ASHRAE NY-08-012-2008 Performance of VAV Fan-Powered Terminal Units Experimental Setup and Methodology (RP-1292)《变风量风机动力型终端的性能 实验装置和方法RP-1292》.pdf
《ASHRAE NY-08-012-2008 Performance of VAV Fan-Powered Terminal Units Experimental Setup and Methodology (RP-1292)《变风量风机动力型终端的性能 实验装置和方法RP-1292》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE NY-08-012-2008 Performance of VAV Fan-Powered Terminal Units Experimental Setup and Methodology (RP-1292)《变风量风机动力型终端的性能 实验装置和方法RP-1292》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、2008 ASHRAE 75ABSTRACTThis paper is the first of three papers on the developmentof experimental performance models of variable air volumefan powered terminal units. Tests were conducted on bothparallel and series fan powered terminal units. Data fromthese tests were used to develop empirical models
2、of airflow,power, and leakage of both parallel and series fan powerterminal units. These models are suitable for use in annualenergy use models of variable air volume systems in commer-cial buildings. This paper provides a description of the exper-imental apparatus, the terminal units, and measureme
3、nts forairflow and power. Both 8 in. (203 mm) and 12 in. (304 mm)primary air inlet terminal units from three manufacturerswere evaluated. INTRODUCTIONVariable Air Volume (VAV) systems maintain comfortconditions by varying the volume of primary air delivered toa space. A VAV system (Figure 1) often c
4、onsists of a centralair handling unit (AHU), where air is cooled by cooling coils(Wendes 1994). This air, referred to as primary air, is sentthrough a single-duct supply system to VAV terminal units bythe supply fan. Each terminal unit is ducted to air outlets,usually serving two or more offices or
5、an open area. VAVterminal units that include a fan to improve circulation withina zone are called fan powered terminal units. These terminalunits can draw in air from the plenum area and mix it withprimary air from the central Air Handling Unit (AHU) tomaintain comfort conditions in the occupied spa
6、ce. There are two configurations for fan powered terminalunits: series and parallel. The fan can be in the path of theprimary airflow (Figure 2). This configuration is a called a fanpowered series terminal unit. The controller will modulate theterminal unit damper in response to the control signals
7、fromthe thermostat and air velocity sensor. The fans on these termi-nal units output a constant amount of air that does not varywith load because the downstream pressure is constant (Alex-ander and Int-Hout 1998). As a result, when the primary airdamper closes, more plenum air is induced and recircu
8、latedinto the space. When the signal from the inlet air velocitysensor indicates that the primary airflow has reached a prede-termined minimum (because of ventilation requirements), thedamper will not close any more. If the space is still too cold,electric or hot water supplemental heat can be used
9、to meet thethermostat setpoint.When the fan is outside the primary airflow, the configu-ration is called a fan powered parallel terminal unit (Figure 3).During operation, the fan for a parallel terminal unit cycles onand off. During periods of maximum cooling, the fan is off. Abackdraft damper preve
10、nts cold air from blowing backwardsthrough the fan. The terminal unit primary air damper modu-lates the airflow to maintain the space temperature setpoint.An inlet air velocity sensor within the primary air streamallows the unit controller to maintain a consistent volume ofairflow to the zone depend
11、ing on the temperature setpoint.When the primary airflow drops below a specified amount, thecontroller activates the fan. At this point, the terminal unitmixes primary air with air being drawn in from the plenum.Electric or hot water supplementary heat can be used for addi-tional heating. Depending
12、on the control scheme, the control-ler can continue to reduce primary air to the conditioned spaceby adjusting the damper. In the field, the fan on a VAV terminal unit often must befine tuned (test and balancing) to provide the airflow output forPerformance of VAV Fan-Powered Terminal Units: Experim
13、ental Setup and MethodologyJames C. Furr Dennis L. ONeal, PhD, PE Michael A. DavisFellow ASHRAEJohn A. Bryant, PhD, PE Andrew CramletMember ASHRAE Student Member ASHRAEJames C. Furr is a Thermal Management Engineer at Lockheed Martin, Fort Worth, TX. Dennis L. ONeal is Holdredge/Paul Professor andHe
14、ad and Andrew Cramlet is a student at the Department of Mechanical Engineering, Texas A Qfan, the airflow through thefan, and Powerfan, the power consumption of the terminal unitfan. The independent variables were:1. The static pressure upstream of the terminal unit, Pup,2. The static pressure downs
15、tream of the terminal unit, Pdwn,3. The speed of the terminal unit fan controlled by the SCR,as represented by the RMS average voltage to the unit,4. The position of the terminal units damper, and 5. The control pressure from the flow sensor, Piav,. Thisvariable was directly affected by the position
16、 of thedamper and the upstream static pressure. Before testing a unit, each of the independent variableswas assigned a set of specific values. The number of levels foreach of the variables and their values are shown in Table 5. Thevalues for the levels differed across VAV terminal unitsbecause the m
17、aximum and minimum values for certain vari-ables differed across units. The maximum and minimumvalues for the SCR voltage were determined by adjusting theSCR setscrew completely in both directions. The maximumvalue for the damper setting was defined as when the damperwas horizontal, or fully open an
18、d minimum was defined aswhen the damper was closed. The levels for downstream staticpressure varied from 0.1 to 0.5 in w.g. (25 to 125 Pa). Thelevels for upstream static pressure varied depending on the testbeing run. Figure 11 Schematic of experimental test setup.Figure 12 Volumetric airflow balanc
19、e of a terminal unit.ASHRAE Transactions 81The characterization of a terminal unit consisted ofseveral tests. These tests were conducted for each combinationof damper and SCR settings. In every test, data for each combi-nation of upstream and downstream static pressure levels wereobtained. This proc
20、ess was a full-factorial design because datapoints for all combinations of independent variables wereobtained. The sequence of these tests usually consisted ofrunning the tests for all of the SCR speeds at a single damperposition, adjusting the damper to the next position, andcontinuing the sequence
21、.Before starting a test, the damper and SCR were manuallyadjusted to the desired positions according to the test beingrun. Throughout a test, the damper and SCR would remain inthe same position. During a test, the data acquisition systemallowed the user to adjust the VSDs on the upstream anddownstre
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAENY080122008PERFORMANCEOFVAVFANPOWEREDTERMINALUNITSEXPERIMENTALSETUPANDMETHODOLOGYRP1292 风量 风机 动力

链接地址:http://www.mydoc123.com/p-455538.html