1、 American National Standard for Cleanroom Materials Flammability Test Protocol ANSI/FM Approvals 4910 ANSI/FM Approvals 4910-2013 Revision of ANSI/FM Approvals 4910-2004 Approved October 3, 2013 October 2013 2013 FM Approvals LLC. All rights reserved. Foreword NOTE: This foreword is introductory onl
2、y and is not part of American National Standard FM 4910. This standard is intended to verify that the product as described will meet minimum specific stated conditions of performance, safety and quality, useful in determining the potential suitability for end-use conditions of these products. It des
3、cribes minimum performance requirements for materials that are intended for use in cleanroom facilities by evaluating the ability of the materials and, in turn, the system components, to limit fire spread and smoke damage resulting from a fire in the cleanroom environment. This American National Sta
4、ndard has been developed according to the essential requirements of due process for standards development of the American National Standards Institute (ANSI). FM Approvals is an ANSI accredited standards developer (ASD). Approval of an American National Standard requires verification by ANSI that th
5、e principles of openness and due process have been followed and that a consensus of those directly and materially affected by the standard has been achieved. Consensus requires that all views and objections be considered, and that a concerted effort be made toward their resolution. Consensus is esta
6、blished when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached. The American National Standards Institute does not develop standards nor will it in any circumstances give an interpretation of any American National Standard. Requests for interpretations of
7、 this test standard should be addressed to FM Approvals. ANSI regulations require that this American National Standard shall be revised, reaffirmed or withdrawn within five years of the date of publication. FM Approvals 1151 Boston-Providence Turnpike P. O. Box 9102 Norwood, MA 02062 U. S. A. Phone:
8、 781-762-4300 Fax: 781-762-9375 E-mail: A TABLE OF CONTENTS 1. INTRODUCTION . 1 1.1 PURPOSE . 1 1.2 SCOPE . 1 1.3 BASIS FOR REQUIREMENTS . 1 1.4 APPLICABLE DOCUMENTS . 1 1.5 DEFINITIONS 1 2. GENERAL INFORMATION 2 2.1 CLEANROOMS 2 2.2 FPI AND SDI 2 2.3 REQUIRED TESTS 2 2.4 UNCERTAINTY RANGES OF FPI A
9、ND SDI 3 2.5 MATERIALS THINNER THAN 0.25 IN. (6 MM) 3 3. FIRE PROPAGATION APPARATUS TESTS 3 3.1 TEST SAMPLES . 3 3.2 SAMPLE PREPARATION AND PLACEMENT IN THE APPARATUS 3 3.3 IGNITION TEST . 5 3.4 FIRE PROPAGATION TEST . 6 3.5 COMBUSTION TEST 7 4. PARALLEL PANEL FIRE TEST . 8 4.1 PURPOSE . 8 4.2 PARAL
10、LEL PANEL TEST ARRANGEMENT . 8 4.3 CONDUCT OF TEST . 10 5. PROCEDURES TO CALCULATE FLAMMABILITY DATA . 11 5.1 IGNITION TEST DATA CALCULATION PROCEDURE . 11 5.2 CHEMICAL HEAT RELEASE RATE CALCULATION 12 5.3 FIRE PROPAGATION TEST DATA CALCULATION PROCEDURE . 14 5.4 COMBUSTION TEST DATA CALCULATION PRO
11、CEDURE 14 5.5 SMOKE DAMAGE INDEX (SDI) CALCULATION 14 6. CONDITIONS OF ACCEPTANCE 15 6.1 FIRE PROPAGATION APPARATUS TESTS 15 6.2 PARALLEL PANEL FIRE TESTS . 15 October 2013 ANSI/FM Approvals 4910 FM Approvals 1 1. INTRODUCTION 1.1 PURPOSE This test standard states test requirements and procedures fo
12、r the evaluation of materials used in cleanroom occupancies mainly for, but not restricted to, use in the semiconductor industry. The test evaluates the materials fire propagation behavior, expressed as Fire Propagation Index (FPI), and potential for smoke contamination, expressed as Smoke Damage In
13、dex (SDI). 1.2 SCOPE 1.2.1 This test standard describes minimum performance requirements for materials which are intended for use in cleanroom facilities. This standard evaluates the ability of the materials to limit fire spread and smoke damage. All requirements in the standard must be met for mate
14、rials to be acceptable. 1.2.2 This standard is intended to verify that the materials, as described, will meet minimum specific stated conditions of performance, safety and quality useful in determining the potential suitability for end-use conditions of these materials. 1.3 BASIS FOR REQUIREMENTS 1.
15、3.1 The requirements of this test standard are based on experience, research and testing, and/or the standards of other organizations. The advice of manufacturers, users, trade associations, jurisdictions and/or loss control specialists was also considered. 1.4 APPLICABLE DOCUMENTS The following sta
16、ndards, test method descriptions and practices are related to this standard: 1. Tewarson, A., Generation of Heat and Chemical Compounds in Fires, Chapter 4, Section 3, pp. 3-82 to 3-161. The SFPE Handbook of Fire Protection Engineering, 3rd Edition. The National Fire Protection Association Press, Qu
17、incy, MA, June 2002. 2. Tewarson, A., Flammability, Chapter 42, pp. 577-604. Physical Properties of Polymers Handbook (J.E. Mark, Editor). American Institute of Physics, Woodbury, NY, 1996. 3. ASTM E2058 Standard Test Methods for Measurement of Synthetic Polymer Material Flammability Using a Fire Pr
18、opagation Apparatus (FPA),American Society for Testing and Materials, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. 4. NFPA 287 Standard Test Methods for Measurement of Flammability of Materials in Cleanrooms Using a Fire Propagation Apparatus (FPA)”, National Fire Protection Association,
19、 1 Batterymarch Park, Quincy, MA 02269. 1.5 DEFINITIONS For purposes of this test standard, the following terms apply: Chemical Heat Release Rate (Qch): energy actually released by chemical reactions during a test Critical Heat Flux (CHF): the maximum heat flux at, or below, which there is no igniti
20、on. October 2013 ANSI/FM Approvals 4910 FM Approvals 2 Fire Propagation Index (FPI ): an index representing the propensity of a material to support fire propagation. Flame Height: elevation of the tip of the contiguous flame region averaged over a 5-second interval Ignition Zone: the area of the sur
21、face of a material heated by an outside source, resulting in ignition. Smoke Damage Index (SDI): smoke yield multiplied by FPI. It is an indicator of thesmoke contamination of the environment during fire propagation. Smoke yield (ys) ratio of the total mass of smoke released to the total mass of the
22、 material vaporized. Thermally Thick Behavior: when a material is heated on one side and exhibits a negligible temperature rise above ambient on the unexposed face of the material. Thermally Thin Behavior: when a material is heated on one side and there is a uniform temperature rise across the thick
23、ness of a material. Thermal Response Parameter (TRP): indicator of the ignition resistance of a material. 2. GENERAL INFORMATION 2.1 CLEANROOMS Due to the sensitivity of cleanroom environments, the high cost of construction and the high value of equipment and products produced and stored in them, si
24、gnificant damage can be caused by the presence of small amounts of contamination. As a result, it is useful to evaluate the ability of a material to limit fire propagation and restrict emission of particulates in the form of smoke. The criteria for the selection of materials for use in cleanrooms ar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIFM49102013CLEANROOMMATERIALSFLAMMABILITYTESTPROTOCOL 清洁 材料 可燃性 试验 协议 PDF

链接地址:http://www.mydoc123.com/p-434791.html