《ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM F2975-2012 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems《商用厨房通风系统的野外使用特性测量方法》.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F2975 12 (Reapproved 2017) An American National StandardStandard Test Method forMeasuring the Field Performance of Commercial KitchenVentilation Systems1This standard is issued under the fixed designation F2975; the number immediately following the designation indicates the year oforigi
2、nal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method can be used to measure and validatesuccessful d
3、esign, installation and commissioning of commer-cial kitchen HVAC and makeup air systems for specificinstallations.1.2 This test method field evaluates commercial kitchenventilation system airflows and pressures.1.3 This test method field evaluates visual hood capture andcontainment performance.1.4
4、The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are for informa-tion only.1.5 The data generated is specific to the field conditions asinstalled.1.6 This test method may involve hazardous materials,gasses (for example, CO) operations, and equipmen
5、t. Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.1.7 This internatio
6、nal standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Commit
7、tee.2. Referenced Documents2.1 ASTM Standards:2F1704 Test Method for Capture and Containment Perfor-mance of Commercial Kitchen Exhaust Ventilation Sys-tems2.2 Other Standards:ANSI/ASHRAE Standard 111-2008 Measurement, Testing,Adjusting and Balancing of Building HVAC Systems3ANSI/ASHRAE Standard 154
8、 Ventilation for CommercialCooking Operations3Testing, Adjusting and Balancing, Chapter 37 2007 HVACApplications Handbook4Kitchen Ventilation, Chapter 31 2007 HVAC ApplicationsHandbook43. Terminology3.1 Definitions:3.1.1 airflow ratevolumetric flow rate of air in units offt3/min (cfm) or m3/s. When
9、adjusted for standard air densitythe flow rate is designated by scfm.3.1.2 appliancecooking device used in kitchen and pow-ered by gas, and/or electricity and/or solid fuel.3.1.3 barometric pressureabsolute pressure of the airmeasured by a barometer or absolute pressure measuringdevice.3.1.4 capture
10、 and containment (C the performance ofthe ventilation system should be checked to verify that thedesign is adequate for the actual operation, particularly atmaximum cooking and at outdoor environmental extremes.Any necessary changes should be made, and all the recordsshould be updated to show the ch
11、anges. Rechecking the airbalance should not be necessary more than once every 2 yearsunless significant changes are made in facility operation. Ifthere are major changes, such as a new type of cookingequipment or added or deleted exhaust connections, the systemshould be modified accordingly and reba
12、lanced.10.2 Exhaust Air Flow Rate Measurements Through KitchenExhaust Hoods:10.2.1 The total air flow rate through each exhaust hoodshall be determined using one of the following methods withthe cooking appliances turned at hot ready-to-cooking condi-tion.10.2.1.1 When a specific air flow rate measu
13、rement protocolis specified by the hood or filter manufacturer, the protocoldeveloped by the manufacturer shall be followed.10.2.1.2 When the filters under test have no protocol fromthe manufacturer but has a protocol specified in this document,the method of test specified in this document shall be
14、followed.10.2.1.3 When the filters under test have no protocol fromthe manufacturer and do not have a protocol specified in thisdocument, or one or more obstructions prevents proper use offace velocity measuring instruments, a duct traverse methodshall be used to determine the total air flow rate th
15、rough anexhaust hood using a Pitot-static tube. The Log-Tchebycheffrule shall be used for rectangular ducts and the Log-linear rulefor circular ducts as specified in ANSI/ASHRAE Standard111-2008, ”Measurement, testing, adjusting and balancing ofbuilding HVAC systems”.10.2.2 Hoods with Baffle Filters
16、:10.2.2.1 These measurements are limited to the use ofa4in.rotating vane anemometer with its body parallel to andpositioned flush to the filter face.FIG. 1 Baffle FilterF2975 12 (2017)510.2.2.2 Each filter in an exhaust hood must be evaluatedseparately and the flow rate through each filter added tod
17、etermine the total airflow rate through the entire exhausthood.10.2.2.3 The dimensions of the open portion, height andwidth (H and W), of each filter shall be measured with anaccuracy of 614 inch and the results recorded.10.2.2.4 The center of the rotating vane anemometer shalltraverse the entire fa
18、ce of the filter in a back-and forth motion.The minimum time to traverse the entire filter face shall be 30s. An example is shown in Fig. 2. Average velocity readingsshall be measured and recorded at each location.10.2.2.5 The body of the instrument shall remain flush to theexterior surface of the f
19、ilters, and be kept parallel to it.10.2.2.6 Airflow through the instrument shall not be ob-structed by the operators hand or fingers.10.2.2.7 The velocity measurements in a filter bank shall bemeasured beginning with the filter at one end of the filter bankand ending with the filter at the opposite
20、end.10.2.2.8 The procedure described above shall be repeatedtwice more to obtain the average velocity for all three readingsat each location in feet per minute (FPM).10.2.3 Hoods with Cyclone Filters:10.2.3.1 These measurements are limited to the use of a234-in. diameter rotating vane anemometer wit
21、h its bodyparallel to and positioned 2 in. from the filter face.10.2.3.2 Each filter in an exhaust hood must be evaluatedseparately and the flow rate through each filter added togetherto determine the total airflow rate through the entire exhausthood.10.2.3.3 The gross dimensions (height and width)
22、of theopening areas of each filter shall be measured and recorded.10.2.3.4 The velometer shall traverse each opening a mini-mum of 30 s. Fig. 4 shows the positions by “X” for an entirefilter bank of cyclone filters.Average velocity readings shall bemeasured and recorded at each location.10.2.3.5 The
23、 body of the anemometer must remain 2 in.from the exterior surface of the filters, and be kept parallel toit.Asmall indicator shall be attached to the exterior body of theanemometer to maintain the 2 in. spacing.10.2.3.6 The vane must attain full speed at each positionbefore the velocity is recorded
24、.10.2.3.7 The airflow through the anemometer shall not beobstructed by the operators hand or fingers.10.2.3.8 The velocity measurements in a filter bank shall bemeasured beginning with the filter at one end of the filter bankand ending with the filter at the opposite end.10.2.3.9 The procedure descr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTMF29752012STANDARDTESTMETHODFORMEASURINGTHEFIELDPERFORMANCEOFCOMMERCIALKITCHENVENTILATIONSYSTEMS

链接地址:http://www.mydoc123.com/p-433237.html