ASHRAE NY-08-007-2008 Geothermal Heat Rejection Systems for Data Centers《数据中心的地热隔离系统》.pdf
《ASHRAE NY-08-007-2008 Geothermal Heat Rejection Systems for Data Centers《数据中心的地热隔离系统》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE NY-08-007-2008 Geothermal Heat Rejection Systems for Data Centers《数据中心的地热隔离系统》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、2008 ASHRAE 37ABSTRACTThis paper investigates the potential of a geothermal heatreject system (GHRS) to improve the performance of a datacenter (DC) cooling system. The paper compares the perfor-mance of conventional systems rejecting heat to the atmo-sphere to a similar system rejecting heat to the
2、 ground. The firstsystem uses water cooled direct expansion (DX) computerroom air conditioners (CRAC); the second system uses watercooled chillers with chilled water computer room air handlers(CRAH) and the third system uses GHRS with CRAH and norefrigeration compressors. The paper also evaluates th
3、e poten-tial of replacing an emergency thermal storage system (TSS)using chilled water storage tank with a GHRS.Deep earth temperatures of the United States will be usedto depict the areas of the country that can be cooled withoutmechanical refrigeration, and those that can be cooled withfewer tons
4、of refrigeration on a percentage basis.GROUND SOURCE COOLING SYSTEMINTRODUCTIONIn most data centers, refrigeration systems are used toremove the heat dissipated by the electrical and computerequipment. The performance of the refrigeration system islimited by the Laws of Thermodynamics to a coefficie
5、nt ofperformance (COP) less than the COP of the Carnot cycle.Figure 1 Deep earth temperature in U.S. (ASHRAE 2007).Geothermal Heat Rejection Systemsfor Data CentersDennis R. Landsberg, PhD, PE Doug K. McLellan, PE Christopher W. Kurkjian, PEMember ASHRAE Member ASHRAE Member ASHRAEDennis R. Landsber
6、g is President of Landsberg Engineering, P.C. and President of L the two major concernsof the modern data center.This paper will investigate the feasibility of a GHRS fora data center. The paper will compare conventional data centersystems to a GHRS.To evaluate and compare the systems, a set of eval
7、uationcriteria were selected as shown below:System Criteria are: ReliabilityAll systems will have sufficient redundancy so that nosingle point of failure will cause system failure. To determinesystem reliability the number of active components andcomplexity of the system will be considered. Every ac
8、tivecomponent such as a motor or belt is a potential failure point.A drive belt is generally considered more likely to fail than apassive component such as a pipe or a duct. Equipment oper-ating at more severe conditions will also be more likely to fail.A compressor operating continuously at 90% of
9、the design liftis more likely to fail than same compressor operating at 80%of the design lift. The system must be able to function duringnatural disasters such as floods and storms. To the extentpossible the system should be protected from vandalism andman made disasters such as gun fire and bombs.M
10、aintainabilityEach system will have redundancy so that normal main-tenance will not interrupt services. Some active componentsare easily replaced. In-house personnel can easily replace abelt or fan motor, but not a compressor. Therefore, somecomponents may require a greater degree of redundancy toac
11、hieve the same maintainability.FlexibilityIn the modern data center, the air-conditioning systemshould be able to adapt to future requirements. The precisenature of the future requirements are usually not known, butfor this evaluation the system that can be most easily modifiedwill be scored highest
12、.Energy EfficiencyEnergy efficiency is the easiest of the criteria to quantify.The systems will be scored on the total power consumptionand peak power demand.All systems will be assumed to provide similar perfor-mance. Each system can provide satisfactory cooling to all thecritical loads.SYSTEM DESC
13、RIPTIONSThe data center (DC) for each system will consist of a10,000 ft2raised floor area with a critical load of 1MW. Theother building loads will be 250 KW. The total design coolingload is therefore 1.25 MW or about 360 tons. The DC locationwill be the Mid Atlantic region. The first two systems ar
14、e stan-dard refrigeration systems and the third system is system withground source heat rejection.System 1 is a direct expansion system with water cooledcondensers inside the CRAC. See Figure 2.The system will have 18 CRAC, 15 operating and 3standbys. Heat is rejected to the atmosphere through remot
15、eFigure 2ASHRAE Transactions 39Figure 3a Summer operation.Figure 3b Winter operation.Figure 4a Summer operation.40 ASHRAE Transactionsevaporative coolers (EC). Redundant pumps circulate thecondenser water between the CRAC and EC. A TSS system isnot included. In order to provide continuous cooling in
16、 theevent of loss of utility the CRAC system will be assumed tooperate from an uninterruptible power supply (UPS). Figure 2represents the heat balance for the System 1 summer opera-tion. During the winter, System 1 operation is the same assummer except that in the CRAC the economizer coil providesth
17、e cooling and the compressor energy is saved.The CRAC have economizer coils so that during thewinter, the CRACs compressors do not need to operate.Figure 2 also represents the heat balance for the System 1winter operation.System 2 is a chiller system with redundant water cooledchillers and 18 CRAH,
18、15 operating and 3 standbys. Figure 3aand 3b represents the heat balance for the System 2 summerand winter operation respectively.Heat is rejected to the atmosphere with redundant evap-orative coolers. The system has redundant primary, secondaryand condenser water pumps. The system has the secondary
19、pumps and CRAH on UPS and incorporates a TSS. The TSSencompasses the thermal storage tank (TST) and associatedvalves and controls. During the winter the chilled water can becooled by the EC without operating the chiller.System 3 is a GHRS. The system rejects heat from thedata center without refriger
20、ation compressors. The GHRShas 18 CRAH similar to the System 2, but they operate athigher temperatures than in System 2. The CRAH have anentering air temperature of 95F and a leaving air tempera-ture of 70F. The chilled water enters the CRAC at 65F andleaves at 75F. The corresponding temperatures in
21、 the chillersystem are 75, 55, 45, and 55F. Heat is rejected to the atmo-sphere through either an EC or to the ground through aground source heat exchanger (GSHE). Cooling water iscirculated by redundant pumps between the CRAH, EC, andGSHE. The pumps and CRAH are on UPS and system doesnot have a TSS
22、. Figure 4a represents the heat balance for theSystem 3 summer operation.Figure 4b Winter operation.Figure 4c Winter operation.ASHRAE Transactions 41As heat is continuously rejected to the ground, the groundtemperature may rise. After several years the ground sourcesystem may loose capacity due to t
23、he high ground tempera-ture. System 3 has an EC to extend the service life of theground source system indefinitely. During the winter there aretwo modes of operation, charge mode and EC only mode.When the outdoor wet bulb is less than 55F, the system canoperate with either the EC or GSHE. If the wat
24、er temperatureof the water leaving the GSHE is above 45F and watertemperature leaving the EC is less than the temperature leav-ing the GSHE, then System 3 operates in the charge mode.During the charge mode, the system cools the DC and “stores”cooling in the ground by removing heat from the ground. O
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAENY080072008GEOTHERMALHEATREJECTIONSYSTEMSFORDATACENTERS 数据中心 地热 隔离 系统 PDF

链接地址:http://www.mydoc123.com/p-455533.html