ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf
《ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf》由会员分享,可在线阅读,更多相关《ANSI ISA 61241-2-2006 Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization pD (12.10.06).pdf(38页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD ISA-61241-2 (12.10.06)-2006 (R2015) Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations Protection by Pressurization “pD” Reaffirmed 29 September 2015 ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) Electrical Apparatus for Use in Zone 21 and Zon
2、e 22 Hazardous (Classified) Locations Protection by Pressurization “pD” ISBN: 978-1-941546-39-0 Copyright 2015 by ISA. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form
3、 or by any means (electronic mechanical, photocopying, recording, or otherwise), without the prior written permission of the Publisher. ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, North Carolina 27709 - 3 - ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) Preface This preface, as well as a
4、ll footnotes and annexes, is included for information purposes and is not part of ANSI/ISA-61241-2 (12.10.06)-2006 (R2015). This document has been prepared as part of the service of ISA towards a goal of uniformity in the field of instrumentation. To be of real value, this document should not be sta
5、tic but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (
6、919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is furthe
7、r aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised
8、 standards, recommended practices, and technical reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing b) the maximum surface temperatures of internal parts that are protected by a
9、type of protection in accordance with IEC 61241-1-2.ANSI/ISA-61241-0 and which remain energized when the supply of protective gas for pressurization is removed or fails, for example electric heaters. If, during normal service, the temperatures of internal surfaces which may be exposed to an explosiv
10、e dust atmosphere exceed the maximum values permitted in IEC 61241-1-1 ANSI/ISA-61241-0, for the temperature class of the equipment, appropriate measures shall be taken to ensure that, if pressurization ceases, any explosive dust atmosphere which may exist is ANSI/ISA-61241-2 (12.10.06)-2006 (R2015)
11、 - 20 - prevented from making contact with that surface before it has cooled below the permitted maximum value. This may be achieved either by design and construction of the joints of the pressurized enclosure and ducts by other means, for example, by bringing alternative (or auxiliary) sources of p
12、rotective gas into operation, or by arranging that the hot surface within the enclosure is in a dust-tight or encapsulated housing. When determining the temperature for rotating electrical machines, the duty type according to IEC 60034-1 as specified by the manufacturer shall also be considered. 7 S
13、afety provisions and safety devices (except for static pressurization) 7.1 General Protective measures shall be adopted to prevent the electrical apparatus installed in a pressurized enclosure from being energized before pressurization is established. All safety devices shall either be a) protected
14、by an appropriate type of explosion-protection in accordance with IEC 61241-1-2 ANSI/ISA-61241-0, or b) non-electrical and not capable of causing ignition, or c) located in a non-hazardous area. The safety devices required by this standard form safety-related parts of a control system. It is the res
15、ponsibility of the manufacturer and the user to assess that the safety and integrity of the control system is appropriate. The safety devices shall be provided by the manufacturer of the apparatus or by the user. In the latter case, the apparatus shall be marked “X“ in accordance with 29.2 of ANSI/I
16、SA-61241-0 and the description documents shall contain all the necessary information required by the user to ensure conformity with the requirements of the standard. The enclosure shall be cleaned before the electrical supply to the system is connected or restored in order to remove any accumulated
17、combustible dust left in the enclosure, either accidentally following failure of the pressurization system, or following normal shutdown. Th e manufacturer shall provide the necessary instructions to the user detailing the requirements for cleaning the enclosure. The manufacturer shall specify the m
18、aximum and minimum action levels and tolerances of the safety devices. The safety devices shall be used within the normal operational limits as specified by the manufacturer taking due account of the most onerous conditions specified for normal service. 7.2 Pressure- or flow-activated devices Pressu
19、re-activated devices provided for the operation of alarm and electrical trip devices shall operate when the pressure within the enclosure falls below the permitted minimum value or exceeds the permitted maximum pressure. Flow-monitoring devices provided for the operation of alarm and electrical trip
20、 devices shall operate when the pressure within the enclosure falls below the permitted minimum value, or exceeds the permitted maximum pressure, and shall be located at the outlet. - 21 - ANSI/ISA-61241-2 (12.10.06)-2006 (R2015) An electrical interlock on the fan motors or controls is not suitable
21、to indicate failure of pressurization. It does not give an indication in the event of the fan belt slipping, the fan becoming loose on the shaft or reverse rotation of the fan. 7.3 Electrical supply Where protection is not provided to prevent the ingress of dust following the shutdown or failure of
22、the pressurization system, a warning label shall be fixed stating that dust shall be removed from the interior prior to switching on the electrical supply. 7.4 Switching off electrical supply When required by this standard, the switching-off of the electrical supply shall require the isolation of al
23、l live conductors, including the neutral, in accordance with IEC 61241-1-2ANSI/ISA-61241-0. 7.5 Failure of pressurization The design of a pressurization system relies on the principle that a failure of the pressurization automatically disconnects the system from the electricity supply and/or initiat
24、es alarms. To guard against the possibility that electrical apparatus protected by pressurization may cause an explosion in the case of the protective gas supply failure, the following measures shall be incorporated. They take into account the characteristics of the apparatus, prevailing environ -me
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIISA6124122006ELECTRICALAPPARATUSFORUSEINZONE21ANDZONE22HAZARDOUSCLASSIFIEDLOCATIONSPROTECTIONBYPRESSURIZATIONPD121006PDF

链接地址:http://www.mydoc123.com/p-436931.html