ASHRAE LV-11-C001-2011 New Analytical and Numerical Solutions for the Short-term Analysis of Vertical Ground Heat Exchangers.pdf
《ASHRAE LV-11-C001-2011 New Analytical and Numerical Solutions for the Short-term Analysis of Vertical Ground Heat Exchangers.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C001-2011 New Analytical and Numerical Solutions for the Short-term Analysis of Vertical Ground Heat Exchangers.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Saqib Javed is a graduate student at Chalmers University of Technology, Sweden. Johan Claesson is a professor at Chalmers University of Technology and Lund University of Technology, Sweden. New Analytical and Numerical Solutions for the Short-term Analysis of Vertical Ground Heat Exchangers Saqib Ja
2、ved, P.E. Johan Claesson, Ph.D. Student Member ASHRAE ABSTRACT This paper presents the background, development and the validation of new analytical and numerical solutions for the modeling of short-term response of borehole heat exchangers. The new analytical solution studies the boreholes heat tran
3、sfer and the related boundary conditions in the Laplace domain. A set of equations for the Laplace transforms for the boundary temperatures and heat-fluxes is obtained. These equations are represented by a thermal network. The use of the thermal network enables swift and precise evaluation of any th
4、ermal or physical setting of the borehole. Finally, very concise formulas of the inversion integrals are developed to obtain the time-dependent solutions. The new analytical solution considers the thermal capacities, the thermal resistances and the thermal properties of all the borehole elements and
5、 provides a complete solution to the radial heat transfer problem in vertical boreholes. The numerical solution uses a special coordinate transformation. The new solutions can either be used as autonomous models or easily be incorporated in any building energy simulation software. INTRODUCTION Long-
6、term response of a borehole represents the development of ground temperatures over time in response to the overall ground heat injections and extractions. On the other hand, short-term response of the borehole shows the variations in circulating fluid temperatures not associated to the long-term res
7、ponse of the ground. The short-term response of the borehole corresponds to time periods ranging from a few minutes to a number of days. Today many commercial buildings, like super markets and shopping centers, have simultaneous heating and cooling demands. Many other commercial and office buildings
8、 have a cooling demand during the day, even in cold climates, and a heating demand during the night. For such buildings, a significant amount of thermal energy is just pumped up and down the borehole system with heat transfer mainly occurring in the borehole. Similarly, the circulating fluid tempera
9、ture of a borehole system operating under peak load conditions depends largely on the internal heat transfer of the borehole. For these cases, the borehole exit fluid temperature depends on the short-term thermal response of the borehole. As operation and performance of a heat pump both depend on th
10、e fluid temperature from the borehole system, the thermal energy use and electrical demands of the heat pump and the overall ground source heat pump (GSHP) system are considerably affected by the short-term response of the borehole. Therefore, when optimizing the operation, control and performance o
11、f a GSHP system, the short term response of the borehole is quite important. The evaluation of thermal response tests (TRTs) and heat-flux build-up analysis of the borehole are also conducted using models based on the short-term response of the borehole. Various numerical, analytical and semi-analyt
12、ical solutions have been developed to model the short-term response of the borehole. Analytical solutions, because of their flexibility and superior computational time efficiencies, are of particular LV-11-C001 2011 ASHRAE 32011. American Society of Heating, Refrigerating and Air-Conditioning Engine
13、ers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAES prior written permission.interest; however, numerical solutions are also re
14、quired to obtain precise solutions and for parametric analysis. The first major contribution came from Yavuzturk (1999), who extended Eskilsons concept of non-dimensional temperature response functions (1987) to include the short-term analysis. As with Eskilsons approach, the work of Yavuzturk also
15、requires the response to be pre-computed for individual cases. Shonder and Beck (1999) and Austin (1998) also developed solutions which numerically solve the heat transfer in the borehole. However, both these solutions are aimed at evaluation of TRTs. Young (2004) modified the classical Buried Elect
16、ric Cable (BEC) solution (Carslaw and Jaeger, 1959) to develop his analytical Borehole Fluid Thermal Mass (BFTM) solution. The solution is based on an analogy between a buried electric cable and a vertical ground heat exchanger and needs to be optimized for individual cases. Lamarche and Beauchamp (
17、2007) presented an exact solution assuming two legs of the U-tube as a hollow equivalent-diameter cylinder. The solution solves the heat transfer problem assuming a steady heat-flux condition across the hollow cylinder boundary. However, it ignores the thermal capacity of the fluid present in the U-
18、tube. Bandyopadhyay et al. (2008) also presented an exact solution for the case of boreholes backfilled with the borehole cuttings. This solution has limited practical application as most of the boreholes are backfilled with a material quite different from the borehole cuttings. Gu and ONeal (1995)
19、developed an analytical short-term response solution assuming a cylindrical source in an infinite composite region. The solution solves the borehole transient heat transfer problem using the generalized orthogonal expansion technique which requires calculation of multiple eigenvalues. Beier and Smit
20、h (2003) also developed a semi-analytical solution, which first solves the borehole heat transfer problem in the Laplace domain and then uses a numerical inversion to obtain the time domain solution. Bandyopadhyay et al. (2008) have also reported a similar solution. Javed et al. (2010) studied the e
21、xisting short-term solutions in detail and noted the need of an analytical solution which should consider the thermal capacities, the thermal resistances and the thermal properties of all the borehole elements and which could be easily incorporated in building energy simulation software to optimize
22、the operation and control of GSHP systems. NEW ANALYTICAL SOLUTION A new analytical solution has been developed to model the short-term response of the borehole (Claesson, 2010). The new solution studies the heat transfer and the related boundary conditions in the Laplace domain. The solution assume
23、s radial heat transfer in the borehole. To meet this requirement, the U-tube in the borehole is approximated as a single equivalent-diameter pipe. The fluid temperatures entering and leaving the U-tube are represented using a single average value. The resulting problem is shown in Figure 1. The heat
24、 flux qinjis injected to the circulating fluid with temperature Tf (). The fluid has a thermal capacity of Cp. The pipe thermal resistance is Rp, and the pipe outer boundary temperature is Tp(). The heat flux qp() flows through the pipe wall to the grout. The thermal conductivity and the thermal dif
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0012011NEWANALYTICALANDNUMERICALSOLUTIONSFORTHESHORTTERMANALYSISOFVERTICALGROUNDHEATEXCHANGERSPDF

链接地址:http://www.mydoc123.com/p-455404.html