ASTM D4637-2004 Standard Specification for EPDM Sheet Used In Single-Ply Roof Membrane《单层屋顶防渗护面中使用的乙丙三元橡胶薄板标准规范》.pdf
《ASTM D4637-2004 Standard Specification for EPDM Sheet Used In Single-Ply Roof Membrane《单层屋顶防渗护面中使用的乙丙三元橡胶薄板标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D4637-2004 Standard Specification for EPDM Sheet Used In Single-Ply Roof Membrane《单层屋顶防渗护面中使用的乙丙三元橡胶薄板标准规范》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 4637 04Standard Specification forEPDM Sheet Used In Single-Ply Roof Membrane1This standard is issued under the fixed designation D 4637; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A nu
2、mber in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers flexible sheet made fromethyl
3、ene-propylene-diene terpolymer (EPDM) intended for usein single-ply roofing membranes exposed to the weather. Thetests and property limits used to characterize the sheet arevalues to ensure minimum quality for the intended use. Thesheet may be non-reinforced, fabric- or scrim-reinforced, orfabric-ba
4、cked vulcanized rubber sheet.1.2 In-place roof system design criteria, such as fire resis-tance, field seaming strength, material compatibility, and upliftresistance, among others, are factors that must be consideredbut are beyond the scope of this specification.1.3 The values stated in SI units are
5、 to be regarded as thestandard. The values stated in parentheses are for informationonly.1.4 This standard may involve hazardous materials, opera-tions, and equipment. This standard does not purport toaddress all of the safety concerns, if any, associated with itsuse. It is the responsibility of the
6、 user of this standard toestablish appropriate safety and health practices and deter-mine the applicability of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 412 Test Methods for Vulcanized Rubber and Thermo-plastic ElastomersTensionD 413 Test Methods for Rubber Pro
7、pertyAdhesion toFlexible SubstrateD 471 Test Method for Rubber PropertyEffect of LiquidsD 518 Test Method for Rubber DeteriorationSurfaceCrackingD 573 Test Method for RubberDeterioration in an AirOvenD 624 Test Method for Tear Strength of ConventionalVulcanized Rubber and Thermoplastic ElastomersD 7
8、51 Test Methods for Coated FabricsD 816 Test Methods for Rubber CementsD 1149 Test Method for Rubber DeteriorationSurfaceOzone Cracking in a ChamberD 1204 Test Method for Linear Dimensional Changes ofNonrigid Thermoplastic Sheeting or Film at ElevatedTemperatureD 2137 Test Methods for Rubber Propert
9、yBrittlenessPoint of Flexible Polymers and Coated FabricsD 5602 Test Method for Static Puncture Resistance ofRoofing Membrane SpecimensD 5635 Test Method for Dynamic Puncture Resistance ofRoofing Membrane SpecimensG 151 Practice for Exposing Nonmetallic Materials in Ac-celerated Test Devices that Us
10、e Laboratory Light SourcesG 155 Practice for Operating Xenon Arc Light Apparatusfor Exposure of Non-Metallic Materials3. Classification3.1 Types describe the sheet construction:3.1.1 Type INon-reinforced.3.1.2 Type IIScrim (or fabric) internally reinforced.3.1.3 Type IIIFabric backed.4. Materials an
11、d Manufacture4.1 The sheet shall be formulated from EPDM polymers andother compounding ingredients. EPDM shall be the principalpolymer used in the sheet and shall be greater than 95 % of thetotal polymer content.4.2 To make seams and repairs, the sheet shall be capable ofbeing bonded watertight to i
12、tself and the supplier or fabricatorshall recommend suitable methods.5. Physical Properties and Tolerances5.1 The sheet shall conform to the physical requirementsprescribed in Table 1.5.2 The tolerance for time conditions (aging, weathering,and so forth) is 615 min or 61 % of the period; whichever i
