ASHRAE AB-10-012-2010 A Comparative Analysis and Validation of Two DX Cooling Coil Modeling Methods.pdf
《ASHRAE AB-10-012-2010 A Comparative Analysis and Validation of Two DX Cooling Coil Modeling Methods.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AB-10-012-2010 A Comparative Analysis and Validation of Two DX Cooling Coil Modeling Methods.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、460 ASHRAE TransactionsABSTRACT Two DX air cooling coil modeling methods, one used in EnergyPlus and the other termed as a generic rating-data-based (GRDB) DX coils modeling method, were summarized and their detailed calculation procedures were presented using one case study. Six rooftop models of t
2、wo manufacturers were used for this study to predict sensible cooling capacity. It demonstrated that the relative errors in sensible cooling capacity prediction ranged from -14.9% to 15.1% for the method used in EnergyPlus and from -7.4% to 4.2% for the GRDB method. In addition to higher accuracy an
3、d precision, the GRDB method is more robust against the variations in parameter selections, has a wider application range, requires less computation power, and is more straightforward.INTRODUCTIONThe DX air cooling coil model is a key module in model-ing or simulating an overall cooling system to fa
4、cilitate the systems design, operation, and maintenance. Generally, all engineering simulation or modeling programs include an element modeling module for DX cooling coils, but individual programs may use different modeling methods and thus have different performance. For example, EnergyPlus is one
5、of the most popular building energy simulation tools which was originally based on Blast and DOE-2 and has been improved during one decade. However, although it is often used as a benchmark for comparative analysis, its performance is still very sensitive to user inputs. For example, the selection o
6、f the rated air flow rate has a significant impact on the DX coil sensible cooling capacity. Within the wide range of rated air flow rate suggested by EnergyPlus, an individual user may select a different rated air flow rate so that the predication could be very different (Hand et. al, 2005). Recent
7、ly, Yang and Li (2009) developed a GRDB DX coils modeling method. This method was validated by extensive laboratory testing and demonstrated to have good accuracy and to be easy to use. The objective of this paper is to perform an extensive comparative analysis between this GRDB DX cooling coil mode
8、ling method and the DX cooling coil modeling method used in EnergyPlus. ENERGYPLUS DX AIR COOLING COIL MODELING METHODEnergyPlus Modeling ProcedureThe modeling method of the DX air cooling coils used in EnergyPlus (US Department of Energy, 2009; ASHRAE HVAC 2 Toolkit; Henderson et al. 1992; Henderso
9、n et al. 2000) is slightly different for different coil types, but their basic procedures and formula are the same. Thus, the Single-Speed Electric DX Air Cooling Coil is taken as an example, and only the key variables (i.e., , , and SHR) in the cooling model are discussed here. The basic logic is:
10、firstly, users define the rated condition for the cooling system, limitation range of air flow rate at operating conditions, and coefficients of two modifiers of total cooling capacity (i.e., entering air temperature and supply air flow rate); secondly, EnergyPlus program constructs the two modifier
11、s to calculate the total cooling capacity at operating conditions other than the rated condition; finally EnergyPlus program calculates the property parameters of air leaving and entering the coil (e.g., the enthalpy of the entering air) and the coils geometry parameters (e.g., the BF of the coil),
12、and then obtains SHR at the operating condition based on the fixed geometry parameter QtotalQsensibleA Comparative Analysis and Validation of Two DX Cooling Coil Modeling MethodsHuojun Yang Haorong Li, PhDMember ASHRAEHuojun Yang is a doctoral student and Haorong Li is a professor at the University
13、of Nebraska-Lincoln, Omaha, NE.AB-10-0122010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). For personal use only. Additional reproduction, distribution, or transmission in either print or
14、digital form is not permitted without ASHRAEs prior written permission.2010 ASHRAE 461and the physical model of the cooling coil. The detailed proce-dure is summarized in Appendix C. Potential Improvements of the EnergyPlus Modeling MethodFrom the calculation procedure in Appendix C, we can see:1. A
15、s a simulation program, EnergyPlus has some inputs that need to be determined by users. These inputs include and the coefficients of two modifiers. In terms of , users can choose any value when it can satisfy the requirement of /rated ton within 300-450. However, each has a specific , and , and the
16、whole calculation about the model may be different even for the same coil. In terms of the coefficients of two modi-fiers, users have to determine the regression equation order, a set of data as the regression base data, and the equations coefficients. EnergyPlus calculates the two modifiers through
17、 these coefficients to adjust the cooling capacity as a function of entering air tempera-tures and supply air flow rate when the operating condi-tion of air is not the rated condition. These input selections give rise to more uncertainties or sensitivity for the simulation result, and the models rob
18、ustness may be weak (one detailed calculation case is also shown in Appendix C). 2. There is one stated limited application range for operat-ing conditions, i.e, CFM/ rated ton at operating condi-tions should be between 200 and 500. This range will limit the wide application of the model, especially
19、 for cases simulating faulty operating conditions such as foul-ing or low air flow rates.3. From the perspective of EnergyPlus users, they need to be educated to perform the following tasks, and it is not easily accessible to common users because there is no clear procedure in some cases, e.g., the
20、EnergyPlus docu-ment doesnt clearly state how to get the coefficients of total capacity modifiers.define the rated condition for the cooling system and limitation range of air flow rate at operating conditions; choose a set of data as the regression base data and the regression equation order; obtai
21、n the coefficients of two modifiers of total cooling capacity. 4. In terms of calculation, the model calculates various physical parameters (e.g., BF and the psychrometric properties of air) and needs iterations for dry-coil condi-tions of each data point. The calculation characteristics may take En
22、ergyPlus more time to get results, especially when there are a lot of data points (especially data of dry-coil condition). GENERIC ALTERNATIVE MODEL OF DX AIR COOLING COIL BASED ON MANUFACTURERS DATAThe development and description of the generic alterna-tive model was detailed in Yang and Li (2009),
23、 and the follow-ing is the short summary of the main procedure.Development of the Generic Alternative ModelBased on the analysis of the free, public, and available manufacturers rating data, the cooling systems relationship of outputs with inputs can be presented by the following formor (1)(2)Combin
24、ing the above equations with the physical model, the generic alternative model further developed the common format of cooling system (seen in Eq. 3). (3)For any fixed ( , CFM, OAT), there is one critical point ( ) that divides the cooling coil condition into wet-coil condition and dry-coil condition
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAB100122010ACOMPARATIVEANALYSISANDVALIDATIONOFTWODXCOOLINGCOILMODELINGMETHODSPDF

链接地址:http://www.mydoc123.com/p-454505.html