1、Designation: E 1513 93 (Reapproved 2005)e1Standard Practice forApplication of Sprayed Fire-Resistive Materials (SFRMs)1This standard is issued under the fixed designation E 1513; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.e1NOTEWarning notes were editorially moved into text in May 2005.1. Scope1.1 This practice covers guidelines for applicat
3、ion ofsprayed fiber and cementitious fire-resistive materials.1.2 This practice is general in nature. It is not intended tocover all requirements for application.1.3 The values stated in both inch-pound and SI units are tobe regarded separately as the standard. The values given inparentheses are for
4、 information only.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to u
5、se. Specific precau-tionary statements are given in Section 10 and 14.1.2.2. Referenced Documents2.1 ASTM Standards:2E119 Test Methods for Fire Tests of Building Constructionand MaterialsE 605 Test Methods for Thickness and Density of SprayedFire-Resistive Material (SFRM) Applied to StructuralMember
6、sE 631 Terminology of Building ConstructionsE 736 Test Method for Cohesion/Adhesion of Sprayed Fire-Resistive Materials Applied to Structural MembersE 759 Test Method for Effect of Deflection of SprayedFire-Resistive Material Applied to Structural MembersE 760 Test Method for Effect of Impact on Bon
7、ding ofSprayed Fire-Resistive Material Applied to StructuralMembersE 1368 Practice for Visual Inspection of Asbestos Abate-ment Projects3. Terminology3.1 Definitions:3.1.1 Many items in this practice are defined in TerminologyE 631.3.2 Definitions of Terms Specific to This Standard:3.2.1 application
8、, nan act of applying sprayed fire-resistive materials.3.2.2 sprayed cementitious material, nconsisting of oneor more binders, aggregates, and fibers, the material is mixedwith water to form a slurry and is conveyed through a hose toa nozzle where compressed air is typically used to disperse themate
9、rial into a spray pattern and directed to the substraterequiring protection.3.2.3 sprayed fire-resistive materials (SFRM), nmaterialsthat are sprayed onto substrates to provide fire-resistive pro-tection of the substrates.3.2.4 sprayed mineral fiber material, nconsisting of oneor more binders, fiber
10、s, and aggregates, the material is con-veyed by low pressure air through a hose to a nozzle where itis mixed with atomized water and directed to the substraterequiring protection.4. Summary of Practice4.1 This practice describes the procedures for selecting,specifying, applying, and testing SFRM.5.
11、Significance and Use5.1 This practice is intended for use by the material speci-fier, general contractor, applicator, or any individual grouprequiring information regarding the application of SFRM.1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the
12、direct responsibility of Subcommittee E06.21 onServiceability.Current edition approved May 1, 2005. Published May 2005. Originallyapproved in 1993. Last pevious edition approved in 2000 as E 1513 93 (2000).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer
13、Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5.2 This practice is not intended to rep
14、lace the manufactur-ers application instructions.6. Materials6.1 The SFRM shall be either sprayed fiber or cementitioustypes. The material shall be manufactured in accordance withthe manufacturers specifications and quality control proce-dures. The material shall be free of any contamination thatcou
15、ld impair its performance.7. Storage and Handling7.1 All materials shall be delivered to the job site in clearlylabeled, unopened bags. Labels shall include the manufacturer,product name, surface burning characteristics of the product,and list of appropriate fire resistance classified assemblies inw
16、hich the product is a component.7.2 Materials with a shelf life shall be used within thatperiod. Materials that have gone beyond their shelf life shall beremoved from the job site, or manufacturer shall providedocumentation attesting that the product is still usable for itsoriginal intended purpose.
17、7.3 Materials shall be kept dry until used and stored off theground under cover.8. Equipment and Utilities8.1 Equipment used for application shall be of a typerecommended by the SFRM manufacturer. Equipment shallinclude, but is not limited to: application machine, materialmixer, material hoses, stan
18、d pipe, and spray nozzles.8.2 The following utilities are typically provided by thegeneral contractor: electricity, potable water, and lighting.8.3 The following utilities may be needed depending uponjob conditions and, if needed, shall be provided by the generalcontractor:8.3.1 Heating (see 12.1.1)
19、, and8.3.2 Forced ventilation (see 12.1.2).9. Fire Resistance Classifications9.1 GeneralRequired fire resistance classifications areoutlined by building codes such as those published by BOCA,3SBCCI,4ICBO5and enforced by local authorities havingjurisdiction. Required fire resistance classifications a
20、re deter-mined by construction type, occupancy, and location.9.2 Architects and material specifiers shall indicate onconstruction drawings and in specifications the required fireresistance classification(s) for a project. They shall also indi-cate what elements of that project are to be so protected
21、. (SeeNote 1.)NOTE 1The architect and material specifier may indicate on construc-tion drawings and in specifications a reference number for a fire resistancesystem capable of providing the required protection.10. Safety10.1 Current OSHA, applicable local ordinances, or coderegulations shall be foll
22、owed at all times.10.1.1 Equipment shall have safety guards that meet appli-cable OSHA regulations in place. Grounded electrical connec-tions shall be used.10.1.2 Protective EquipmentAll persons in the applica-tion area shall wear protective equipment as required. Ex-amples of equipment that may be
23、needed are: respirators, dustmasks, coveralls, goggles or safety glasses, and hard hats.10.1.3 Workmen shall not wear loose fitting clothing thatcould become caught in the machinery. However, that person-nel actually spraying product may wear loose, long sleeveclothing for protection and comfort rea
24、sons.10.1.4 ScaffoldWhen required, a strong, lightweight,stable, rolling scaffold shall be used. An open grate flooringwill help prevent material build up on the scaffold floor. Safetyrailing meeting OSHA regulations shall surround the scaffoldfloor area.10.1.5 FloorsThe floors in the work area shal
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME151319932005E1STANDARDPRACTICEFORAPPLICATIONOFSPRAYEDFIRERESISTIVEMATERIALSSFRMS 喷涂 耐火材料 应用 SFRMSPDF

链接地址:http://www.mydoc123.com/p-528844.html