ANSI ATIS 0600015.04-2010 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting DC Power Plant - Rectifier Requirements.pdf
《ANSI ATIS 0600015.04-2010 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting DC Power Plant - Rectifier Requirements.pdf》由会员分享,可在线阅读,更多相关《ANSI ATIS 0600015.04-2010 Energy Efficiency for Telecommunication Equipment Methodology for Measurement and Reporting DC Power Plant - Rectifier Requirements.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、 AMERICAN NATIONAL STANDARD FOR TELECOMMUNICATIONS ATIS-0600015.04.2010 ENERGY EFFICIENCY FOR TELECOMMUNICATION EQUIPMENT: METHODOLOGY FOR MEASUREMENT AND REPORTING DC POWER PLANT RECTIFIER REQUIREMENTS ATIS is the leading technical planning and standards development organization committed to the ra
2、pid development of global, market-driven standards for the information, entertainment and communications industry. More than 250 companies actively formulate standards in ATIS 18 Committees, covering issues including: IPTV, Service Oriented Networks, Energy Efficiency, IP-Based and Wireless Technolo
3、gies, Quality of Service, and Billing and Operational Support. In addition, numerous Incubators, Focus and Exploratory Groups address emerging industry priorities including “Green”, IP Downloadable Security, Next Generation Carrier Interconnect, IPv6 and Convergence. ATIS is the North American Organ
4、izational Partner for the 3rd Generation Partnership Project (3GPP), a member and major U.S. contributor to the International Telecommunication Union (ITU) Radio and Telecommunications Sectors, and a member of the Inter-American Telecommunication Commission (CITEL). For more information, please visi
5、t . AMERICAN NATIONAL STANDARD Approval of an American National Standard requires review by ANSI that the requirements for due process, consensus, and other criteria for approval have been met by the standards developer. Consensus is established when, in the judgment of the ANSI Board of Standards R
6、eview, substantial agreement has been reached by directly and materially affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a concerted effort be made towards their
7、resolution. The use of American National Standards is completely voluntary; their existence does not in any respect preclude anyone, whether he has approved the standards or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standards. T
8、he American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue an interpretation of an American National Standard in the name of the American Nat
9、ional Standards Institute. Requests for interpretations should be addressed to the secretariat or sponsor whose name appears on the title page of this standard. CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards
10、Institute require that action be taken periodically to reaffirm, revise, or withdraw this standard. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute. Notice of Disclaimer 2) controlled ferroreso
11、nant; and 3) switchmode (newest). This standard will include the most common North American single phase and three phase 120, 208, 240, 277, 480 Volt AC input and +/- 24, 48, 130, 190 Volt DC outputs. There are additional standard voltages used internationally; those are listed in the Annex. 5 METRI
12、C DEFINITION 5.1 Preamble For the evaluation of power plant rectifiers, it is necessary to consider normal operating conditions over the life cycle of the rectifier(s). A rectifier can be expected to operate between 40% and 80% of rated capacity dependent on application. In telecommunication power p
13、lants, variables include: Power forecasts Engineering planning cycle Redundancy Recharge requirements Rectifier efficiency varies over the load range. Efficiency will be 0% at no load, achieve peak efficiency, and drop off at max load. The rise to peak efficiency varies by technology. Presently, the
14、 switchmode rectifier technology offers the highest peak operating efficiency. Therefore, rectifier selection should be matched to the application, sizing the rectifiers to operate in the range where the efficiency is highest. Power plant control and energy management are beyond the scope of this st
15、andard. ATIS-0600015.04.2010 4 Figure 1: Sample Switchmode Rectifier Efficiency Curve 5.2 Rectifier TEER If we define the efficiency as the ratio of power dissipated by a specific load and power drawn from the source, then it is straightforward to calculate the Rectifier TEER from the equation below
16、. Efficiency: INOUTPP=Where: is efficiency. POUTis simply the DC output voltage multiplied by the current. PINis the RMS voltage at the input multiplied by the current multiplied by the power factor and for 3 multiplied by 3. 1 AC Power in Watts: PFIVP INININ =Where: VIN= Input Voltage. ATIS-0600015
17、.04.2010 5 IIN= Input Current. PF = Power Factor. 3 AC Power in Watts: 3= PFIVP INININWhere: VIN= Input Voltage. IIN= Input Current. PF = Power Factor. 3= Phase angle displacement. DC Power in Watts: OUTOUTOUT IVP =Where: VOUT= Output Voltage. IOUT= Output Current. The rectifier TEER is a summation
18、of the efficiency measurements at 10% intervals from 30%-80% EUT capacity divided by the number of samples. The TEER has a maximum value of 1000. TEER Formula: 10006%)10(83=iiTEERWhere: i= multiple of 10% of rectifier rating. 6 TEST PROCEDURE 6.1 Measurements The test methodology and test conditions
19、 used to independently verify the power consumption shall meet the requirements called out in ATIS-0600015.2009, as well as this document. Where conflicts occur, this document supersedes other standards. ATIS-0600015.04.2010 6 6.2 Equipment Configuration The EUT shall be evaluated with a source prov
20、iding the following conditions: A power source with a rating of at least 2X the maximum input power rating of the rectifier. Total Harmonic Distortion 2% up to and including the 13th harmonic: (RMS)1322(%)V100=hhVTHD AC input voltage shall be the specified nominal voltage and frequency 1%. Rectifier
21、s designed to operate at multiple input voltages shall be tested at each nominal operating input voltage - e.g. 120,208,240,480, etc. The AC voltage measured at the input of the rectifier shall not vary over the load range. A power analyzer shall be connected at the input terminals and the following
22、 measurements shall be recorded at the prescribed loads as required in 7.1, Table 1: Input Voltage Input Current Input Power Input kVA Input Power Factor A variable resistive load bank with sufficient capacity for at least 110% of the maximum output rating of the rectifier shall be connected to the
23、load terminals. Output voltage shall be adjusted to 53 Vdc 1 V. A power analyzer shall be connected at the output terminals and the following measurements shall be recorded simultaneously with the input measurements as required in Table 1: Output Voltage Output Current Output Power 7 REPORTING & DOC
24、UMENTATION 7.1 Power Measurement Data All products claiming compliance with this specification shall provide the information as defined the ATIS-0600015.2009. In addition, the report shall include the following nameplate information and Table 1: Input Voltage Output Voltage Number of Phases Total Ha
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIATIS0600015042010ENERGYEFFICIENCYFORTELECOMMUNICATIONEQUIPMENTMETHODOLOGYFORMEASUREMENTANDREPORTINGDCPOWERPLANTRECTIFIERREQUIREMENTSPDF

链接地址:http://www.mydoc123.com/p-433455.html