ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 39-2012 CONDENSERS.pdf
《ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 39-2012 CONDENSERS.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 39-2012 CONDENSERS.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、39.1CHAPTER 39CONDENSERSWATER-COOLED CONDENSERS 39.1Heat Removal. 39.1Heat Transfer . 39.2Water Pressure Drop 39.4Liquid Subcooling 39.5Water Circuiting. 39.5Types 39.5Noncondensable Gases 39.6Testing and Rating . 39.7Operation and Maintenance 39.7AIR-COOLED CONDENSERS 39.8Types 39.8Fans and Air Req
2、uirements 39.9Heat Transfer and Pressure Drop 39.9Condensers Remote from Compressor. 39.10Condensers as Part of Condensing Unit 39.10Water-Cooled Versus Air-Cooled Condensing. 39.10Testing and Rating 39.11Control . 39.11Installation and Maintenance 39.13EVAPORATIVE CONDENSERS 39.14Heat Transfer . 39
3、.14Condenser Configuration. 39.15Condenser Location . 39.16Multiple-Condenser Installations 39.16Ratings . 39.16Desuperheating Coils. 39.17Refrigerant Liquid Subcoolers . 39.17Multicircuit Condensers and Coolers 39.17Water Treatment . 39.17Water Consumption 39.18Capacity Modulation 39.18Purging. 39.
4、18Maintenance. 39.18Testing and Rating 39.18HE CONDENSER in a refrigeration system is a heat ex-Tchanger that rejects all the heat from the system. This heat con-sists of heat absorbed by the evaporator plus the heat from theenergy input to the compressor. The compressor discharges hot,high-pressure
5、 refrigerant gas into the condenser, which rejects heatfrom the gas to some cooler medium. Thus, the cool refrigerant con-denses back to the liquid state and drains from the condenser to con-tinue in the refrigeration cycle.Condensers may be classified by their cooling medium as (l)water-cooled, (2)
6、 air-cooled, (3) evaporative (air- and water-cooled), and (4) refrigerant-cooled (cascade systems). The firstthree types are discussed in this chapter; see Chapter 48 in the 2010ASHRAE HandbookRefrigeration for a discussion of cascade-cooled condensers.WATER-COOLED CONDENSERSHEAT REMOVALThe heat rej
7、ection rate in a condenser for each unit of heatremoved by the evaporator may be estimated from the graph in Fig-ure 1. The theoretical values shown are based on Refrigerant 22 with5 K suction superheat, 5 K liquid subcooling, and 80% compressorefficiency. Depending on compressor efficiency, the hea
8、t removedcould be higher or lower than these values. Usually, the heat rejectionrequirement can be accurately determined by adding the knownevaporator load and the heat equivalent of the power required forcompression (obtained from the compressor manufacturers cata-log). (Note that heat from the com
9、pressor is reduced by an indepen-dent heat rejection processes such as oil cooling, motor cooling, etc.)The volumetric flow rate of condensing water required may becalculated as follows:Q = (1)whereQ = volumetric flow rate of water, m3/sqo= heat rejection rate, kW = density of water, kg/m3t1= temper
10、ature of water entering condenser, Ct2= temperature of water leaving condenser, Ccp= specific heat of water at constant pressure, kJ/(kgK)The preparation of this chapter is assigned to TC 8.4, Air-to-RefrigerantHeat Transfer Equipment; TC 8.5, Liquid-to-Refrigerant Heat Exchangers;and TC 8.6, Coolin
11、g Towers and Evaporative Condensers.qocpt2t1-Fig. 1 Heat Removed in Condenser39.2 2012 ASHRAE HandbookHVAC Systems and Equipment (SI)Example 1. Estimate volumetric flow rate of condensing water required forthe condenser of an R-22 water-cooled unit operating at a condensingtemperature of 40C, an eva
12、porating temperature of 4C, 5 K liquid sub-cooling, and 5 K suction superheat. Water enters the condenser at 30Cand leaves at 35C. The refrigeration load is 300 kW.Solution: From Figure 1, the heat rejection factor for these conditionsis about 1.19.qo=1.19 300 = 357 kW = 995 kg/m3at 33Ccp= 4.18 kJ/(
