ASHRAE OR-16-C045-2016 Energy Use of Ground-Source Heat Pumps for Various Load Temperatures.pdf
《ASHRAE OR-16-C045-2016 Energy Use of Ground-Source Heat Pumps for Various Load Temperatures.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C045-2016 Energy Use of Ground-Source Heat Pumps for Various Load Temperatures.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Nicolas Hache is a graduate student from the Department of Mechanical Engineering, Polytechnique Montreal, Montreal, Canada. Guillaume Soudan is a undergraduate student from the Department of Mechanical Engineering, Polytechnique Mons, Mons, Belgium. Michel Bernier is a professor in the Department o
2、f Mechanical Engineering, Polytechnique Montreal, Montreal, Canada. Energy Use of Ground-Source Heat Pumps for Various Load Temperatures Nicolas Hache Guillaume Soudan Michel Bernier, PhD, PE ASHRAE member ABSTRACT This paper examines the impact of the secondary fluid temperatures at the evaporator
3、and condenser on the energy use of water-to-water ground-source heat pumps (GSHP). In the first part of the paper, the energy consumption reduction associated with small temperature differences between source and load temperatures is evaluated from a thermodynamic point-of-view by examining the coef
4、ficient of performance (COP) of an ideal refrigeration cycle. Then, the performance map of a typical water-to-water heat pump is examined to determine real COPs for a range of source/load temperatures and flow rates. In the second part of the paper, annual simulations are performed on a ground-sourc
5、e heat pump system providing space heating and domestic hot water (DHW) for a well-insulated single-family house. Two different load temperatures and two different source and load flow rates are examined for a total of eight cases. The concept of seasonal performance factors (SPF) is used to account
6、 for all the energy flows into the system including pumping energy. Results show that the highest value of SPF4 (2.44) is obtained when the source and load flow rates are 9.0 gpm (0.56 l/s) and 4.5 gpm (0.28 l/s) respectively, and the return load temperature is 40 C (104 F). There is a difference of
7、 8% between the lowest and highest values of SPF4 for the eight cases studied here indicating that the choice of the source and load flow rates as well as the load temperature is relatively important to limit the energy use of GSHP. INTRODUCTION Classic thermodynamics tells us that the energy requir
8、ed in a compression heat pump decreases with a reduction of the difference between the condensing and evaporating temperatures of the refrigerant. This can be achieved with efficient heat transfer at the evaporator and condenser and by lowering the difference between the source and load temperatures
9、 of the secondary fluids. Recent studies (e.g. Girard et al. 2015, Sarbu and Sebarchievici 2015, and Maivel and Kurnitski 2015) have examined the effects of temperature on heat pump performance. In this study, the impact of the secondary fluid temperatures at the evaporator and condenser on the ener
10、gy use of water-to-water ground-source heat pumps (GSHP) is examined. In addition, various source and load flow rates of the secondary fluids are examined as they modify heat transfer and refrigerant temperatures in the evaporator and condenser. This paper is organized as follows. First, the coeffic
11、ient of performance (COP) for an ideal heat pump is presented. Then, COPs of a commercially available water-to-water heat pump are reviewed and compared to the COP of an ideal heat pump. Finally, seasonal performance factors are calculated based on annual simulations of a GSHP system used for space
12、heating and domestic hot water (DHW) heating of a typical house located in a northern climate. COP The four basic components of a heat pump are shown in Figure 1a. The ideal cycle involves an isentropic compression (1-2), a condensation at constant pressure (2-3), an isenthalpic pressure reduction (
13、3-4) and an evaporation at constant pressure (4-1). There is a finite temperature difference between the secondary fluid temperatures, Tsource and Tload , and the refrigerant evaporating and condensing temperatures, Tevap and Tcond . Hence, the refrigerant temperature in the evaporator is a few degr
14、ees lower than the temperature of the secondary fluid on the source side. Similarly, the refrigerant temperature in the condenser is a few degrees higher than the temperature of the secondary fluid on the load side. Com p r e s s o rE x pa ns i onv a lv eE v a p or a t o rCon d e n s e r1234Q EQ CW
15、a) b) Figure 1 (a) Schematic representation of a compression heat pump and (b) Pressure-enthalpy diagram for two sets of conditions. (1000 kPa = 145 psia ; 300 kJ/kg = 129 Btu/lbm) Figure 1b shows the P-h diagram for two pairs of (Tsource/Tload), i.e. 30/120 F (-1.1/48.9 C) and 60/60 F (15.6/15.6 C)
16、. The refrigerant used is R-410A and temperature differences (Tsource - Tevap) and (Tcond - Tload) of 5 K (9 F) are assumed. The COPideal values calculated for these conditions are given in Table 1. This table also includes data from a commercially available water-to-water heat pump (used later in t
17、his study). The two shaded columns identified by the letter A refer to COPideal. As shown in this table, COPideal decreases as the difference between the load and source temperatures increases. The lowest (3.75) and the highest (25.84) values of COPideal are obtained for source and load temperatures
18、 equal to 30/120 F (-1.1/48.9 C) and 60/60 F (15.6/15.6 C), respectively. This relatively large difference between the lowest and highest values of COPideal can be explained using the P-h diagram shown in Figure 1b. When the difference between the evaporating and condensing temperatures of the refri
19、gerant is small, the heating effect (2 3) is relatively large and the compression work (2 1) is relatively small which leads to high values of COPideal. In practice, heat pumps do not operate ideally mainly because of compressor inefficiencies. Furthermore, isentropic efficiencies of compressors are
20、 not constant but vary as a function of the pressure ratio between the condensing and evaporating temperatures. Thus, the COP of a heat pump will not only vary because of the difference between the condensing and evaporating temperatures but also because the compressor efficiency changes with this t
21、emperature difference. Actual COP values of a commercially available water-to-water heat pump are shown in columns B in Table 1 for four source and four load temperatures as well as two source flow rates and two load flow rates ( and in Figure 1a). As shown in this table, COPs follow the same trend
22、as the values obtained earlier for COPideal , i.e. they decrease with an increase of the temperature difference (Tload -Tsource ). The lowest COP value is 2.20 and the highest is 8.60. High load and source flow rates increase heat transfer coefficients in the evaporator and condenser which reduces t
23、he temperature difference (Tcond - Tload) and (Tsource -Tevap) and increases the value of the COP. For example, for a source temperature of -1.1 C (30 F) and a load temperature of 48.9 C (120 F), the COP increases from a value of 2.20 for source and load flow rates both equal to 0.28 L/s (4.5 gpm) t
24、o a value of 2.50 when both the load and source flow rates are doubled. Two additional columns representing the ratios of the real COP to COPideal have been added to the right of the B columns. This ratio varies from 0.28 to 0.72 with an average of 0.59. Thus, on average, the COP of this heat pump i
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0452016ENERGYUSEOFGROUNDSOURCEHEATPUMPSFORVARIOUSLOADTEMPERATURESPDF

链接地址:http://www.mydoc123.com/p-455769.html