ASHRAE OR-16-C039-2016 Cold Climate Heat Pumps Using Tandem Compressors.pdf
《ASHRAE OR-16-C039-2016 Cold Climate Heat Pumps Using Tandem Compressors.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C039-2016 Cold Climate Heat Pumps Using Tandem Compressors.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Dr. Bo Shen, Dr. Omar Abdelaziz, Dr. Keith Rice and Mr. Van Baxter are Research and Development Staff in Building Technologies Research and Integration Center, ORNL, TN, USA. Mr. Hung Pham is an engineering leader in Emerson Climate Technologies. Cold Climate Heat Pumps Using Tandem Compressors Bo S
2、hen, PhD Omar Abdelaziz, PhD C Keith Rice, PhD Member ASHRAE Member ASHRAE Member ASHRAE Van D. Baxter, P.E. Hung Pham Fellow ASHRAE Member ASHRAE ABSTRACT In cold climate zones, e.g. ASHRAE climate regions IV and V, conventional electric air-source heat pumps (ASHP) do not work well, due to high co
3、mpressor discharge temperatures, large pressure ratios and inadequate heating capacities at low ambient temperatures. Consequently, significant use of auxiliary strip heating is required to meet the building heating load. We introduce innovative ASHP technologies as part of continuing efforts to eli
4、minate auxiliary strip heat use and maximize heating COP with acceptable cost-effectiveness and reliability. These innovative ASHP were developed using tandem compressors, which are capable of augmenting heating capacity at low temperatures and maintain superior part-load operation efficiency at mod
5、erate temperatures. Two options of tandem compressors were studied; the first employs two identical, single-speed compressors, and the second employs two identical, vapor-injection compressors. The investigations were based on system modeling and laboratory evaluation. Both designs have successfully
6、 met the performance criteria. Laboratory evaluation showed that the tandem, single-speed compressor ASHP system is able to achieve heating COP = 4.2 at 47F (8.3C), COP = 2.9 at 17F (-8.3C), and 76% rated capacity and COP = 1.9 at -13F (-25C). This yields a HSPF = 11.0 (per AHRI 210/240). The tandem
7、, vapor-injection ASHP is able to reach heating COP = 4.4 at 47F (8.3C), COP = 3.1 at 17F (-8.3C), and 88% rated capacity and COP = 2.0 at -13F (-25C). This yields a HSPF = 12.0. The system modeling and further laboratory evaluation are presented in the paper. INTRODUCTION As described by Khowailed
8、et al. (2011), in the U. S., the primary target market for cold climate heat pumps is the 2.6 million U.S. homes using electric furnaces and heat pumps in the cold/very cold region, with an annual energy consumption of 0.16 quads (0.17 EJ). A high performance air-source cold climate heat pump (CCHP)
9、 would result in significant savings over current technologies ( 60% compared to strip heating). It can result in an annual primary energy savings of 0.1 Quads (0.1055 EJ) when fully deployed, which is equivalent to 5.9 million tons (5.35 million MT) of annual CO2 emissions reduction. In cold climat
10、e areas with limited access to natural gas, conventional electric ASHPs or electric resistance furnaces can be used to provide heating. During very cold periods, the ASHPs tend to use almost as much energy as the electric furnaces due to their severe capacity loss and efficiency degradation. Present
11、ly, technical and economic barriers limit market penetration of heat pumps in cold climates. R the evaporator exit was assumed to be saturated vapor, i.e. from use of a suction line accumulator. When using a VI compressor with an economizer, the economizer exit superheat degree was set at 10 R (5.6
12、K) and its heat transfer effectiveness was assumed as 70%. The indoor return air temperature was always set at 70F (21.1C). Table 1: Parameters of Indoor and Outdoor Units Parameters (heating mode) Indoor Fin- otherwise, the higher air flow rate and blower power were used. 00.10.20.30.40.50.60.70.80
13、.911.01 . 52.02 . 53.03 . 54.04 . 55.0R ate d C O P at 4 7 F I n te gr ate d C O P w R es Heat at -13 F C ap ac i ty R atioCOP W/WCapacityRatioFigure 3 Ratios of heating capacity relative to 47F, COP at 47F and integrated COP at -13F The heat pump rated capacity at 47F (8.3C), approximately the rate
14、d cooling capacity at 95F (35C) is usually the value used to match a building cooling design load for the sizing selection. Regarding the multi-capacity compressor(s), VS_R4500RPM, 3600RPM, and 2700RPM mean getting the rated heating capacity at 47F (8.3C) by running the VS compressor speed at 4500,
15、3600, and 2700 RPM, respectively. Tandem_RLow means achieving the rated heating capacity at 47F (8.3C), by running a single compressor. The simulation results in Figure 3 compare heating COPs at 47F (8.3C), integrated COPs at -13F (-25C), and ratios of heat pump heating capacity at -13F vs. 47F rati
16、ng point. The ratios of heating capacity were defined as heat pump capacity running at full speed at -13F vs. the rated capacity at 47F. The integrated COPs at -13F (-25C) were calculated by including the supplemental resistance heat needed to match 80% rated heating capacity at 47F (8.3C), i.e. the
17、 building heating load for a well-insulated home at -13F (-25C) in Region V. If no resistance heat was needed, the heat pump COP was used as the integrated COP. It can be seen that over-capacity is the key to match the 75% capacity goal at -13F (-25C) and provide higher integrated COP due to the eli
18、mination of resistance heat use. Four options in Figure 3 are able to reach the DOE capacity goal at -13F (-25C), i.e. 75% relative to the rated capacity at 47F (8.3C) (VS_R4500RPM, 3600RPM, Tandem_RLow and TandemVI_RLow). Tandem_RLow has a higher integrated COP than the VS options, since the VS com
19、pressor has an efficiency drop when running at the top speed of 7200 RPM. The tandem compressors with vapor injection and inter-stage economizing result in the highest integrated COP and the second highest capacity. Based on the analysis, two prototypes were selected for laboratory evaluation. First
20、 was a most cost-effective design, i.e. using equal tandem, single-speed compressors with an electronic expansion valve (EXV) for discharge temperature control. The other is a Premium design, i.e. using equal tandem, VI compressors with inter-stage economizing and discharge temperature control. MOST
21、 COST-EFFECTIVE DESIGN - EQUAL TANDEM, SINGLE-SPEED COMPRESSORS The most cost-effective design using two equal, single-speed compressors is shown in Figure 4. The design considerations are summarized as below: 1. The two equal, single-speed compressors were provided with special “heating application
22、” design features that allow the compressors to operate at higher discharge temperatures than most typical compressors (up to 280F (138C). This enables the heat pump to operate at extremely low ambient temperatures. 2. Current two-speed heat pumps on the market use a single, two-stage compressor hav
23、ing a typical displacement volume split ratio of 100%/67%. In comparison, the tandem compressors have a volume split ratio of 100%/50%, which provides a larger extended-capacity potential, if the heat pump nominal COP and capacity ratings are established for one compressor. That is the reason that t
24、he heat pump using the tandem compressors can reach 75% capacity at -13F (-25C). 3. The CCHP is sized to match a 3-ton/10.6 kW building cooling load using a single compressor. The system uses heat exchangers of a typical 5-ton heat pump. With a single compressor running (cooling mode and moderate te
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0392016COLDCLIMATEHEATPUMPSUSINGTANDEMCOMPRESSORSPDF

链接地址:http://www.mydoc123.com/p-455763.html