ASHRAE HVAC APPLICATIONS IP CH 38-2015 TESTING ADJUSTING AND BALANCING.pdf
《ASHRAE HVAC APPLICATIONS IP CH 38-2015 TESTING ADJUSTING AND BALANCING.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC APPLICATIONS IP CH 38-2015 TESTING ADJUSTING AND BALANCING.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、38.1CHAPTER 38TESTING, ADJUSTING, AND BALANCINGTerminology . 38.1General Criteria. 38.1Air Volumetric Measurement Methods. 38.2Balancing Procedures for Air Distribution 38.3Variable-Volume Systems . 38.4Principles and Procedures for Balancing Hydronic Systems . 38.6Water-Side Balancing. 38.8Hydronic
2、 Balancing Methods. 38.9Fluid Flow Measurement . 38.12Steam Distribution 38.15Cooling Towers. 38.15Temperature Control Verification. 38.16Field Survey for Energy Audit 38.17Reports . 38.18Testing for Sound and Vibration. 38.19YSTEMS that control the environment in a building changeSwith time and use
3、, and must be rebalanced accordingly. Thedesigner must consider initial and supplementary testing and balanc-ing requirements for commissioning. Complete and accurate operat-ing and maintenance instructions that include intent of design andhow to test, adjust, and balance the building systems are es
4、sential.Building operating personnel must be well-trained, or qualified oper-ating service organizations must be employed to ensure optimumcomfort, proper process operations, and economical operation.This chapter does not suggest which groups or individuals shouldperform a complete testing, adjustin
5、g, and balancing procedure. How-ever, the procedure must produce repeatable results that meet thedesign intent and the owners requirements. Overall, one source mustbe responsible for testing, adjusting, and balancing all systems. Aspart of this responsibility, the testing organization should check a
6、llequipment under field conditions to ensure compliance.Testing and balancing should be repeated as systems are reno-vated and changed. Testing boilers and other pressure vessels forcompliance with safety codes is not the primary function of the test-ing and balancing firm; rather, it is to verify a
7、nd adjust operatingconditions in relation to design conditions for flow, temperature,pressure drop, noise, and vibration. ASHRAE Standard 111 detailsprocedures not covered in this chapter.1. TERMINOLOGYTesting, adjusting, and balancing (TAB) is the process of check-ing and adjusting all environmenta
8、l systems in a building to producethe design objectives. This process includes (1) balancing air andwater distribution systems, (2) adjusting the total system to providedesign quantities, (3) electrical measurement, (4) establishing quan-titative performance of all equipment, (5) verifying automatic
9、 con-trol system operation and sequences of operation, and (6) sound andvibration measurement. These procedures are accomplished bychecking installations for conformity to design, measuring andestablishing the fluid quantities of the system as required to meetdesign specifications, and recording and
10、 reporting the results.The following definitions are used in this chapter. Refer to ASH-RAE Terminology (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) for additional definitions.Test. Determine quantitative performance of equipment.Adjust. Regulate the specified flu
11、id flow rate and air patterns atterminal equipment (e.g., reduce fan speed, adjust a damper).Balance. Proportion flows in the distribution system (submains,branches, and terminals) according to specified design quantities.Balanced System. A system designed to deliver heat transferrequired for occupa
12、nt comfort or process load at design conditions.A minimum heat transfer of 97% should be provided to the space orload served at design flow. The flow required for minimum heattransfer establishes the systems flow tolerance. The fluid distribu-tion system should be designed to allow flow to maintain
13、therequired tolerance and verify its performance.Procedure. An approach to and execution of a sequence of workoperations to yield repeatable results.Report forms. Test data sheets arranged in logical order for sub-mission and review. They should also form the permanent record tobe used as the basis
14、for any future TAB work.Terminal. A point where the controlled medium (fluid or energy)enters or leaves the distribution system. In air systems, these may bevariable- or constant-volume boxes, registers, grilles, diffusers, lou-vers, and hoods. In water systems, these may be heat transfer coils,fan-
15、coil units, convectors, or finned-tube radiation or radiant panels.2. GENERAL CRITERIAEffective and efficient TAB requires a systematic, thoroughlyplanned procedure implemented by experienced and qualified staff.All activities, including organization, calibration of instruments, andexecution of the
16、work, should be scheduled. Air-side work must becoordinated with water-side and control work. Preparation includesplanning and scheduling all procedures, collecting necessary data(including all change orders), reviewing data, studying the system tobe worked on, preparing forms, and making preliminar
17、y field in-spections.Air leakage in a conduit (duct) system can significantly reduceperformance, so conduits (ducts) must be designed, constructed, andinstalled to minimize and control leakage. During construction, allduct systems should be sealed and tested for air leakage. Water,steam, and pneumat
18、ic piping should be tested for leakage, which canharm people and equipment.Design ConsiderationsTAB begins as design functions, with most of the devicesrequired for adjustments being integral parts of the design and instal-lation. To ensure that proper balance can be achieved, the engineershould sho
19、w and specify a sufficient number of dampers, valves,flow measuring locations, and flow-balancing devices; these must beproperly located in required straight lengths of pipe or duct for accu-rate measurement. Testing depends on system characteristics andlayout. Interaction between individual termina
20、ls varies with pres-sures, flow requirements, and control devices.The design engineer should specify balancing tolerances. Mini-mum flow tolerances are 10% for individual terminals andbranches in noncritical applications and 5% for main air ducts. Forcritical water systems where differential pressur
21、es must be main-tained, tolerances of 5% are suggested. For critical air systems, rec-ommendations are the following:The preparation of this chapter is assigned to TC 7.7, Testing and Balancing.38.2 2015 ASHRAE HandbookHVAC ApplicationsPositive zones:Supply air 0 to +10%Exhaust and return air 0 to 1
22、0%Negative zones:Supply air 0 to 10%Exhaust and return air 0 to +10%Balancing Devices. Balancing devices should be used to providemaximum flow-limiting ability without causing excessive noise.Flow reduction should be uniform over the entire duct or pipe. Sin-gle-blade dampers or butterfly balancing
23、valves are not good bal-ancing valves because of the uneven flow pattern at high pressuredrops. Pressure drop across equipment is not an accurate flow mea-surement but can be used to determine whether the manufacturerdesign pressure is within specified limits. Liberal use of pressuretaps at critical
24、 points is recommended.3. AIR VOLUMETRIC MEASUREMENT METHODSGeneralThe pitot-tube traverse is the generally accepted method of mea-suring airflow in ducts; ways to measure airflow at individual ter-minals are described by manufacturers. The primary objective is toestablish repeatable measurement pro
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACAPPLICATIONSIPCH382015TESTINGADJUSTINGANDBALANCINGPDF

链接地址:http://www.mydoc123.com/p-454931.html