ARMY MIL-DTL-53135-1996 AUXILARY POWER UNIT 10 KW 120 240 VAC 60 HZ《60赫兹120 240伏10万千瓦辅助动力单元》.pdf
《ARMY MIL-DTL-53135-1996 AUXILARY POWER UNIT 10 KW 120 240 VAC 60 HZ《60赫兹120 240伏10万千瓦辅助动力单元》.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-DTL-53135-1996 AUXILARY POWER UNIT 10 KW 120 240 VAC 60 HZ《60赫兹120 240伏10万千瓦辅助动力单元》.pdf(88页珍藏版)》请在麦多课文档分享上搜索。
1、- MIL-DTL-53135 m 9999906 2022930 TT2 INCH-POUX2 MIL-DTL-53135 (NE) 9 September 1996 I DETAIL SPECIFICATION AUXILIARY POWER UNIT, 10 KW, 120/240 VAC, 60 HZ This specification is approved for use within the USA Communications- Electronics Command, Logistics and Readiness Center, Department of the Arm
2、y, and is available for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This detail specification covers the requirements for a 10 kW Auxiliary Power Unit, 120/240 VAC, 60 Hz, hereinafter called “APU“. The APU is a power source consisting of a self-contained eng
3、ine and generator, including remote controls, capable of producing electrical power when connected to its hosts source of fuel and starting power. 1.2 APU ratings. Rated voltage shall be 120 and 240 volts alternating current (VAC). Rated frequency shall be 60 Hz. Rated power factor shall be 0.8. Rat
4、ed speed shall be 3,E:O rpm. Rated power shall be 10 kW at 0.8 power factor (pf) lagging. The APU shall be re-connectable for the following voltages : a. 120-volt, single-phase, 2-wire b. 120/240-volt, single-phase, 3-wire 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are
5、 needed to meet the requirements specified in sections 3 and 4 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this li
6、st, document users are cautioned that they must meet all specified requirements documents cited in sections 3 and 4 of this specification, whether or not they are listed. Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in mproving this document
7、should be addressed to: USA 10115 GRIDLEY RD, STE 228, FT BELVOIR VA 22060-5849 by using the Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. COMMUNICATIONS ELECTRONICS COMMAND, BELVOIR RDE CENTER, ATTN: AMSEL-LC-IEW-D-ED, AMSC N/A FSC
8、6115 DISTRIBUTION STATEMENT A. Approved for public release, distribution is unlimited. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53135 (ME) 2.2 Government documents. 2.2.1 Specifications and standards. The following specifications and s
9、tandards form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Department of Defense Index of Specifications and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2). SPECI
10、FICATIONS FEDERAL A-A-52557 - DEPARTMENT OF DEFENSE MIL-L-2104 - MIL-T-5624 - MIL-A-11755 - MIL-A-4 6153 - MIL-F-46162 - MIL-L-4 61 67 - MIL-A-53009 - MIL-T-83133 - STANDARDS DEPARTMENT OF DEFENSE MIL-STD-4 O1 - MIL-STD-705 - MIL-STD-882 - MIL-STD-1472 - HANDBOOKS DEPARTMENTOF DEFENSE MIL-HDBK-705 -
11、 Fuel Oil; Diesel; For Posts, Camps and Stations. Lubricating Oil, Internal Combustion Engine, Tactical Service. Turbine Fuels, Aviation, Grades JP-4 and JP-5. Antifreeze, Arctic-type. Antifreeze, Ethylene Glycol, Inhibited, Heavy Duty, Single Package. Fuel, Diesel, Referee Grade. Lubricating Oil, I
12、nternal Combustion Engine, Arctic. Additive, Antifreeze Extender, Liquid Cooling Systems. Turbine Fuel, Avi.ation, Kerosene Type, Grade JP- 8. Electromagnetic Emission and Susceptibility Requirements for the Control of Electromagnetic Interference. Generator Sets, Engine-Driven, Methods of- Tests an
