ASHRAE OR-16-C015-2016 Optimizing the Flammability and Performance of Next Generation Low GWP R410A Replacements.pdf
《ASHRAE OR-16-C015-2016 Optimizing the Flammability and Performance of Next Generation Low GWP R410A Replacements.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C015-2016 Optimizing the Flammability and Performance of Next Generation Low GWP R410A Replacements.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Steve Kujak is the director-next generation refrigerant research for Ingersoll Rand, La Crosse, WI. Kenneth Schultz, PhD, is an engineer- next generation refrigerant research for Ingersoll Rand, La Crosse, WI. Optimizing the Flammability and Performance of Next Generation Low GWP R410A Replacements
2、Steve Kujak Kenneth Schultz, PhD Member ASHRAE Member ASHRAE ABSTRACT Lower global warming potential (GWP) refrigerant replacements for R410A have been extensively studied over the past few years with limited success in finding an optimal replacement. Refrigerant candidates offered to date have been
3、 a trade-off of GWP to performance, but so far candidates have not been offered that trade GWP to flammability while preserving or improving performance of R410A to allow for quick and orderly transition to lower GWP refrigerants. These refrigerants have been either pure R32 or blends of R32 with va
4、rious new olefin refrigerants, like R1234yf and R1234ze(E), along with other traditional hydrofluorocarbons. Pure R32 has good performance, but would require significant hardware redesign to accommodate fluid properties differences, the GWP is one of the highest (GWP=675), as well as being one of th
5、e more flammable refrigerants (burning velocity 6.7 cm/sec). Performance modelling, unit performance testing, and flammability studies were conducted to guide the best refrigerant design to optimize GWP to flammability for blends of R32, R1234yf and R125. This study determined that in fact flammabil
6、ity can be minimized while allowing for a R410A “design compatible” refrigerant that improves on the performance of R410A while balancing GWP. INTRODUCTION Growing concerns about the global warming impact of refrigerants used in HVAC R32 runs 1% to 2% higher than R410A. DR-55 exhibits a small temper
7、ature glide, ranging from 1.6 F (0.9 C) at 40 F (40 C) to a maximum of 2.3 F (1.3 C) at 77 F (25 C). Figure 5. GWP (AR5) and burning velocity relationships for R32/R125/R1234yf blends. Figure 6. Lines of constant capacity relative to R410A for R32/R125/R1234yf blends. Figure 7. Pressure-enthalpy dia
8、gram for R410A, DR-55, and R32 at the A Test condition Figure 8. Temperature-entropy diagram for R410A, DR-55, and R32 at the A Test condition Table 2. Critical Properties of Refrigerants R410A DR-55 R32 Critical temperature (F/C) 160.4 / 71.3 175.4 / 79.7 172.6 / 78.1 Critical pressure (psia/MPa) 7
9、11 / 4.90 803 / 5.53 839 / 5.78 The critical temperature and pressure of R410A, DR-55 and R32 are listed in Table 2. DR-55s critical temperature is much higher than R410A and slightly higher than R32. This provides extended high ambient temperature operating range relative to R410A. The Ph and Ts do
10、mes are wider for DR-55 than R410A because of DR-55s higher R32 content. This reduces the refrigerant mass flow rate needed to achieve a given capacity, potentially reducing pressure drops through heat exchangers. Although DR-55 has an elevated compressor discharge temperature relative to R410A, it
11、is substantially lower than with R32. System Performance Testing of DR-55 4 Ton Residential Split HP Unit DR-55 was evaluated in the original equipment manufacturers laboratories in a 5 ton (17.6 kW), 19 SEER residential split HP unit with variable speed compressor and fans. Unit performance was det
12、ermined in accordance with AHRI Standard 210/240 (AHRI-210/240, 2008). Performance at a number of extended high ambient and low ambient temperatures was determined as well. The unit contains an EXV for cooling and a TXV for heat pump operation. The DR-55 refrigerant charge was determined to be 10% l
13、ess than R410A to achieve the same condenser exist subcooling of 15 F (8 C) at the “A” rating condition. The TXV was not adjusted for the heating tests. Table 3 below gives a summary of the test points and conditions. As noted above, the thermodynamic capacity of the DR-55 is slightly less than R410
14、A by 2% to 3%. Here, all tests were run at equal capacity by increasing compressor speed slightly. Figure 9 shows the relative EER of DR-55 to R410A at all test points. The EER is higher for DR-55 during cooling operation and slightly lower during heating operation as compared to R410A. SEER is used
15、 as the efficiency performance rating factor for residential products. The nominal catalogue SEER for this product is 19.0 with R410A and was determined in this testing to be 19.18. The SEER with DR-55 was determined as 19.65 based on two trials or about a 2.5% increase in efficiency. This increase
16、comes in part from the favourable thermodynamic characteristics of DR-55 noted above. In addition, the refrigerant mass flow rate is lower for the DR-55, leading to lower pressure drop losses in the coils and a higher evaporator exit saturation temperature. DR-55 has been designed to have a marginal
17、ly higher compressor discharge temperature than R410A, but significantly lower than with R32. Unexpectedly, the compressor discharge temperatures with DR-55 were lower than with R410A for most test points; see Figure 10. After review of the test setup, this was likely due to improper instrumentation
18、 positioning. The conclusion from the testing is that DR-55 is a “design compatible” refrigerant for this R410A product and offers increased efficiency over R410A while balancing both capacity and compressor discharge temperature. Table 3. Summary of 4 Ton Residential Split Test Points & Conditions.
19、 Mode Outdoor Temp F (C) Compressor Speed Mode Outdoor Temp F (C) Compressor Speed Cooling 120 (49) High Heating 62 (17) Low Cooling 95 (35) High Heating 47 (8) High Cooling 87 (31) Int. Heating 47 (8) Nom Cooling 82 (28) High Heating 47 (8) Low Cooling 82 (28) Low Heating 35 (2) High Cooling 67 (19
20、) Low Heating 35 (2) Int. Heating 17 (-8) High 15 Ton Packaged Rooftop AC Unit DR-55 was tested at third party laboratory in an experimental high performance 13 ton (45.7 kW) R410A packaged rooftop air conditioning unit. Unit performance was determined in accordance with AHRI Standard 210/240 (AHRI-
21、210/240, 2008) practices. No adjustments were made to the unit other than the refrigerant charge. DR-55 charge was found to be 10% less than R410A to achieve the same condenser subcooling. Figures 11, 12 and 13 show the performance characteristics of DR-55 at a number of extended high ambient condit
22、ions. DR-55 high ambient performance was far superior to R410A in this unit configuration. These large increases in both EER (12% to 27%) and capacity (5% to 18%) are partially the result of DR-55 having a higher critical temperature and preferential thermodynamic properties to R410A which allowed i
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0152016OPTIMIZINGTHEFLAMMABILITYANDPERFORMANCEOFNEXTGENERATIONLOWGWPR410AREPLACEMENTSPDF

链接地址:http://www.mydoc123.com/p-455740.html