13、kgK)From Equation (1):Q = = 0.0172 m3/sHEAT TRANSFERA water-cooled condenser transfers heat by sensible cooling inthe gas desuperheating and condensate subcooling stages and bytransfer of latent heat in the condensing stage. The condensing stageis by far the dominant process in normal refrigeration
14、applications,accounting for approximately 83% of the heat rejection. Becausethe tube wall temperature is normally lower than the condensingtemperature at all locations in the condenser, condensation takesplace throughout the condenser.The effect of changes in the entering gas superheat is typicallyi
15、nsignificant because of an inverse proportional relationshipbetween temperature difference and heat transfer coefficient. As aresult, an average overall heat transfer coefficient and the mean tem-perature difference (calculated from the condensing temperaturecorresponding to the saturated condensing
16、 pressure and the enteringand leaving water temperatures) give reasonably accurate predic-tions of performance.Subcooling affects the average overall heat transfer coefficientwhen tubes are submerged in liquid. The heat rejection rate is thendetermined asq = UAtm(2)whereq = total heat transfer rate,
17、 WU = overall heat transfer coefficient, W/(m2K)A = heat transfer surface area associated with U, m2tm= mean temperature difference, KChapter 4 of the 2009 ASHRAE HandbookFundamentals de-scribes how to calculate tm.Overall Heat Transfer CoefficientThe overall heat transfer coefficient Uoin a water-c
18、ooled con-denser with water inside the tubes may be computed from calcu-lated or test-derived heat transfer coefficients of the water andrefrigerant sides, from physical measurements of the condensertubes, and from a fouling factor on the water side, using the follow-ing equation:Uo= (3)whereUo= ove
19、rall heat transfer coefficient, based on external surface and mean temperature difference between external and internal fluids, W/(m2K)Ao /Ai= ratio of external to internal surface areahw= internal or water-side film coefficient, W/(m2K)rfw= fouling resistance on water side, (m2K)/Wt = thickness of
20、tube wall, mk = thermal conductivity of tube material, W/(mK)Ao /Am= ratio of external to mean heat transfer surface areas of metal wallhr= external or refrigerant-side coefficient, W/(m2K)s= surface fin efficiency (100% for bare tubes)For tube-in-tube condensers or other condensers where re-frigera
21、nt flows inside the tubes, the equation for Uo, in terms ofwater-side surface, becomesUo= (4)wherehr= internal or refrigerant-side coefficient, W/(m2K)hw= external or water-side coefficient, W/(m2K)For brazed or plate-and-frame condensers A0= Ai; thereforethe equation for UoisUo= (5)where t is plate
22、 thickness.Water-Side Film CoefficientValues of the water-side film coefficient hwmay be calculatedfrom equations in Chapter 4 of the 2009 ASHRAE HandbookFun-damentals. For turbulent flow, at Reynolds numbers exceeding10 000 in horizontal tubes and using average water temperatures,the general equati
23、on (McAdams 1954) is(6)whereD = inside tube diameter, mk = thermal conductivity of water, W/(mK)G = mass velocity of water, kg/(sm2) = viscosity of water, kg/(sm)cp= specific heat of water at constant pressure, kJ/(kgK)The constant 0.023 in Equation (6) reflects plain inner diameter(ID) tubes. Bergl
24、es (1995) and Pate et al. (1991) discuss numerouswater-side enhancement methods that increase the value of this con-stant.Because of its strong influence on the value of hw, a high watervelocity should generally be maintained without initiating erosionor excessive pressure drop. Typical maximum velo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACSYSTEMSANDEQUIPMENTSICH392012CONDENSERSPDF

链接地址:http://www.mydoc123.com/p-455118.html