ASHRAE D-MECP15-2-2014 Modeling and Energy Consumption with Parallel and Series VAV Terminal Units with ECM and PSC Motors (Third Edition Product Code D-MECP15-2).pdf
《ASHRAE D-MECP15-2-2014 Modeling and Energy Consumption with Parallel and Series VAV Terminal Units with ECM and PSC Motors (Third Edition Product Code D-MECP15-2).pdf》由会员分享,可在线阅读,更多相关《ASHRAE D-MECP15-2-2014 Modeling and Energy Consumption with Parallel and Series VAV Terminal Units with ECM and PSC Motors (Third Edition Product Code D-MECP15-2).pdf(210页珍藏版)》请在麦多课文档分享上搜索。
1、An ASHRAE Topical CompilationExpanded to Include New ResearchModeling andEnergy Consumptionwith Parallel and Series VAV Terminal Unitswith ECM and PSC MotorsThird EditionISBN 978-1-939200-07-5 2014, 2015 ASHRAE1791 Tullie Circle, NEAtlanta, GA 30329www.ashrae.orgAll rights reserved._ASHRAE is a regi
2、stered trademark in the U.S. Patent and Trademark Office, owned by the American Society of Heating, Refrigeratingand Air-Conditioning Engineers, Inc.ASHRAEhascompiledthispublicationwithcare,butASHRAEhasnotinvestigated,andASHRAEexpresslydisclaimsanydutytoinves-tigate, any product, service, process, p
3、rocedure, design, or the like that may be described herein. The appearance of any technical data oreditorial material in this publication does not constitute endorsement, warranty, or guaranty byASHRAE of any product, service, process,procedure, design, or the like.ASHRAE does not warrant that the i
4、nformation in the publication is free of errors, andASHRAE does notnecessarily agree with any statement or opinion in this publication. The entire risk of the use of any information in this publication isassumed by the user.No part of this publication may be reproduced without permission in writing
5、from ASHRAE, except by a reviewer who may quote briefpassages or reproduce illustrations in a review with appropriate credit, nor may any part of this publication be reproduced, stored in aretrievalsystem,ortransmittedinanywayorbyanymeanselectronic,photocopying,recording,orotherwithoutpermissioninwr
6、itingfrom ASHRAE. Requests for permission should be submitted at www.ashrae.org/permissions._ASHRAE STAFF SPECIAL PUBLICATIONS Mark S. Owen, Editor/Group Manager of Handbook and Special PublicationsCindy Sheffield Michaels, Managing EditorJames Madison Walker, Managing Editor of StandardsSarah Boyle
7、, Assistant EditorLauren Ramsdell, Assistant EditorMichshell Phillips, Editorial CoordinatorPUBLISHER W. Stephen ComstockThis collection of papers reflects ASHRAE Research co-sponsored byASHRAE Technical Committee 5.3, Room Air Distribution,and ASHRAE Technical Committee 7.7, Testing and Balancing.T
8、he collection was compiled by Eugene W. (Gus) Faris.Project Monitoring Committee MembersThe following members of the Project Monitoring Committees are gratefully acknowledged.Floyd Blackwell Dan Int-Hout Jerry SipesDouglas Fetters David John Jack StegallGaylon RichardsonInvestigatorsJohn Bryant Mich
9、ael A. Davis Dennis ONealIntroductionSince fan-powered variable-air-volume (VAV) terminal units were introduced to the marketplace, proponents ofboth parallel and series types have argued about which provides a system with the highest energy efficiency.*ASHRAE/AHRI research was undertaken to define
10、the operation of each type and investigate the issue.Descriptions of the findings are described in the first six papers included in this collection. Additional researchwas undertaken by a consortium of terminal unit manufacturers, motor manufacturers, and Texas A Qfan, the airflow through thefan, an
11、d Powerfan, the power consumption of the terminal unitfan. The independent variables were:1. The static pressure upstream of the terminal unit, Pup,2. The static pressure downstream of the terminal unit, Pdwn,3. The speed of the terminal unit fan controlled by the SCR,as represented by the RMS avera
12、ge voltage to the unit,4. The position of the terminal units damper, and 5. The control pressure from the flow sensor, Piav,. Thisvariable was directly affected by the position of thedamper and the upstream static pressure. Before testing a unit, each of the independent variableswas assigned a set o
13、f specific values. The number of levels foreach of the variables and their values are shown in Table 5. Thevalues for the levels differed across VAV terminal unitsbecause the maximum and minimum values for certain vari-ables differed across units. The maximum and minimumvalues for the SCR voltage we
14、re determined by adjusting theSCR setscrew completely in both directions. The maximumvalue for the damper setting was defined as when the damperwas horizontal, or fully open and minimum was defined aswhen the damper was closed. The levels for downstream staticpressure varied from 0.1 to 0.5 in w.g.
15、(25 to 125 Pa). Thelevels for upstream static pressure varied depending on the testbeing run. Figure 11 Schematic of experimental test setup.Figure 12 Volumetric airflow balance of a terminal unit.ASHRAE Transactions 81The characterization of a terminal unit consisted ofseveral tests. These tests we
16、re conducted for each combinationof damper and SCR settings. In every test, data for each combi-nation of upstream and downstream static pressure levels wereobtained. This process was a full-factorial design because datapoints for all combinations of independent variables wereobtained. The sequence
17、of these tests usually consisted ofrunning the tests for all of the SCR speeds at a single damperposition, adjusting the damper to the next position, andcontinuing the sequence.Before starting a test, the damper and SCR were manuallyadjusted to the desired positions according to the test beingrun. T
18、hroughout a test, the damper and SCR would remain inthe same position. During a test, the data acquisition systemallowed the user to adjust the VSDs on the upstream anddownstream blowers to meet desired conditions for a testpoint. The upstream static pressure was first adjusted to thesmaller of the
19、following: the point where the primary airflowwas approximately 5% greater than the terminal units speci-fied maximum or 2 in. w.g. (498 Pa). This pressure was desig-nated as the maximum level for the upstream static pressurevariable. The minimum upstream static pressure setting wasdetermined by the
20、 downstream pressure. It could not be lowerthan the downstream static pressure because primary airwould flow backwards into the terminal unit. Each test hadthree minimum level upstream static pressures. These mini-mums were selected to be approximately 0.25 in. w.g (60 Pa)greater than the correspond
21、ing downstream static pressure,except in cases where damper position caused insufficientprimary airflow. For each downstream static pressure, a thirdpoint was obtained for the upstream static pressure approxi-mately halfway between the corresponding minimum andmaximum. This procedure resulted in thr
22、ee data points foreach downstream static pressure level, and nine points per test.The upstream and downstream blowers were manuallyadjusted to the desired conditions for a specific data point.After static pressures reached steady state, data were acquired DATA ACQUISITION SYSTEMA computer data acqui
23、sition system was used to obtain,process, and store data. This system consisted of a personalcomputer, two separate data acquisition cards, and the termi-nation blocks for all signal wires.An eight channel, sixteen-bit sample-and-hold data cardwas used to measure instantaneous current and voltage. T
24、hesimultaneous sample and hold prevented any introduction oferror due to phase shift between the voltage and currentsignals. The elimination of phase shift allowed for accuratedetermination of the power factor for the VAV unit fans. Theanalog inputs had a resolution of 16 bits. The other data acquis
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEDMECP1522014MODELINGANDENERGYCONSUMPTIONWITHPARALLELANDSERIESVAVTERMINALUNITSWITHECMANDPSCMOTORSTHIRDEDITIONPRODUCTCODEDMECP152PDF

链接地址:http://www.mydoc123.com/p-454623.html