13、d Instructions. System Safety Program Requirements. Human Engineering Design Criteria for Military System, Equipment and Facilities. Generator Sets, Electrical, Measurements and Instrumentation. (Unless otherwise indicated, copies of federal and military specifications and standards are availab.le f
14、orm the Standardization Documents Order Desk, Building 4D, 700 Robbins Avenue, Philadelphia, PA 19111-5094.) 2.2.2 Other Government drawings and publications. The following other Government drawings and publications form a part.,of this document to the extent specified herein. Unless otherwise speci
15、fied, the issues shall be those in effect on the date of the solicitation (see 6.2). 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-* r MIL-DTL-53135 (ME) DRAWINGS ME TA 1323036218 - Auxiliary Power Unit, 10 KW, 120/240 VAC, 60 Hz. (Copies of draw
16、ings are available from the: US Army Communications- Electronics Command, RDE Center, Command, Control grade low sulfur No. 1-D or No. 2-D diesel fuel conforming to A-A-52557; JP-5 turbine fuel conforming to MIL-T-5624; or JP-8 turbine fuel conforming to MIL-T-83133, shall meet- all requirements Spe
17、cified herein. The APU, while operating on JP-4 turbine fuel conforming to MIL-T-5624 (with a cetane rating of 30 to 351, shall meet all requirements specified herein, except rated load may be reduced 15 percent and a maximum of 300 hours of operation on JP-4 per 3,000 hours of APU operation shall b
18、e required. Operation on JP-4 shall only be,required at temperatures from -18 to 38 C (O to 100 F) and at altitudes up to 914 meters (m) (3,000 feet ftl) . 3.7.4 Lubricants. The engine shall operate on lubricating oil conforming to MIL-L-2104, when temperatures are above -26 C (-15 F). The engine sh
19、all operate on lubricatingoil conforming to MIL-L-46167 when temperatures are at or below 4 .“C (40 OF). 3.7.5 Coolant. The APU shall operate with the following coolants: a. MIL-A-11755 antifreeze from -32 to 49 OC (-25 to 120 OF) ambient. b. Water with MIL-A-46153 inhibited antifreeze from -32 to 4
20、9 OC (-25 to 120 FI ambient. c. Water withMIL-A-53009 additive from 4 to 49 OC (40 to 120 OF) ambient. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-53135 (ME) 3.8 Audio noise. When tested as specified in 4.7.2.1, audio noise sound- pressur
21、e levels (SPLs) emanating from the APU shall not exceed 15 dBA at 7 m (22.9 ft) from the perimeter of the APU, when measured at 1.2 m (3.9 ft) above the ground. In addition, audio noise emanating from the APU shall not exceed 85 dBA at the operators station, defined to be 0.7 m (2.3 ft) from the con
22、trol panel. These requirements apply under all operating conditions specified herein with the APU operating at all loads from no load to rated load. 3.9 Environmental requirements. 3.9.1 Starting and operating. The APU shall start and operate under each and any combination of the following operating
23、 conditions: a. All possible relative humidities, with ambient temperatures ranging from -32 to 49 C (-25 to 120 F) at sea level; and from -32 to 35 “C at 1,219 m (-25 to 95 F at 4,000 ft). The high temperature requirement remains at 35 C (95 OF) at altitudes above 1,219 m (4,000 ft) . b. Altitudes
24、up to and including 2,438 m (8,000 ft). Rated load may be reduced by 3.5 percent for each 305 m (1,000 ft) above 1,219 m (4,000 ft) (e.g., at 8,000 ft rated load may be reduced by 14 percent). Exhaust smoke conditions shall be measured during all altitudes. Exhaust smoke testing shall be in accordan
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILDTL531351996AUXILARYPOWERUNIT10KW120240VAC60HZ60 赫兹 120240 10 千瓦 辅助 动力 单元 PDF

链接地址:http://www.mydoc123.com/p-444379.html