ASHRAE LV-11-027-2011 Optimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based Model.pdf
《ASHRAE LV-11-027-2011 Optimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based Model.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-027-2011 Optimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based Model.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、934 ASHRAE TransactionsABSTRACTThis study investigates the optimization of the coolingtower condenser-water leaving temperature using a compo-nent-based model. This model consists of a chiller, acondenser-water pump, and two cooling towers. The chiller ismodeled with a Gordon-Ng model for vapor-comp
2、ressionchillers with variable-condenser flow. The cooling tower issimulated with an effectiveness-NTU model. The pump poweris calculated from the pump flow rate, pump head, and effi-ciency. This optimization problem is formulated as that of mini-mizing the total power of the chiller, pump, and fans
3、byselecting an optimal cooling tower condenser-water leavingtemperature at given weather conditions, chiller load, chilled-water leaving temperature, and condense-water flow rate. Themodel is applied in an example chiller CW system, and a gener-alized reduced gradient solver is used to search the op
4、timalcooling tower approach setpoint. Simulation results show thatthe optimal cooling tower approach reset schedule can beapproximated with two straight lines. Significant energysavings could be achieved if compared with the scenario witha constant cooling tower condenser-water leaving tempera-ture.
5、 Further simulations show that the chilled-water leavingtemperature, chiller part-load ratio, and the climate zones theplant locates in have a minor effect on the optimal approachreset schedule. A higher condenser-water flow rate per coolington leads to a higher optimal cooling tower approach, but t
6、hiseffect can be neglected for a system with a constant CW flowrate. The approach setpoint reset schedule that yields optimalcontrol depends on the performance characteristics of thechiller and the cooling tower. INTRODUCTIONA condenser water (CW) loop consists of chillers,condenser-water pumps (CWP
7、), and cooling towers (CT). Theelectricity consumption of these components accounts for themajority of total electricity consumption in a chiller plant. Fora water-cooled chiller system, it is typically designed aroundentering condenser-water temperatures of 85F (29.4C) witha nominal CW flow of 3.0
8、gallon per minute (gpm) per ton(0.1937 m3/h per kW cooling) and a 10F (5.6C) range(Furlong and Morrison 2005). However, most of the time, thesystem could be operated under nondesign load and weatherconditions. How to optimize the operation of the condenser-water loop is of great interest.Supervisory
9、 control is typically applied in the chillerplant. The CWP control is dedicated to the chiller control toprovide relatively constant flow for individual chillers. It ismore and more popular to apply variable-speed devices (VSD)to cooling tower fans to reduce their cycling frequency andallow better t
10、emperature control for any given chiller load andweather conditions. The CT condenser-water leaving temper-ature (CWLT) setpoint is maintained by modulating the CTfan speed. A dead band for the CWLT setpoint is adopted toavoid fan cycling. Braun and Diderrich (1990) demonstratedthat feedback control
11、 for cooling tower fans could be elimi-nated by using an open-loop supervisory control strategy. Thisstrategy requires only measuring chiller loading to specify thecontrol and is inherently stable.Optimization of the cooling tower CWLT setpoint isintensively studied by some researchers. This setpoin
12、t and theCWP flow rate are the main inputs that are directly related tothe optimization of the condenser side. Some engineers keepthe setpoint at the lower limit at any time to minimize chillerOptimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based ModelZhiqin Z
13、hang, PhD Hui Li, PhDStudent Member ASHRAE Associate Member ASHRAEWilliam D. Turner, PhD, PE Song Deng, PE Member ASHRAEZhiqin Zhang is a PhD student in the Department of Mechanical Engineering and a graduate research assistant in the Energy Systems Labo-ratory, Hui Li is a post-doctorate and Song D
14、eng is an associate director in the Energy Systems Laboratory, and William D. Turner is a profes-sor in the Department of Mechanical Engineering, Texas A (a) I-P, (b) SI.Table 2. Hour Number in Each DB and WB Bin for Houston, TXWet-Bulb Temperature, F (C)Dry Bulb, F (C)17(8)24 (4)30(1)36(2)43(6)49(9
15、)55(13)62(17)68(20)74(23)81(27)21 (6) 5 7 29 (2) 26 66 37 (3) 2 118 227 25 46 (8) 4 147 395 78 54 (12) 18 158 503 272 62 (17) 19 202 432 681 18 70 (21) 42 152 380 915 239 78 (26) 48 111 467 1476 7387 (31) 13 154 644 22895 (35) 29 258 108103 (39) 1 14 5(a)(b)all2011 ASHRAE 939humid). The Typical Mete
16、orological Year 3 (TMY3) hourlyweather data (NREL 2008) are used to generate a two-dimen-sion bin. One dimension is DB temperature and the other isWB temperature. In each bin, the hour number is counted andthe average DB and WB temperatures in each bin are calcu-lated. These data are used as inputs
17、for the CW loop simulationprogram. Table 2 shows an 11 by 11 bin for the TMY3 weatherdata of Houston, TX. For example, for the bin of the DB is54F and the WB is 49F, the total hour number is 503. In thisstudy, to achieve a higher accuracy, the DB is divided into 46bins and the WB is divided into 39
18、bins.OPTIMIZATION RESULTSOptimal Cooling Tower Approach TemperatureIn this simulation, the chiller part-load ratio is 80%(4400 ton 15,474 kW), and the chiller ChW leaving temper-ature is 36.0F (2.2C). The chiller CW flow rate is10,000 gpm (2271 m3/h). The system is located in Houston,TX, and it is a
19、 VSD-equipped fan. These are the default condi-tions for the following analysis. Figure 4 shows the optimalcooling tower CWLT setpoint versus the ambient WB temper-ature, and a strong linear correlation can be observed. Thisrelationship can be approximated with two straight lines toform a near-optim
20、al fan control.(17)When the ambient WB is lower than 47.0F (8.3C), thetower CWLT is controlled at 55.0F (12.8C) to meet thelower limit of the chiller. When the WB is higher than 47F(8.3C), a higher WB temperature leads to a lower optimaltower CWLT. The slope and the intercept of the optimal resetFig
21、ure 4 Optimal CT approach temperature versus ambient WB temperature; (a) I-P, (b) SI.(a) (b)Figure 5 Cooling tower approach temperatures under various fan control strategies; (a) I-P, (b) SI.(a) (b)TAppTwb 55 if Twb47F+=TApp0.1325Twb 13.56 if Twb47F+=940 ASHRAE Transactionsschedule could be changed
22、with many factors, which will bediscussed one by one in the following sections.Energy Savings PotentialFigure 5 shows the simulated cooling tower approachversus the ambient WB temperature for different CT controlstrategies. For the scenario with 70.0F (21.1C) CWLTsetpoint, if the ambient WB is highe
23、r than 66.0F (18.9C), thefan speed reaches 100% and the approach setpoint cannot bemaintained. For the scenario with 4.0F (2.2C) constantapproach temperature, if the ambient WB temperature is lowerthan 68.0F (20.0C), the fan is running at full speed and theactual approach is higher than 4.0F (2.2C).
24、 The scenario of controlling the cooling tower CWLTsetpoint at 70F (21.1C) is used as the baseline. The annualtotal electricity consumptions of the chiller, cooling towerfans, and CW pump are simulated. Another six CT fan controlstrategies are simulated and the energy savings percentages foreach str
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV110272011OPTIMIZATIONOFTHECOOLINGTOWERCONDENSERWATERLEAVINGTEMPERATUREUSINGACOMPONENTBASEDMODELPDF

链接地址:http://www.mydoc123.com/p-455400.html