ANSI ISA 62453-301-2011 Field device tool (FDT) interface specification C Part 301 Communication profile integration C IEC 61784 CPF 1 (103.00.03)《现场设备工具(FDT)接口规范.第301部分 通信剖面综合.IEC.pdf
《ANSI ISA 62453-301-2011 Field device tool (FDT) interface specification C Part 301 Communication profile integration C IEC 61784 CPF 1 (103.00.03)《现场设备工具(FDT)接口规范.第301部分 通信剖面综合.IEC.pdf》由会员分享,可在线阅读,更多相关《ANSI ISA 62453-301-2011 Field device tool (FDT) interface specification C Part 301 Communication profile integration C IEC 61784 CPF 1 (103.00.03)《现场设备工具(FDT)接口规范.第301部分 通信剖面综合.IEC.pdf(148页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD ANSI/ISA62453-301 (103.00.03)2011 Field device tool (FDT) interface specification Part 301: Communication profile integration IEC 61784 CPF 1 Approved 31 May 2011 ANSI/ISA62453-301 (103.00.03)2011, Field device tool (FDT) interface specification Part 301: Communication pr
2、ofile integration IEC 61784 CPF 1 ISBN: 978-0-876640-57-9 Copyright 2011 IEC and ISA. These materials are subject to copyright claims of IEC and ISA. No part of this publication may be reproduced in any form, including an electronic retrieval system, without the prior written permission of ISA. All
3、requests pertaining to the ANSI/ISA62453-301 (103.00.03)-2011 Standard should be submitted to ISA. ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, North Carolina 27709 ANSI/ISA-62453-301 (103.00.03)-2011 - 3 - Preface This preface, as well as all footnotes and annexes, is included for
4、information purposes and is not part of ANSI/ISA62453-301 (103.00.03)2011. This document has been prepared as part of the service of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Towa
5、rd this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549 -8411; Fax (919) 549-8288; E-mail: standardsisa.org. The ISA
6、Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA stand
7、ards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end , this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical
8、 reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing the DTM shall provide support for the data described in 9.1.2; for each block in the device all standard block parameters shal
9、l be provided by the corresponding BTM object as specified in IEC ISA-62453 2 (103.00.02) It is recommended that all non-standard block parameters are also provided as specified in 9.2. A Device DTM shall provide access to the following groups of parameters if they are presented to the user: link pa
10、rameters; action parameters; alert parameters; ANSI/ISA-62453-301 (103.00.03)-2011 - 21 - trend parameters; domain objects; program invocation objects. 6.2 BTM BTMs built according to the function block specification shall expose all parameters for the corresponding block as defined for the DTM. All
11、 standard parameters defined for a block in the FF specification shall be exposed. The manufacturer specific parameters may be added to extend this list. User defined parameter shall be exposed if they exist. 7 Protocol specific behavior 7.1 Connection management The Connect service establishes an F
12、DT connection. The FDT connection acts as a container for FMS connections, as a container for SM connectionless services and as a container for FDA sessions. It is necessary to maintain the FMS connection separate from the underlying FDT connection. 7.1.1 FMS connection FDT implements all FMS and SM
13、 services as transactions in the respective protocols. This includes the services for the FMS connection management. FmsInitiate transaction and FmsAbort transaction manage the lifetime of a FMS connection. In order to open multiple FMS connections on the same FDT connection, a Transaction service r
14、equest is called with an FmsInitiateRequest element as argument. The communication reference passed with the FmsInitiateRequest element identifies the FDT connection to be used. The FmsInitiateResponse element returned with Transaction service response provides a communication reference used for all
15、 further FMS services on that FMS connection. This mapping allows multiple FMS connections on one FDT connection. ANSI/ISA-62453-301 (103.00.03)-2011 - 22 - Figure 4 FMS mapping in the FDT connection If the FDT connection is closed, the FMS connections for this connection are also closed automatical
16、ly (by the communication channel) before the FDT Disconnect service is completed. Any transactions requested after that will fail. No outstanding services will be processed. Figure 5 FDT Disconnect service FMSAbort service request closes a single FMS connection. IEC 1123/09 IEC 1124/09 ANSI/ISA-6245
17、3-301 (103.00.03)-2011 - 23 - 7.1.2 FDT connection FDT connection is using Connect service request: to establish an FDT connection intended for System Management services only. When FDT connections for SM services only are established, the OpenSessionRequest element is not part of the ConnectRequest
18、. Any request to establish an FMS connection on this type of FDT connection shall be rejected; to establish an FDT connection that represents a session as described with the specification FF-588 Field Device Access Agent. FMS connections can be established by using the FDT communication reference re
19、turned as a result of FDT connection establishment. Note that multicast SM services are not allowed in this connection. If an HSE device needs both types of connections it needs to create System management and FDT Session Connections. When a Frame Application requests the DTM to disconnect, all FMS
20、connections and FDT connections (SM and Session) shall be terminated. 7.2 Abort 7.2.1 OnAbort Indication At any moment during the lifetime of the (FDT or FMS) Connection an OnAbort event indication can be received by the DTM/BTM from the Communication Channel. There can be two reasons for OnAbort Ev
21、ent: FMS Connection Abort; FDT Connection Abort. The Communication reference uniquely identifies the Connection to be aborted. If a FDT Connection Abort is indicated, all FMS connections of the corresponding FDT Connection shall be terminated. No Abort requests are issued to the Communication Channe
22、l. All pending requests shall be cancelled. If an FMS Connection Abort is indicated, only the FMS Connection identified by that Communication Reference is terminated. 7.2.2 Abort request At any moment during the lifetime of the (FDT or FMS) connections a DTM/BTM can issue an Abort request to the Com
23、munication Channel. There can be two types of Communication References in the Abort request: FMS Communication Reference; FDT Communication Reference. The Communication reference uniquely identifies the Connection to be aborted. If an FDT Connection Abort is requested, all related FMS connections in
24、 the Communication channel shall be terminated. No separate Abort requests are issued to the Communication Channel for the individual FMS Connections. All pending requests shall be cancelled. ANSI/ISA-62453-301 (103.00.03)-2011 - 24 - If an FMS Communication Reference is used in the Abort, only the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIISA624533012011FIELDDEVICETOOLFDTINTERFACESPECIFICATIONCPART301COMMUNICATIONPROFILEINTEGRATIONCIEC61784CPF11030003

链接地址:http://www.mydoc123.com/p-436941.html