ASHRAE AN-04-3-2-2004 Total Energy Comsumption Model of Fan Subsystem Suitable for Continuous Commissioning《适合连续调试的风机子系统的总的能源消耗模式》.pdf
《ASHRAE AN-04-3-2-2004 Total Energy Comsumption Model of Fan Subsystem Suitable for Continuous Commissioning《适合连续调试的风机子系统的总的能源消耗模式》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AN-04-3-2-2004 Total Energy Comsumption Model of Fan Subsystem Suitable for Continuous Commissioning《适合连续调试的风机子系统的总的能源消耗模式》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、AN-04-3-2 Total Energy Consumption Model of Fan Subsystem Suitable for Continuous Commissioning Fu I in Wang Harunori Yoshida, Ph.D. Member ASHRAE Masato Miyata ABSTRACT This paper describes a newly developed total energy consumption model of a fan subsystem, which consists of fun, driveline, motor,
2、 and variable-speed drive. How to use this model for automated continuous commissioning is explained and verijied usingan experimental study. This model can accu- rately simulate the total energy consumption of a fan subsystem, which can be easily measured. Therefore, this model is useful for the au
3、tomated continuous commissioning of u fan subsystem during operation. The simulation results were verified using measured data in a real variable-air- volume system. The average diference between the simulated and measured datu is 5.1 %, which is accurate enoughfrom an automatedcontinuous commission
4、ingpoint of view to monitor the operation of a fan subsystem and detect faults during oper- ation. An experiment demonstrated that loose fan belts can be detected and the results are discussed as an example showing that the model can successfully detect this fault. INTRODUCTION Building commissionin
5、g is the process of ensuring that building systems are designed, installed, functionally tested, and capable of being operated and maintained to perform in conformity with the design intent (ASHRAE 1996). The awareness that commissioning is a viable method to help ensure buildings and their energy c
6、onservation measures (ECMs) meet design intent has been gradually growing since the 1980s. Some analyses of the data from the buildings partic- ipating in an energy conservation program revealed that many installed energy efiiciency measures were not performing as expected (BPA 1992). The main reaso
7、n is that the installed ECMs had not been properly commissioned. Building commissioning begins with the program phase and continues through the design phase, construction phase, acceptance phase, and post-acceptance phase (ASHRAE 1996). Post- acceptance phase commissioning is to continuously commis-
8、 sion the building systems to make them always run efficiently during their whole life cycle. For the purpose of automatically and continuously commissioning fan subsystems using simulation analysis during the operation phase, currently available fan simulation models were checked to determine wheth
9、er or not these models are suitable for continuous commissioning. Model validity checking showed that no fan model can give simula- tion results that match the experimental measured data quite well. Therefore, a new total energy consumption model of a fan subsystem was developed, which is suitable a
10、nd useful for continuous commissioning. This newly developed models accuracy and validity for continuous commissioning were verified using experiments. MODELS The fan models used by currently available simulation tools can only simulate the performance of a fan itself. There are no models to simulat
11、e the performance of other compo- nents in a fan subsystem, such as motor, inverter, etc. For example, SIMBAD can simulate a fans energy consumption using an empirical equation by inputting the real-time and maximum airflow rate and maximum energy consumption (CSTB 2001). HVACSIM+ is able to simulat
12、e a fans energy consumption and a fans pressure head using airflow rate and fan rotation speed by a series of equations fitted using manu- facturers data (Clark 1985). Fulin Wang is a Ph.D. candidate, Harunori Yoshida is a professor, and Masato Miyata is a masters student in the Department of Urban
13、and Environmental Engineering, Kyoto University, Kyoto, Japan. 02004 ASHRAE. 357 30% I 0.4 05 06 07 O8 o9 Cf 1800 rlm 8 1400 rlm A 1000 rlm Figure 1 Fan eficiency vs. dimensionless airflow rate. However, it is difficult to commission a fan using these models because they simulate the energy consumpt
14、ion of a fan itself and this energy consumption, which is termed fan shaft power, is difficult to measure. Especially during the operations phase, there is no building energy management system (BEMS) that measures a fans shaft power; but it is very easy to measure the total power consumed by the fan
15、 subsystem, which includes fan, dnveline, motor, and variable-speed drive (VSD), using a power meter set at the power input point such as the power switch. If the above-mentioned fan models are used to simulate the total power consumption of a fan subsystem, they will not give acceptable results. Fo
16、r instance, SIMBAD gives an average difference of 50%, and HVACSIM offers an average difference of 48%. Therefore, it is unreason- able to use these fan simulation models for continuous commissioning. Furthermore, the characteristics of total effi- ciency of a fan subsystem are different from that o
17、f the fan itself. A fans efficiency changes only according to dimension- less air-flow rate Cf The 7- Cfcurve shows a uniform shape at different fan rotation speeds, as shown in Figure 1, whereas the total efficiency of a fan subsystem changes according to not only Cf but also fan rotation speed, as
18、 shown in Figure 2. Therefore, new total efficiency models of fan subsystems are needed to express the unique characteristics of a fan subsystem. To address this problem, a total energy consump- tion model was proposed, which takes into account the perfor- mance of all the components in a fan subsys
19、tem, Le., fan, driveline, motor, and VSD inverter. The components and energy flow of a fan subsystem are shown in Figure 3. The total energy consumption model is defined by the following equa- tions. VAP E, = - qt 75% 100% AHU outlet 50% I damperopening E 45% : 35% 2 ._ 5 r 8 40% 6 30% =-. * 25% ; 2
20、0% /! - 2 15% 10% : , O 0.1 O2 03 04 05 06 07 Cf o 1800 r/m A 1350 rim x 900 r/m Figure2 Total eficiency of fan subsystem vs. Dimensionless airflow rate. Air, VAP AA Figure 3 Components and energyflow of a fan subsystem. (4) q, = mo+mlL+m2L 2 +m3L 3 +m4L 4 (5) 2.3 4 q. = io + ilL + i2L + zL + i4L c
21、=P u2 APD4 (9) V e-, -ND Equation 1 is used to calculate the total energy consump- tion of a fan subsystem using airflow rate, pressure head, and total efficiency of the fan subsystem. Total efficiency of a fan subsystem is calculated using Equation 2 by multiplying the efficiency of all the compone
22、nts ofthe fan subsystem, i.e., fan, driveline, motor, and inverter. Equation 3 is used to calculate 358 ASHRAE Transactions: Symposia Figure 4 Comparison of measured and calculated fan rotation speed. fan efficiency using a fourth-order function of dimensionless airflow rate. This equation is taken
23、from HVACSIM+ (Clark 1985). Motor and inverter efficiency is calculated using Equa- tions 4 and 5, respectively, which are fourth-order functions of load factor. Load factor is calculated using Equation 6, which is the rate of fan shaft power to rated shaft power. As discussed below, Equation 7 is u
24、sed to calculate the dimensionless airflow rate using dimensionless flow resis- tance. Dimensionless flow resistance is calculated using Equation 8, instead of the method used in HVACSIM+, which uses airflow rate and fan rotation speed as shown in Equation 9. Fan rotation speed is estimated using Eq
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAN04322004TOTALENERGYCOMSUMPTIONMODELOFFANSUBSYSTEMSUITABLEFORCONTINUOUSCOMMISSIONING 适合 连续 调试

链接地址:http://www.mydoc123.com/p-454540.html