13、sgreater, unless otherwise specified.5.3 Tolerances for temperature shall be 62C (64F).1This specification is under the jurisdiction of ASTM Committee D08 onRoofing and Waterproofing and is the direct responsibility of Subcommittee D08.18on Nonbituminous Organic Roof Coverings.Current edition approv
14、ed Aug. 1, 2004. Published August 2004. Originallyapproved in 1987. Last previous edition approved in 2003 as D 4637 03.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer
15、 to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.6. Dimensions6.1 The width and length of the sheet shall be agreed uponbetween the purchaser and the supplier.6.1.1 The width
16、and length tolerance shall be +3 %, 0 %.6.2 The thickness tolerance shall be +15 %, 10 % of thethickness agreed upon between the purchaser and supplier, butin no case shall the thickness be less than the minimum listedin Table 1.7. Workmanship, Finish, and Appearance7.1 The sheet, including the full
17、 width of factory seams ifpresent, shall be fully adhered, watertight, and visibly free ofpinholes, particles of foreign matter, undispersed raw material,or other manufacturing defects that might affect serviceability.If the number of irregularities in the form of pockmarks (seeNote 1) appear excess
18、ive on the sheet (or portion thereof), thenits rejection shall be negotiated between involved parties.7.2 Edges of the sheets shall be straight and flat so that theymay be seamed to one another without fishmouthing.NOTE 1Pockmarks are oblong depressions, cavities, or craters on thesurface of the she
19、et that have an approximate surface dimension of 3.2 by1.6 mm (18 by116 in.), and have a maximum depth approaching one halfof the sheet thickness.8. Test Methods8.1 DimensionsTest Methods D 751, after permitting thesheet to relax at 23 6 2C (73.4 6 4F) for 1 h 6 15 min.8.2 Thickness, Sheet OverallFr
20、om across the full width ofthe unbuffed sheet, take three samples, 300 by 300 mm (1 by1 ft). Measure the thickness of each corner. On fabric backed(Type III) the coating thickness can be measured after cuttingor buffing fabric from the rubber. Refer to Test Method D 412for Type I sheet and Test Meth
21、od D 751 for Type II and TypeIII sheet.8.3 Thickness of Coating Over Scrim (ReinforcingFabric)Optical Method, see Annex A1.8.4 Breaking StrengthTest Methods D 751, Grab Method.8.5 Tensile StrengthTest Methods D 412, Die C.8.6 Dynamic Puncture ResistanceTest Method D 5635, atan energy of 5 J min at 2
22、3 6 2C (73.4 6 4F) for Type I andan energy of 10 J min for Type II.8.7 Static Puncture ResistanceTest Method D 5602, at aload of 20 kg (44.1 lbf) min for Type I and a load of 25 kg (55.1lbf) min for Type II at 23 6 2C (73.4 6 4F).8.8 Elongation, UltimateTest Methods D 412, Die C.8.9 Elongation at Fa
23、bric Break, UltimateTest MethodD 751, Grab Method, 50 mm (2 in.) per minute jaw separationrate.8.10 Tensile SetTest Methods D 412, Method A, Die C,50 % elongation.8.11 Tear ResistanceTest Method D 624, Die C.8.12 Tearing StrengthTest Methods D 751, B-TongueTear.8.13 Brittleness PointTest Methods D 2
24、137.8.14 Ozone ResistanceTest Method D 1149. Inspect at73 magnification on specimens exposed to 100 mPa (1 3 105psi) ozone in air at 40 6 2C (104 6 4F). Elongate Type Ispecimens 50 % for 166 6 1.66 h exposure. Type II and TypeIII specimens must be wrapped around a 75 mm (3 in.)diameter mandrel for 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD46372004STANDARDSPECIFICATIONFOREPDMSHEETUSEDINSINGLEPLYROOFMEMBRANE 单层 屋顶 防渗 护面中 使用 三元 橡胶 薄板 标准规范

链接地址:http://www.mydoc123.com/p-517574.html