics, lighting and colour terms Part 2: Terms particular to power engineering Group 08: Electric cables.BS 5099, Electric cables Voltage levels for spark testing.BS EN 50356, Method for spark testing of cables.BS EN 50363-3, Insulating, sheathing and covering mater
19、ials for low voltage energy cables Part 3: PVC insulating compoundsBS EN 50395:2005, Electrical test methods for low voltage energy cablesBS EN 50396:2005, Non-electrical test methods for low voltage energy cablesBS EN 60228, Conductors of insulated cablesBS EN 60332-1-2, Tests on electric and optic
20、al fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flameBS EN 60811-1-1, Insulating and sheathing materials of electric cables Common test methods Part 1-1: General application Measurement of thickness
21、 and overall dimensions Tests for determining the mechanical properties.3 Terms and definitionsFor the purposes of this British Standard the definitions given in BS 4727-2: Group 08 apply, together with the following.3.1 rated voltage Unominal power-frequency voltage between phase conductors for whi
22、ch the cable is suitableBS 6231:20062 BSI 20063.2 rated voltage U0nominal power-frequency voltage between conductor(s) and earth for which the cable is suitable 3.3 approximate valuevalue which is only indicativeNOTE In this standard, values described as “approximate” do not constitute requirements
23、to be checked by measurement. 3.4 nominal valuevalue by which a quantity is designatedNOTE Nominal values usually give rise to values to be checked by measurements taking into account specified tolerances.4 Voltage designationCables shall be designated by the rated voltages U0and U, expressed in the
24、 form U0/U.NOTE The rated voltage recognized for the purpose of this British Standard is 600/1000 V.5 ConductorsThe conductors shall conform to BS EN 60228, class 5. The insulated conductors shall be circular, plain annealed copper.6 Insulation6.1 TypesThe insulation shall be type TI 1 as specified
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS62312006ELECTRICCABLESSINGLECOREPVCINSULATEDFLEXIBLECABLESOFRATEDVOLTAGE6001000VFORSWITCHGEARANDCONTROLGEARWIRING

链接地址:http://www.mydoc123.com/p-545878.html