ANSI ASTM F1883-2003 Standard Practice for Selection of Wire and Cable Size in AWG or Metric Units《用美国线规(AWG)或米制单位选择电线和电缆规格的实施规程》.pdf
《ANSI ASTM F1883-2003 Standard Practice for Selection of Wire and Cable Size in AWG or Metric Units《用美国线规(AWG)或米制单位选择电线和电缆规格的实施规程》.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM F1883-2003 Standard Practice for Selection of Wire and Cable Size in AWG or Metric Units《用美国线规(AWG)或米制单位选择电线和电缆规格的实施规程》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1883 03 (Reapproved 2013) An American National StandardStandard Practice forSelection of Wire and Cable Size in AWG or Metric Units1This standard is issued under the fixed designation F1883; the number immediately following the designation indicates the year oforiginal adoption or, in
2、the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice is intended as a guide to shipbuilders,shipowners, and design agents f
3、or use in the selection ofconductor size for single conductor or multiple conductor cablesizes either in American Wire Gauge (AWG) or metric desig-nations for commercial ship design and construction.1.2 The comparison chart of electrical conductor sizesshown in Table 1 presents a combined listing of
4、 internationalstandard sizes of Class 2 stranded copper conductors inaccordance with AWG (Specification B8) English units or IEC(IEC 60228) metric units.1.3 As a precautionary caveat, some conductor sizes listedin Table 1 may exceed minimal size requirements of the U.S.Coast Guard, theAmerican Burea
5、u of Shipping, and IEEE STD45 for specific applications.1.4 The values stated for ampacity and dc resistance arepresented as maximum values and are provided for informationonly.2. Referenced Documents2.1 ASTM Standards:2B8 Specification for Concentric-Lay-Stranded CopperConductors, Hard, Medium-Hard
6、, or SoftB193 Test Method for Resistivity of Electrical ConductorMaterials2.2 IEC Standards:3IEC 60092-350 Electrical Installations in ShipsPart 350:Shipboard Power: CablesGeneral Construction and TestRequirementsIEC 60228 Conductors of Insulated Cables2.3 IEEE Standard:4IEEE STD 45 Recommended Prac
7、tice for Electric Installa-tions on Shipboard3. Significance and Use3.1 The selection criteria is to be applied for uses of (1) newcable and (2) replacement cable.3.2 For the selection of new cable or the selection ofreplacement cable, this practice defines the choice criteria forconductor selection
8、 for cables in AWG (ASTM) or metric(IEC) sizes.4. Selection Criteria4.1 When selecting cable for any application, AWG ormetric sizing should be selected according to preferred sizes.The sizes of conductors that have been marked with an asteriskin Table 1 designate preferred sizes per Specification B
9、8 andIEC 60228. Those sizes not marked are given for reference,and it is recommended that their use be discouraged.4.2 When selecting cable for any application, AWG ormetric sizing should be selected with full consideration of therelationship of type of insulation and ampacity. Direct selectionbetwe
10、en AWG and metric sizes can be made only after adetermination of the equivalence of insulation is made.4.3 When selecting cable, the conductor size will be deter-mined from analysis of required ampacity, voltage dropconsiderations, type of cable insulation, and planned installa-tion. Recommended pra
11、ctices for selection and installation ofcable systems are detailed in IEEE STD 45 and IEC 60092-350.4.4 For the selection of cable sizes for new applications,conductor size that satisfies ampacity requirements, voltagedrop factors, and the adequacy for application in the availablecable space must al
12、so be considered.4.5 For the selection of cable sizes for replacementapplications, cable size should be selected in excess of or equalto the replaced cable size. Existing cable space limitationsshould then be determined to ensure that space for installationof the replacement cable is adequate.1This
13、specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Technologyand is the direct responsibility of Subcommittee F25.10 onElectrical.Current edition approved May 1, 2013. Published May 2013. Originallyapproved in 1998. Last previous edition approved in 2008 as F1883 03 (20
14、08).DOI: 10.1520/F1883-03R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from International El
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTMF18832003STANDARDPRACTICEFORSELECTIONOFWIREANDCABLESIZEINAWGORMETRICUNITS 美国 线规 AWG 米制 单位 选择

链接地址:http://www.mydoc123.com/p-432943.html