ASTM C411-2005 Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation《高温隔热材料受热面性能的标准试验方法》.pdf
《ASTM C411-2005 Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation《高温隔热材料受热面性能的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM C411-2005 Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation《高温隔热材料受热面性能的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 411 05Standard Test Method forHot-Surface Performance of High-Temperature ThermalInsulation1This standard is issued under the fixed designation C 411; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last
2、revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This test method covers the determination
3、 of the perfor-mance of commercial sizes of both block and pipe forms ofthermal insulating materials when exposed to simulated hot-surface application conditions. The term “hot-surface perfor-mance” has reference to a simulated use-temperature test inwhich the heated testing surface is in a horizont
4、al position.1.2 This test method refers primarily to high-temperatureinsulations that are applicable to hot-side temperatures inexcess of 200F (93C). It is used for materials such aspreformed insulations, insulating cements, blankets, and thelike, by proper laboratory preparation of the samples.1.3
5、The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are forinformation only.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish
6、 appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 168 Terminology Relating to Thermal Insulation3. Terminology3.1 DefinitionsTerminology C 168 shall apply to theterms used in this test method
7、.4. Significance and Use4.1 Performance in service is the final measure of value fora thermal insulation, but simulative service tests give usefulindications. One type involves application for a specified timeto a surface heated at a temperature approximately that ofintended service, and noting duri
8、ng the test and afterward,changes in the material and its properties. Measurement ofthese changes are used for predicting what occurs in service asa result of exposure to temperatures corresponding to those ofthe tests.5. Apparatus5.1 Heating PlateThe heating plate shall consist of acorrosion-resist
9、ant and heat-resistant plate with a preferredexposed test area of 36 by 18 in. (914 by 457 mm), but havinga minimum test area of 18 by 18 in. (457 by 457 mm). Theheated area shall have an insulated, heated guard area having aminimum width of 3 in. (76 mm) around the entire periphery ofthe test area.
10、 The plate shall be supported in a horizontal planeat a sufficient number of points to prevent sagging. It shall beheated on the under side by gas or electricity. The surfacetemperature of the plate shall be measured by not less than fivethermocouples. Four of the thermocouples shall be locatedalong
11、 the diagonals that extend from the corners of the exposedarea of the plate and at a distance of 6 in. (152 mm) in fromeach corner. A fifth thermocouple shall be located near thecenter of the test plate area. The temperature at no point ofmeasurement shall vary more than 65%or625F (614C),whichever i
12、s less, from the desired temperature. A heatingchamber beneath the heating plate shall be formed to retain theheat generated by the heating means. A 6-in. thickness ofinsulation shall form the bottom and the sides, and the heatingplate shall form the top of the chamber. Two suitable types ofheating
13、plates are shown in Fig. 1 and Fig. 2.5.2 Heating PipeThe heating pipe shall consist of acorrosion-resistant and heat-resistant pipe having a length ofnot less than 3 ft (0.9 m) and preferably 6 ft 6 in. (1.98 m). Itshall be supported horizontally. The nominal diameter of thepipe shall preferably be
14、 3 in. (76 mm). The pipe shall be heatedelectrically with a spiral heating coil placed along the inside ofthe pipe. Supplementary end heaters, and a guard section atleast 3 in. long of the same insulation as that being placed onthe test section, shall also be provided to guard againstexcessive losse
15、s from the ends of the test specimen. (Wherepossible, the use of standard thermal conductivity pipe test1This test method is under the jurisdiction ofASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.31 on Chemical andPhysical Properties.Current edition app
16、roved Nov. 1, 2005. Published December 2005. Originallyapproved in 1958. Last previous edition approved in 2004 as C 411 04.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, r
17、efer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.apparatus to serve as the heating pipe is recommended.) Thesurface temperature of the pipe shall be measured by means ofth
18、ermocouples, not less than one for each 1 ft (0.3 m) of lengthof the test specimen, and located spirally around the pipe at 90intervals. The test portion of the pipe shall be that area undera full length of a pipe insulation undergoing test. The tempera-ture at any point of measurement on the test p
19、ortion shall notvary more than 65%or625F (614C), whichever is less,from the desired temperature.5.3 Temperature MeasurementThermocouples shall beused to measure the surface temperature of the heating plateand the heating pipe. They shall be applied either by peeningthe individual wires into small ho
20、les drilled into the surface andseparated by not more than18 in. (3 mm) or by joining thewires with a welded bead and cementing them in grooves withthe bead tangent to the surface but not projecting above it. Thethermocouples shall be made from wires having a size notgreater than No. 22 Awg (0.644 m
21、m), and preferably not largerthan No. 26 Awg (0.405 mm). The combination of thethermocouple and measuring instrument used shall ensure anaccuracy of temperature measurement of 61%.NOTE 1This requires different thermocouples and measuring instru-ments for high-temperature tests than for moderate-temp
22、erature tests.5.4 Straightedge and RuleA straightedge having a lengthof at least 36 in. (0.9 m) and a small rule divided in164 or110of 1 in. shall be used to determine warpage.6. Sampling and Preparation of Test Specimens6.1 All samples that are required to complete the tests shallbe selected at one
23、 time and in such a manner so as to be fullyrepresentative of the average of the material. Test specimensfor any one test condition shall be selected from the originalsample lot so as to be as representative as possible. The testspecimens shall be commercial pieces. For pipe insulation, thefull-size
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC4112005STANDARDTESTMETHODFORHOTSURFACEPERFORMANCEOFHIGHTEMPERATURETHERMALINSULATION 高温 隔热材料 受热 性能

链接地址:http://www.mydoc123.com/p-466509.html