ANSI ASTM F481-1997 Standard Practice for Installation of Thermoplastic Pipe and Corrugated Pipe in Septic Tank Leach Fields.pdf
《ANSI ASTM F481-1997 Standard Practice for Installation of Thermoplastic Pipe and Corrugated Pipe in Septic Tank Leach Fields.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM F481-1997 Standard Practice for Installation of Thermoplastic Pipe and Corrugated Pipe in Septic Tank Leach Fields.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F481 97 (Reapproved 2014)Standard Practice forInstallation of Thermoplastic Pipe and Corrugated Pipe inSeptic Tank Leach Fields1This standard is issued under the fixed designation F481; the number immediately following the designation indicates the year of originaladoption or, in the ca
2、se of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A superscriptepsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice describes procedures for handling andinstalling thermoplastic pipe and corru
3、gated pipe in septic tankleach fields, curtain drains, and from the septic tank to the leachfield. Proper installation ensures that the pipe will satisfactorilyconvey and distribute partially treated waste water to aleaching field for additional treatment and disposal by soilabsorption. The curtain
4、or perimeter drain will function toprotect the soil absorption capacity of the leach field.1.2 To ensure compliance with local regulatory provisions,the local approving authority (local health departments and soforth) should be contacted regarding specific requirements forleach field design material
5、s and installation.1.3 This practice applies to pipe and fittings made undereach of the following ASTM specifications:1.3.1 For transport from tank to leach field: SpecificationsD2680, D2729, D2751, D2852, D3034, F405, F758, F789,F810, F891, F892, and F949.1.3.2 Perforated, for use in leach field or
6、 curtain drain:Specifications D2729, D2751, F405, F810, F891, and F892.1.4 Pipe intended for installation in accordance with thispractice should have a minimum pipe stiffness as specified inthe appropriate product standard referenced in 1.3.1 or 1.3.2.1.5 The values stated in inch-pound units are to
7、 be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of
8、the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificprecautionary statements, see Section 7.2. Referenced Documents2.1 ASTM Standards:2D1600 Terminology forAbbreviated Terms Relating to P
9、las-ticsD2321 Practice for Underground Installation of Thermoplas-tic Pipe for Sewers and Other Gravity-Flow ApplicationsD2680 Specification for Acrylonitrile-Butadiene-Styrene(ABS) and Poly(Vinyl Chloride) (PVC) Composite SewerPipingD2729 Specification for Poly(Vinyl Chloride) (PVC) SewerPipe and F
10、ittingsD2751 Specification for Acrylonitrile-Butadiene-Styrene(ABS) Sewer Pipe and Fittings (Withdrawn 2014)3D2852 Specification for Styrene-Rubber (SR) Plastic DrainPipe and FittingsD3034 Specification for Type PSM Poly(Vinyl Chloride)(PVC) Sewer Pipe and FittingsF405 Specification for Corrugated P
11、olyethylene (PE) Pipeand FittingsF412 Terminology Relating to Plastic Piping SystemsF449 Practice for Subsurface Installation of CorrugatedPolyethylene Pipe for Agricultural Drainage or WaterTable ControlF758 Specification for Smooth-Wall Poly(Vinyl Chloride)(PVC) Plastic Underdrain Systems for High
12、way, Airport,and Similar DrainageF789 Specification for Type PS-46 and Type PS-115 Poly-(Vinyl Chloride) (PVC) Plastic Gravity Flow Sewer Pipeand Fittings (Withdrawn 2004)3F810 Specification for Smoothwall Polyethylene (PE) Pipefor Use in Drainage and Waste DisposalAbsorption FieldsF891 Specificatio
13、n for Coextruded Poly(Vinyl Chloride)(PVC) Plastic Pipe With a Cellular CoreF892 Specification for Polyethylene (PE) Corrugated PipeWith a Smooth Interior and Fittings (Withdrawn 2001)31This practice is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsib
14、ility of Subcommittee F17.65 on LandDrainage.Current edition approved Aug. 1, 2014. Published November 2014. Originallyapproved in 1976. Last previous edition approved in 2008 as F481 97(2008). DOI:10.1520/F0481-97R14.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact AS
15、TM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box
16、 C700, West Conshohocken, PA 19428-2959. United States1F949 Specification for Poly(Vinyl Chloride) (PVC) Corru-gated Sewer Pipe With a Smooth Interior and Fittings3. Terminology3.1 Definitions are in accordance with Terminology F412and abbreviations are in accordance with Terminology D1600,unless ot
17、herwise specified.3.2 Definitions of Terms Specific to This Standard:3.2.1 dual-wall pipepipe with corrugated exterior andsmooth interior.3.2.2 pipesmooth or corrugated interior wall thermoplas-tic pipe.4. General Requirements4.1 StoragePipe should be stored with support from a flatsurface to preven
18、t the pipe from developing a permanent set.4.2 HandlingCare should be exercised during loading,unloading, and in transit because pipe may be damaged byabrasion and sharp edges. Because thermoplastics are tempo-rarily softened by high temperatures, care should be takenunder these conditions to avoid
19、damage during handlingoperations.4.3 If contact with chemicals not ordinarily present insanitary sewage is anticipated, the approval of the regulatoryauthority to install pipe should be obtained.NOTE 1The manufacturer should be contacted for information onchemical resistance.4.4 Coiled pipe is not r
20、ecommended for use in leach fieldsbecause it is difficult to install at the proper grade andalignment; it is acceptable with special equipment installation.NOTE 2Corrugated interior pipe should not be used between thedwelling and the waste water treatment unit (septic tank or similar device)because
21、the corrugations may inhibit the flow of solids contained in thewaste.5. InstallationLeach Field5.1 Leach fields should be constructed to meet the require-ments of the local Department of Health or other governingauthority, which should be contacted for information andrequirements on design, locatio
22、n, installation, materials, and soforth.5.2 Before installation, pipe should be inspected for damagesuch as kinks, crushed portions, splits, and so forth. Anydamaged portions of pipe shall be cut out as a cylinder anddiscarded. Make a visual check of the bore to ensure it is clearof foreign objects
23、that might impede flow.5.3 Gravel SystemsFor proper waste water flow into thesurrounding soils and to provide for support of pipe, a uniformlayer of 4 to 6 in. (100 to 150 mm) of graded aggregate shouldbe placed in the trench bottom and leveled true to grade priorto laying the pipe (see Fig. 1). Agg
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTMF4811997STANDARDPRACTICEFORINSTALLATIONOFTHERMOPLASTICPIPEANDCORRUGATEDPIPEINSEPTICTANKLEACHFIELDSPDF

链接地址:http://www.mydoc123.com/p-433262.html