BS 6121-5-2005 Mechanical cable glands - Code of practice for selection installation and inspection of cable glands and armour glands《机械电缆密封套 电缆密封套和铠装密封套的选择 安装和检验的实施规程》.pdf
《BS 6121-5-2005 Mechanical cable glands - Code of practice for selection installation and inspection of cable glands and armour glands《机械电缆密封套 电缆密封套和铠装密封套的选择 安装和检验的实施规程》.pdf》由会员分享,可在线阅读,更多相关《BS 6121-5-2005 Mechanical cable glands - Code of practice for selection installation and inspection of cable glands and armour glands《机械电缆密封套 电缆密封套和铠装密封套的选择 安装和检验的实施规程》.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 6121-5:2005 Mechanical cable glands Part 5: Code of practice for selection, installation and inspection of cable glands and armour glands ICS 21.140; 29.080.20 BS 6121-5:2005 This British Standard was published under the authority of the Standards Policy and Strategy Committee on
2、 21 February 2005 BSI 21 February 2005 First published January 1993 Second edition February 2005 The following BSI references r e l a t e t o t h e w o r k o n t h i s British Standard: Committee reference GEL/20/11/1 Draft for comment 03/308266 DC ISBN 0 580 45375 8 Committees responsible for this
3、British Standard The preparation of this British Standard was entrusted by Technical Committee GEL/20, Electric cables, to Subcommittee GEL/20/11/1, Cable glands, upon which the following bodies were represented: BEAMA Ltd. Council for Electrical Equipment BEAMA Installation Ltd. British Approvals S
4、ervice for Cables British Cables Association Gland Manufacturers Technical Committee Co-opted members Amendments issued since publication Amd. No. Date CommentsBS 6121-5:2005 BSI 21 February 2005 i Contents Page Committees responsible Inside front cover Foreword ii 1S c o p e 1 2 Normative reference
5、s 1 3T e r m s a n d d e f i n i t i o n s 1 4G e n e r a l 2 5 Selection of glands 3 6I n s t a l l a t i o n 8 7 Electrical continuity test 10 8 Inspection and testing 11 Annex A (informative) Cable glands and armour glands corresponding to the type designations given in BS 6121-1:1989 13 Bibliogr
6、aphy 14 Table A.1 Cable glands and armour glands corresponding to the type designations given in BS 6121-1:1989 13BS 6121-5:2005 ii BSI 21 February 2005 Foreword This part of BS 6121 has been prepared by Subcommittee GEL/20/11/1. It supersedes BS 6121-5:1993 which is withdrawn. This part of BS 6121
7、has been updated to refer to the properties of cable glands and armour glands specified in BS EN 50262 and in the new edition of BS 6121-1, respectively, which specify performance, rather than construction as was the case in earlier editions of BS 6121. Some of the testing recommended in BS 6121-5:1
8、993 has been removed because this testing is now specified in BS EN 50262 and/or BS 6121-1. This revision of BS 6121-5 includes new recommendations for selection of glands on the basis of mechanical and electrical properties, as well as new clauses relating electrical properties to installation prac
9、tice. As a code of practice, this part of BS 6121 takes the form of guidance and recommendations. It should not be quoted as if it were a specification and particular care should be taken to ensure that claims of compliance are not misleading. It has been assumed in the drafting of this standard tha
10、t the execution of its provisions will be entrusted to appropriately qualified and competent people, for whose use it has been prepared. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a Briti
11、sh Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 14, an inside back cover and a back cover. The BSI copyright notice displayed in this document indicates when the document
12、was last issued.BS 6121-5:2005 BSI 21 February 2005 1 1 Scope This part of BS 6121 gives recommendations on the selection, installation and inspection of cable glands conforming to BS EN 50262, armour glands conforming to BS 6121-1, and accessories, for industrial, commercial and domestic use. It is
13、 not applicable to glands for use with fibre-optic cables or mineral insulated cables. It is not applicable to glands for installation in explosive atmospheres. NOTE Requirements for installation of electrical equipment in explosive gas atmospheres are specified in BS EN 60079-14. Requirements for i
14、nstallation of electrical equipment in explosive dust atmospheres are specified in BS EN 50281-1-2. This part of BS 6121 is intended for use by specifiers of electrical installations, by installers and by those responsible for carrying out inspections. 2 Normative references The following referenced
15、 documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. BS 6121-1:2005, Mechanical cable glands Part 1: Armour glands Requirement
16、s and test methods. BS 7671:2001 including amendments 1:2002 and 2:2004, Requirements for electrical installations IEE Wiring Regulations. Sixteenth edition. BS EN 50262:1999 including amendments 1:2001 and 2:2004, Cable glands for electrical installations. 3 Terms and definitions For the purposes o
17、f this part of BS 6121, the terms and definitions given in BS EN 50262:1999 and BS 6121-1:2005 and the following apply. 3.1 non-integral earth connection accessory with a means of attaching an additional earth conductor which is fitted to a cable gland or armour gland and which, when installed, prov
18、ides a protective connection to earth NOTE A protective connection to earth is also known as a PE function. 3.2 integral earth connection connection point with a means of attaching an additional earth conductor which is permanently attached to a cable gland or armour gland and which, when installed,
19、 provides a protective connection to earth 3.3 clearance hole hole in the wall of an enclosure which is not threaded internally 3.4 functional earth earth connection required for the correct operation of a piece of equipment NOTE An example of a functional earth is the earth connection to a co-axial
20、 radio-frequency cable or screened data cable. This connection reduces external interference and is essential to the functioning of the equipment; it does not work properly without it. 3.5 circuit protective conductor conductor used to protect people against electric shock by interrupting the supply
21、 in the event of an earth fault and so causing the fuse or circuit breaker to tripBS 6121-5:2005 2 BSI 21 February 2005 4 General 4.1 Properties of glands 4.1.1 BS EN 50262 and BS 6121-1 each specifies requirements to which all glands have to conform in order to be deemed to conform to the respectiv
22、e standard. Each of these standards also specifies additional requirements to which glands have to conform if the manufacturer wishes to claim that the glands have particular additional properties. 4.1.2 BS EN 50262 also provides a “classification” of cable glands according to the material from whic
23、h they are made, their mechanical and electrical properties, the degree of ingress protection they provide and whether they have a single orifice or a multi-orifice seal. 4.1.3 Glands conforming to BS EN 50262 or to BS 6121-1 are supplied with manufacturers information including the following: the m
24、aterial(s) from which the glands have been manufactured; the type of seal (cable glands only); the entry thread length; the range of cable sizes with which the glands can be used; the impact category (indicating the impact resistance on a scale from 1 to 8, where 8 is the highest resistance). 4.1.4
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS612152005MECHANICALCABLEGLANDSCODEOFPRACTICEFORSELECTIONINSTALLATIONANDINSPECTIONOFCABLEGLANDSANDARMOURGLANDS

链接地址:http://www.mydoc123.com/p-545755.html