BS 5682-2015 Dimensions of probes and terminal units for medical gas supply systems Requirements《医疗供气系统用探测器和终端装置尺寸 要求》.pdf
《BS 5682-2015 Dimensions of probes and terminal units for medical gas supply systems Requirements《医疗供气系统用探测器和终端装置尺寸 要求》.pdf》由会员分享,可在线阅读,更多相关《BS 5682-2015 Dimensions of probes and terminal units for medical gas supply systems Requirements《医疗供气系统用探测器和终端装置尺寸 要求》.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、BSI Standards PublicationBS 5682:2015Dimensions of probes andterminal units for medicalgas supply systems RequirementsPublishing and copyright informationThe BSI copyright notice displayed in this document indicates when the documentwas last issued. The British Standards Institution 2015Published by
2、 BSI Standards Limited 2015ISBN 978 0 580 85407 1ICS 11.040.10The following BSI references relate to the work on this document:Committee reference CH/121/6Draft for comment 14/30295295 DCPublication historyFirst published December 1978Second edition May 1984Third edition September 1998Fourth (curren
3、t) edition June 2015Amendments issued since publicationDate Text affectedBS 5682:2015 BRITISH STANDARDContentsContents iiiForeword iv1 Scope 12 Normative references 13 Terms and definitions 14 General requirements 25 Probes 26 Terminal units 47 Marking and colour-coding 6Bibliography 8List of figure
4、sFigure 1 Probe dimensions 3Figure2Terminal unit indexing ring dimensions 6List of tablesTable 1 Diameters of indexing collars and identification symbols of probes 4Table 2 Diameters of indexing rings and identification symbols of terminalunits 5Table 3 Symbols and colour coding for probes and termi
5、nal units 7Summary of pagesThis document comprises a front cover, an inside front cover, pages i to iv,pages 1 to 8, an inside back cover and a back cover.ForewordPublishing informationThis British Standard is published by BSI Standards Limited, under licence fromThe British Standards Institution, a
6、nd came into effect on 30 June 2015. It wasprepared by Subcommittee CH/121/6, Medical gas supply systems, under theauthority of Technical Committee CH/121, Anaesthetic and respiratoryequipment. A list of organizations represented on this committee can beobtained on request to its secretary.Supersess
7、ionThis British Standard supersedes BS 5682:1998, which is withdrawn.Information about this documentThis is a full revision of the standard, which takes account of productdevelopment and changes in products since the last edition. Its principal changesare:a) introduction of dimensions for probes and
8、 terminal outlets forhelium/oxygen mixtures;b) specifications for the dimensions of the terminal outlets for all specifiedmedical gases.Presentational conventionsThe provisions of this standard are presented in roman (i.e. upright) type. Itsrequirements are expressed in sentences in which the princi
9、pal auxiliary verb is“shall”.Commentary, explanation and general informative material is presented insmaller italic type, and does not constitute a normative element.Requirements in this standard are drafted in accordance with Rules for thestructure and drafting of UK standards, subclause J.1.1, whi
10、ch states,“Requirements should be expressed using wording such as: When tested asdescribed in Annex A, the product shall .”. This means that only those productsthat are capable of passing the specified test will be deemed to conform to thisstandard.Contractual and legal considerationsThis publicatio
11、n does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legalobligationsBS 5682:2015 BRITISH STANDARD1 ScopeThis British Standard specifies dimensions for probes and term
12、inal units for thesupply of medical gases (including vacuum).It is applicable to probes and terminal units for the following medical gases: oxygen; nitrous oxide; oxygen/nitrous oxide mixture; medical air 400 kPa; medical air 700 kPa and above; helium/oxygen mixture; and vacuum.This standard does no
13、t include specifications for probes and terminal units for: nitrogen for driving surgical tools; carbon dioxide; or oxygen 93.2 Normative referencesThe following documents, in whole or in part, are normatively referenced in thisdocument and are indispensable for its application. For dated references
14、, onlythe edition cited applies. For undated references, the latest edition of thereferenced document (including any amendments) applies.BS EN ISO 18082, Anaesthetic and respiratory equipment Dimensions ofnon-interchangeable screw-threaded (NIST) low-pressure connectors for medicalgasesBS EN ISO 535
15、9, Anaesthetic and respiratory equipment Low-pressure hoseassemblies for use with medical gasesBS EN ISO 6506-1, Metallic materials Brinell hardness test Test methodBS EN ISO 9170-1:2008, Terminal units for medical gas pipeline systems Terminal units for use with compressed medical gases and vacuumI
16、SO 32, Gas cylinders for medical use Marking for identification of content3 Terms and definitionsFor the purposes of this British Standard, the terms and definitions given inBS EN ISO 9170-1 and the following apply.3.1 direct probeintegral part of a medical device that connects to a terminal unit3.2
17、 probegas-specific male component designed for acceptance by and retention in thesocket of a terminal unitSOURCE: BS EN 9170-1:2008, 3.113.3 probe insertportion of a probe pushed into and secured within the bore (lumen) of the hoseNOTE Probe inserts are also known as probe tails or probe spigots.BRI
18、TISH STANDARD BS 5682:2015 The British Standards Institution 2015 13.4 remote probepart of a hose assembly that connects to a terminal unit3.5 terminal unitoutlet assembly (inlet for vacuum) of a medical gas supply system at which theoperator makes connections and disconnectionsSOURCE: BS EN ISO 917
19、0-1:2008, 3.154 General requirementsThe safety, materials, design and construction of the probes and terminal unitsshall be in accordance with BS EN ISO 9170-1.5 Probes5.1 The probes shall conform to the dimensions detailed in Figure 1, and Table1. The shoulder of the probe-indexing collar shall hav
20、e a diameter no greaterthan diameter A and shall not extend beyond 46 mm from the tip of the probe.NOTE The restriction on the distance from the tip of the probe to the shoulderof the probe indexing collar is to allow access to the mechanism for releasing theprobe from the terminal unit when install
21、ed.5.2 Remote probes shall be provided with a probe insert to suit the appropriatehose as specified in BS EN ISO 5359.5.3 Direct probes shall be either an integral part of a medical device, notintended to be dismantled by the user, or shall incorporate the body of theappropriate non-interchangeable
22、screw-threaded (NIST) connector as specified inBS EN ISO 18082.5.4 The coupling between a direct probe and a medical device shall permitaccess to the probe release mechanism on the terminal units.NOTE See note to 5.1.5.5 With the exception of the locating slot, the gas-specific indexing collar ofthe
23、 Probe shall be a fully formed annulus.5.6 The gas-specific indexing collar and probe shall be machined or formed froma single piece in order to maintain the concentricity of the component, i.e. thecollar shall not be comprised of a separately manufactured component.5.7 The material used for probes
24、shall have a minimum hardness value of 120HBW 2.5/62.5 when tested in accordance with BS EN ISO 6506-1.NOTE 1 The mechanical properties of the probes are specified to minimize the riskof cross-connection in conditions of normal use and reasonably foreseeable misuse.NOTE 2 Hardness equivalence tables
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS56822015DIMENSIONSOFPROBESANDTERMINALUNITSFORMEDICALGASSUPPLYSYSTEMSREQUIREMENTS 医疗 供气 系统 探测器 终端 装置

链接地址:http://www.mydoc123.com/p-545304.html