AWWA C510-2007 Double Check Valve Backflow Prevention Assembly《双止回阀倒流防止器》.pdf
《AWWA C510-2007 Double Check Valve Backflow Prevention Assembly《双止回阀倒流防止器》.pdf》由会员分享,可在线阅读,更多相关《AWWA C510-2007 Double Check Valve Backflow Prevention Assembly《双止回阀倒流防止器》.pdf(28页珍藏版)》请在麦多课文档分享上搜索。
1、The Authoritative Resource for Safe WaterANSI/AWWA C510-07(Revision of ANSI/AWWA C510-97)AWWA StandardEffective date: Oct. 1, 2008.This first edition approved by AWWA Board of Directors Jan 27, 1969.This edition approved June 24, 2007.Approved by American National Standards Institute July 24, 2008.D
2、ouble Check Valve Backflow Prevention Assembly6666 West Quincy AvenueDenver, CO 80235-3098T 800.926.7337www.awwa.orgAdvocacyCommunicationsConferencesEducation and TrainingScience and TechnologySectionsiiAWWA StandardThis document is an American Water Works Association (AWWA) standard. It is not a sp
3、ecification. AWWA standardsdescribe minimum requirements and do not contain all of the engineering and administrative information normallycontained in specifications. The AWWA standards usually contain options that must be evaluated by the user of thestandard. Until each optional feature is specifie
4、d by the user, the product or service is not fully defined. AWWApublication of a standard does not constitute endorsement of any product or product type, nor does AWWA test, certify,or approve any product. The use of AWWA standards is entirely voluntary. This standard does not supersede or takeprece
5、dence over or displace any applicable law, regulation, or codes of any governmental authority. AWWA standardsare intended to represent a consensus of the water supply industry that the product described will provide satisfactoryservice. When AWWA revises or withdraws this standard, an official notic
6、e of action will be placed on the first page ofthe classified advertising section of Journal AWWA. The action becomes effective on the first day of the month followingthe month of Journal AWWA publication of the official notice.American National StandardAn American National Standard implies a consen
7、sus of those substantially concerned with its scope and provisions. AnAmerican National Standard is intended as a guide to aid the manufacturer, the consumer, and the general public. Theexistence of an American National Standard does not in any respect preclude anyone, whether that person hasapprove
8、d the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or proceduresnot conforming to the standard. American National Standards are subject to periodic review, and users are cautionedto obtain the latest editions. Producers of goods made in conformity with an
9、 American National Standard areencouraged to state on their own responsibility in advertising and promotional materials or on tags or labels that thegoods are produced in conformity with particular American National Standards.CAUTION NOTICE: The American National Standards Institute (ANSI) approval
10、date on the front cover of this standardindicates completion of the ANSI approval process. This American National Standard may be revised or withdrawn atany time. ANSI procedures require that action be taken to reaffirm, revise, or withdraw this standard no later than fiveyears from the date of publ
11、ication. Purchasers of American National Standards may receive current information on allstandards by calling or writing the American National Standards Institute, 25 West 43rd Street, Fourth Floor, New York,NY 10036; (212) 642-4900.All rights reserved. No part of this publication may be reproduced
12、or transmitted in any form or by any means, electronicor mechanical, including photocopy, recording, or any information or retrieval system, except in the form of briefexcerpts or quotations for review purposes, without the written permission of the publisher. Copyright 2008 by American Water Works
13、AssociationPrinted in USAiiiCommittee PersonnelThe AWWA Standards Committee on Backflow Preventers, which reviewed and approvedthis standard, had the following personnel at the time of approval:James T. Cowgill, ChairRichard A. Coates, SecretaryGeneral Interest MembersS.F. Asay, Drinking Water thatm
14、oving parts do not bind or gall; and that there be no distortion that will interferewith the intended performance of the assembly. Flow channels shall be streamlined toprevent cavitation, minimize pressure loss, and eliminate pockets that could entrapforeign materials.4.3.1.1 Access to internal part
15、s. Internal wetted parts shall be accessible forinspection, repair, and renewal without disturbing either the structural integrity ofthe piping system or the integrity of the shutoff valves to isolate the backflowpreventer by the removal of the assembly from the line, using the shutoff valves toisol
16、ate the assembly.4.3.1.2 Connections. End connections, test cocks, and control pipingconnections to components of the backflow prevention assembly shall be eitherthreaded in accordance with ASME B1.20.1, or flanged in accordance with ASMEB16.1, ASME B16.24, or ANSI/AWWA C110/A21.10, or grooved and s
17、houlderedjoints per ANSI/AWWA C606.4.3.1.3 Test cocks. Resilient-seated full-ported test cocks shall be attached tocorrosion-resistant nipples or shall have male threads to be installed in tapped holes. Ateach location on a valve body where such a tapped hole is required, there shall be a bossto per
18、mit sufficient threading for nipples. Test cocks shall have female iron pipe size(IPS) ends on the discharge side. Test connections of 1/8 in. (3 mm) shall be permittedto be either IPS female threads or male in. (6 mm) flared-type connections perSAE J513. The minimum sizes (IPS) of test cocks shall
19、be 1/8 in. (3 mm) forassemblies up to and including 1-in. (25-mm) nominal size; 1/4 in. (6 mm) forassemblies up to and including 2-in. (50-mm) nominal size; 1/2 in. (12 mm) forassemblies 21/2-in. through 4-in. (63-mm through 100-mm) nominal size; and 3/4 in.(19 mm) for assemblies 6 in. (150 mm) and
20、larger. Test cocks shall be installed at thefollowing locations on backflow prevention assemblies:8 AWWA C510-071. On the supply (inlet) side of the supply shutoff valve.NOTE: The #1 test cock is not required for the 1/4-in. and 3/8-in. sizeassemblies.2. Between the supply shutoff valve and the firs
21、t check valve.3. Between the check valves.4. Between the second check valve and the shutoff valve on the outlet side ofthe assembly.4.3.1.4 Valve seats. Provision shall be made for renewal and replacement ofvalve seats.4.3.1.5 Alignment of check valves. Each clapper disk, facing ring, andclamping an
22、d securing bolt or stud shall be concentric to an axis that is normal to theface of the facing ring. When applicable, the unit shall be designed so that the facingring may be clamped and reclamped without warping its face. The clapper must notbe able to tip and catch under the seat ring. When clappe
23、rs or poppets are in awide-open position, they must bear on a definite stop that is so designed and placedthat the action of the water will not twist or bend the valve parts or cause them tochatter. The design shall be such that at any flow rate, from zero to (and including)rated flow, the component
24、 parts shall not create any chatter or noise. Working partsshall be designed and supported in a manner to preclude distortion or misalignment.4.3.1.6 Shutoff valves. Shutoff valves shall be resilient seated. Shutoff valvesshall be considered an integral part of the assembly and shall meet the materi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。