《ANSI UL 508 BULLETINS-2001 UL Standard for Safety Industrial Control Equipment (08 16 2001 (74p) 05 31 2001 (140p) 05 31 2001 (98p)).pdf》由会员分享,可在线阅读,更多相关《ANSI UL 508 BULLETINS-2001 UL Standard for Safety Industrial Control Equipment (08 16 2001 (74p) 05 31 2001 (140p) 05 31 2001 (98p)).pdf(312页珍藏版)》请在麦多课文档分享上搜索。
1、Subject 508 (in reply, refer to Subject 508) 12 Laboratory Drive Research Triangle Park, NC 27709 August 16, 2001 TO: Standards Technical Panel (STP) for Industrial Control Equipment, STP 508, Industry Advisory Conference of UL for Industrial Control Equipment, Subscribers to ULs Standards Service f
2、or Industrial Control Equipment SUBJECT: Report of the Meeting of the Industry Advisory Conference of UL for Industrial Control Equipment; Request for Comments on the Proposed Requirements for the Seventeenth Edition of the Standard for Industrial Control Equipment, UL 508; PROPOSED EFFECTIVE DATES
3、The following topics were discussed at the meeting: 1. Standards Technical Panels (STPs) - ULs Enhanced Standards Development Process 2. Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations 3. Backfeeding of Self-Protected Combination Motor Controllers 4. Short Circu
4、it Tests - A. Bus Bar Accessories for Use With Industrial Control Equipment, B. Assemblies of Indostrial Control Equipment 5. Equipment Rated 601 - 1500 Volts 6. Insulating Materials 7. Spacings 8. Insulating Barriers 9. Float and Pressure Operated Switches -A. Float Switches, B. Short Circuit Test
5、and Three Phase Motor Ratings, C. Ratings for Pressure Operated Switches IO. Miscellaneous Apparatus - A. Resistors, B. Power Supplies II. Field Wiring Terminals 12. Marking Locations 13. New Descriptive Report Format - Discussion Regarding the Elimination of Figures, Illustrations, etc. 14. NEMA Ra
6、tings on Equipment SUBJECT 508 -2- AUGUST 16,2001 15. Proposed First Edition of UL 60947-1 General Rules and UL 60947-4-1 Contactors and Starters 16. Reorganization of Industrial Control Equipment Product Categories 17. Proposed New Standard for General-Purpose Branch-Circuit Motor Controllers 18. S
7、chedule for Next Meeting COMMENTS DUE: October 12,2001 A meeting of the Industry Advisory Conference of UL for Industrial Control Equipment was held on April 9 b) the ampacity of the tap conductor, on the line side of the manual motor controller, is not less than 1/10 of the ampere rating of the bra
8、nch circuit protection for the motor group; and c) when listed and specifically marked for this purpose. SUBJECT 508 -5- AUGUST 16,2001 In support of the panel action, UL is proposing requirements for inclusion in UL 508 to evaluate a manual motor controller for this purpose. This proposal includes
9、additional performance tests consistent with the substantiation presented to the code making panel and marking requirements for manual motor controllers suitable for use as tap conductor protection within motor groups. The proposed marking, ”Suitable for Tap Conductor Protection in Group Installatio
10、ns” is also included in the NEC text of the revision to Section 430-53(d). As these devices will be limited by the NEC proposal for use on the load side of the branch circuit protection only, the current UL 508 general industrial spacings are sufficient for this use. The proposed performance test pr
11、ogram includes evaluation of the integral overcurrent protection to interrupt short circuits and faults to ground. In order to demonstrate the interrupting ability of the device and to minimize impedance in the test circuit, the interrupting tests will be performed without an additional branch circu
12、it protective device on the line side. In addition, the device will be required to comply with performance requirements for motor disconnect switches. As these devices do not have a means for remote control of their contacts, there are also provisions in the proposal to conduct short circuit testing
13、 of motor controllers that will be installed on the load side of these devices. Per the aforementioned NEC revisions, UL also plans to revise the guide information with the following text for Manual Motor Controllers (NLRV) to facilitate identification of these devices in the field: Tap Conductor Pr
14、otection - Manual motor controllers that have been additionally investigated for use as tap conductor protection within a motor group are marked ”Suitable as Tap Conductor Protection in Group Installations”. These devices are intended to be installed on the load side of motor branch circuit protecti
15、on for a motor group in accordance with Section 430-53(d)(3) of the National Electrical Code. Industry suggested that these proposals be revised to address the use of replaceable and non- replaceable current elements. UL has revised and included additional proposals to address this concern. UL has a
16、lso included additional proposals to address manual motor controllers intended for use as tap conductor protection based upon the discussions at the meeting. Revisions to Table 67.1, Marking locations for industrial control equipment, resulting from the proposed requirements are located in Item 12,
17、Marking Locations of this meeting report. IMPACT As these proposals represent an additional level of performance that is optional for manual motor controllers, no review or retest of currently Listed or Recognized components will be necessary. Therefore, UL proposes that these revisions become effec
18、tive upon publication. 3. BACKFEEDING OF SELF-PROTECTED COMBINATION MOTOR CONTROLLERS RATIONALE and DISCUSSION Back-feeding is a common practice with certain types of components, such as a circuit breaker, to overcome wiring problems for a specific installation. Manufacturers have asked what evaluat
19、ion would be required to permit a self-protected combination motor controller to be back-fed, that is, have the source of supply connected to the terminals normally used for connection of the load. SUBJECT 508 -6- AUGUST 16,2001 Back-feeding is not feasible for most combination motor controllers as
20、this would place discrete components such as the motor controller, and motor overload relay, on the line side of the motor branch circuit protection and disconnecting means. In the case of a self-protected combination motor controller, this construction is possible when all of the combination motor
21、control functions are contained in a common housing. In general, when a self-protected combination motor controller is mounted on a horizontal DIN rail, the line side terminals for connection to the supply are on the top and the load side terminals for connection of the motor load are on the bottom.
22、 UL proposes to add requirements to UL 508 to specifically address this optional installation method. These proposals would require self-protected combination motor controllers intended for back-fed installation to comply with the line side terminal spacing requirements on both the line and load sid
23、es of the device and also undergo additional performance requirements with the line and load connections reversed. The additional performance requirements are intended to demonstrate that the device can safely operate in this mode without having to repeat the entire test program. As most combination
24、 motor controllers are not able to be back-fed, UL is proposing that only those self-protected combination motor controllers that comply with the additional requirements be marked to indicate their suitability for back-feed ing . The performance requirements selected to evaluate back-fed self-protec
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIUL508BULLETINS2001ULSTANDARDFORSAFETYINDUSTRIALCONTROLEQUIPMENT0816200174P05312001140P0531200198PPDF

链接地址:http://www.mydoc123.com/p-439273.html