1、Designation: C610 11Standard Specification forMolded Expanded Perlite Block and Pipe ThermalInsulation1This standard is issued under the fixed designation C610; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revis
2、ion. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers molded expanded perli
3、teblock, fittings, and pipe thermal insulation intended for use onsurfaces with temperatures between 80 to 1200F (27 to649C).1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for informat
4、ion onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory
5、limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C165 Test Method for Measuring Compressive Propertiesof Thermal InsulationsC168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe G
6、uarded-Hot-Plate ApparatusC203 Test Methods for Breaking Load and Flexural Prop-erties of Block-Type Thermal InsulationC302 Test Method for Density and Dimensions of Pre-formed Pipe-Covering-Type Thermal InsulationC303 Test Method for Dimensions and Density of Pre-formed Block and BoardType Thermal
7、InsulationC335 Test Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC356 Test Method for Linear Shrinkage of PreformedHigh-Temperature Thermal Insulation Subjected to Soak-ing HeatC390 Practice for Sampling and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface
8、Performance of High-Temperature Thermal InsulationC421 Test Method for Tumbling Friability of PreformedBlock-Type and Preformed Pipe-Covering-Type ThermalInsulationC450 Practice for Fabrication of Thermal Insulating FittingCovers for NPS Piping, and Vessel LaggingC518 Test Method for Steady-State Th
9、ermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC585 Practice for Inner and Outer Diameters of ThermalInsulation for Nominal Sizes of Pipe and TubingC795 Specification for Thermal Insulation for Use in Con-tact with Austenitic Stainless SteelC1045 Practice for CalculatingTherma
10、lTransmission Prop-erties Under Steady-State ConditionsC1058 Practice for Selecting Temperatures for Evaluatingand Reporting Thermal Properties of Thermal InsulationC1616 Test Method for Determining the Moisture Contentof Organic and Inorganic Insulation Materials by WeightE84 Test Method for Surfac
11、e Burning Characteristics ofBuilding MaterialsE136 Test Method for Behavior of Materials in a VerticalTube Furnace at 750C3. Standard Shapes, Sizes, and Dimensions3.1 Molded expanded perlite block, fitting, and pipe thermalinsulation shall be as follows:3.1.1 BlockBlock shall be furnished in lengths
12、 of either36 or 39.4 in. (914 or 1000 mm), widths of 6 in. (152 mm), 12in. (305 mm), 18 in. (457 mm), or 24 in. (610 mm), and inthickness from 112 to 6 in. (38 to 152 mm) in increments of12in. (13 mm).3.1.2 Pipe InsulationMolded expanded perlite pipe insu-lation shall be supplied either as hollow cy
13、lindrical shapes splitin half lengthwise (in a plane including the cylindrical axis) orcurved segments. The pipe insulation shall be furnished in1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.20 onHomogene
14、ous Inorganic Thermal Insulations.Current edition approved Sept. 1, 2011. Published December 2011. Originallyapproved in 1967. Last previous edition approved in 2010 as C610 10. DOI:10.1520/C0610-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service
15、 at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.sections or segments in lengths of either 36 or
16、 39.4 in. (914 or1000 mm) to fit standard sizes of pipe and tubing, and innominal thickness from 1 to 4 in. (25 to 102 mm) in12-in.(13-mm) increments. Inner and outer diameters of multilayerconstruction shall be specified. Inner and outer diameters shallbe in accordance with those standard dimension
17、s specified inPractice C585. Since outside diameter tolerances differ be-tween individual manufacturing processes, it is acceptable tohave pipe insulation furnished in two or more layers nested bythe manufacturer. The purchaser shall consult the manufacturerfor specific requirements.3.1.3 FittingsMo
18、lded (expanded insulation fittings shallconform to the inner and outer diameters in accordance withPractice C585. Mitered fittings shall be in accordance withPractice C450.4. Description4.1 Compositionmolded expanded perlite block, fitting,and pipe thermal insulation shall be composed principally of
19、expanded perlite and silicate binders may contain reinforcingfibers.5. Dimensional Tolerances5.1 GeneralThe average tolerances for length, width, andthickness shall comply with the requirements shown in Table 1.5.2 Pipe InsulationThe following additional tolerancesapply to perlite pipe insulation su
20、pplied as half sections:5.2.1 Fit and ClosureWhen fitted to the appropriate sizepipe, the longitudinal seam of the pipe insulation shall close towithin116 in. (1.6 mm) along the entire length of the section.5.2.2 ConcentricityThe inner bore of the pipe insulationshall be concentric with the outer cy
21、lindrical surface. Thedeviation from concentricity shall not exceed18 in. (3.2 mm)or 5 % of the wall thickness, whichever is greater.5.2.3 Half-Section BalanceThe plane formed by the splitbetween half sections shall include the cylindrical axis. Devia-tion of the split plane from the cylinder axis o
22、ver the 36 or39.4-in. (914 or 1000-mm) length shall not exceed18 in. (3.2mm).6. Workmanship, Finish, and Appearance6.1 Since some requirements for this material are not easilydefined by a numerical value, the insulation shall not havevisible defects that will adversely affect its service qualities.7
23、. Physical Requirements7.1 The insulation shall conform to the physical require-ments in Table 2.8. Sampling8.1 The insulation shall be sampled in accordance withPractice C390. Specific provision for sampling shall be agreedupon between the purchaser and the supplier.9. Qualification Requirements9.1
24、 The following requirements are generally employed forpurpose of initial material or product qualification:9.1.1 Flexural strength,9.1.2 Compressive resistance,9.1.3 Surface burning characteristics,9.1.4 Linear shrinkage after soaking heat,9.1.5 Water absorption after heat aging,9.1.6 Apparent therm
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC6102011STANDARDSPECIFICATIONFORMOLDEDEXPANDEDPERLITEBLOCKANDPIPETHERMALINSULATION 膨胀 珍珠岩 管道 保温 标准规范

链接地址:http://www.mydoc123.com/p-507755.html