ANSI UL 1666-2007 UL Standard for Safety Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts (Fifth Edition Reprint with Revisio.pdf
《ANSI UL 1666-2007 UL Standard for Safety Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts (Fifth Edition Reprint with Revisio.pdf》由会员分享,可在线阅读,更多相关《ANSI UL 1666-2007 UL Standard for Safety Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts (Fifth Edition Reprint with Revisio.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1666 Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTIO
2、N OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts, UL 1666 Fifth Edi
3、tion, Dated February 16, 2007 Summary of Topics This revision to ANSI/UL 1666 is being issued to reect the reaffirmation of the ANSI approval of the Standard. No technical changes have been made to the document. The revisions are substantially in accordance with Proposal(s) on this subject dated Nov
4、ember 4, 2016. Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic,
5、 mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable
6、 for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of su
7、ch damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, da
8、mage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. JANUARY 31, 2017 UL 1666 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBU
9、TION WITHOUT PERMISSION FROM UL JANUARY 31, 2017 UL 1666 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL FEBRUARY 16, 2007 (Title Page Reprinted: January 31, 2017) 1 UL 1666 Standard for Test for Flame Propagation Hei
10、ght of Electrical and Optical- Fiber Cables Installed Vertically in Shafts First Edition November, 1986 Second Edition January, 1991 Third Edition February, 1997 Fourth Edition November, 2000 Fifth Edition February 16, 2007 This ANSI/UL Standard for Safety consists of the Fifth Edition, including re
11、visions through January 31, 2017. The most recent designation of ANSI/UL 1666 as a Reaffirmed American National Standard (ANS) occurred on as an American National Standard (ANSI) occurred on January 31, 2017. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, and Title
12、Page. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at https:/. ULs Standards for Safety are copyrighted by UL. Neither a printe
13、d nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2017 UNDERWRITERS LABORATORIES INC. ANSI/UL 1666-2012 (R2017)UL COPYRIGHTED MATERI
14、AL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL JANUARY 31, 2017 UL 1666 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 Units of Measurement .4 P
15、ERFORMANCE 3 Fire Test Room .4 4 Fire Test Apparatus .4 4.1 Fire test chamber .4 4.2 Burner apparatus .5 4.3 Burner fan .8 4.4 Propane .8 4.5 Exhaust blower and duct 8 4.6 Temperature and ow measurement instrumentation 8 4.7 Data acquisition equipment .10 5 Specimen Conditioning 10 6 Determination o
16、f Specimen Diameter 10 7 Number of Cable Lengths 11 8 Test Procedure 11 REQUIREMENTS AND REPORT 9 Acceptance Criteria 12 10 Report 13 GUIDE TO MOUNTING METHODS 11 Introduction 13 12 Method .13 FEBRUARY 16, 2007 UL 1666 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION
17、WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 This is a re test for determining values of ame propagation height for electrical and optical-ber cables that are for installation vertically in shafts or in vertical runs that penetrate one or more oors. 1.1 revised June 27, 2012 1.2 The purpose o
18、f this test is to determine whether the ame propagation characteristics of these riser cables are in accordance with the National Electrical Code. 1.3 This test does not investigate the toxicity or corrosivity of the products of combustion or decomposition. 1.4 This test does not cover the construct
19、ion requirements for any cable or the electrical, optical, and other performance requirements for any cable. 2 Units of Measurement 2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. PERFORMANCE 3 Fire Test Room 3.1 The re tes
20、t room in which the chamber is located is to have provision for a free inow of air to maintain the room at a controlled pressure of 0 0.05 in (0 12 Pa) of water column with respect to barometric pressure and at a temperature of 73 5F (23 3C) and a relative humidity of 50 5 percent throughout each te
21、st. 4 Fire Test Apparatus 4.1 Fire test chamber 4.1.1 The test chamber is to be as shown in Figure 4.1. The test chamber, all equipment, and the cable specimens are to be protected from the wind and other conditions of weather that could affect the test results. The walls of the structure are to be
22、of standard concrete masonry nominally 8 in (203 mm) thick. The rst and second oors shall be constructed of reinforced normal-weight concrete nominally58i n (127 203 mm) thick. The roof shall be constructed of a suitable building construction capable of providing a tight seal with the walls of the s
23、tructure. A slot measuring 1 ft by 2 ft (305 mm by 610 mm) is to be located in the rst oor, and an identical slot is to be located directly above in the second oor. As shown in Figure 4.1, each slot is to be 8 in (203 mm) from the back wall of the room and 4 in (102 mm) from the side wall of the roo
24、m. The slots are to be oriented adjacent to either side wall of the room based on installation and position of the re test chamber. Windows are to be positioned as needed for observation. JUNE 27, 2012 UL 1666 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT P
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIUL16662007ULSTANDARDFORSAFETYTESTFORFLAMEPROPAGATIONHEIGHTOFELECTRICALANDOPTICALFIBERCABLESINSTALLEDVERTICALLYINSHAFTSFIFTHEDITIONREPRINTWITHREVISIOPDF

链接地址:http://www.mydoc123.com/p-438956.html