ANSI ARI 580-2001 Non-Condensible Gas Purge Equipment for Use with Low Pressure Centrifugal Liquid Chillers《低压离心液体冷冻装置上使用的不凝性气体吹洗设备》.pdf
《ANSI ARI 580-2001 Non-Condensible Gas Purge Equipment for Use with Low Pressure Centrifugal Liquid Chillers《低压离心液体冷冻装置上使用的不凝性气体吹洗设备》.pdf》由会员分享,可在线阅读,更多相关《ANSI ARI 580-2001 Non-Condensible Gas Purge Equipment for Use with Low Pressure Centrifugal Liquid Chillers《低压离心液体冷冻装置上使用的不凝性气体吹洗设备》.pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、 4100 N. FAIRFAX DR.,STE.200 z ARLINGTON, VIRGINIA 22203 / 2001 STANDARD for NON- CONDENSABLE GAS PURGE EQUIPMENT FOR USE WITH LOW PRESSURE CENTRIFUGAL LIQUID CHILLERS ANSI/ARI Standard 580 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo
2、reproduction or networking permitted without license from IHS-,-,-Price $10.00 (M) $20.00 (NM) Copyright 2001, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does
3、 not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally re
4、cognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its stan
5、dards/guidelines will be non-hazardous or free from risk. ARI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification Program includes testing purge systems used in conjunction with low pressure centrifugal liquid chillers. Certified Ratings The following Certification
6、Program ratings are verified by test: 1. Concentration, ratio of mass of refrigerant to mass of air, g of refrigerant / g of air at the Refrigerant Holding Capacity where applicable. Note: This standard supersedes ARI Standard 580-2001. Copyright Air-Conditioning and Refrigeration Institute Provided
7、 by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Test Requirements2 Section 5. Rating Requirements 2 Section 6. Minimum Data Req
8、uirements for Published Ratings.2 Section 7. Marking and Nameplate Data.2 Section 8. Conformance Conditions3 APPENDICES Appendix A. References - Normative4 Appendix B. References - Informative 4 Appendix C. Methods of Testing for Rating Performance of Non-Condensable Gas Purge Equipment - Normative.
9、5 Appendix D. Specific Rating and Testing Instructions for Purges Containing Adsorptive/Absorptive Media - Normative.9 Appendix E. Calculation of Purge Equipment Concentration Rating - Normative.11 Appendix F. Determination of Discharge Gas Concentration For Non-Condensable Gas Purge Equipment Testi
10、ng - Normative12 FIGURES FOR APPENDICES Figure C1. Activated Carbon Sampling Method6 Figure C2. Gas Chromatograph Sampling Method7 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from I
11、HS-,-,-Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ANSI/ARI STANDARD 580-2001 1 NON-CONDENSABLE GAS PURGE EQUIPMENT FOR USE WITH LOW PRESSURE CENTRIFUGAL LIQUID CHILLER
12、S Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Non-Condensable Gas Purge Equipment for use with Low Pressure Centrifugal Liquid Chillers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate da
13、ta; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 S
14、cope. This standard applies to Non-Condensable Gas Purge Equipment for use with Low Pressure Centrifugal Liquid Chillers as defined in Section 3. This standard defines general equipment requirements, test methods and analysis techniques used to determine the performance rating for Purge Equipment th
15、at remove Non-Condensable gases from Low Pressure Centrifugal Liquid Chillers. This purge equipment is typically used in conjunction with chillers which operate with at least a portion of the system below atmospheric pressure. Section 3. Definitions All terms in this document shall follow the standa
16、rd industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air-Conditioning, and Refrigeration unless otherwise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Dew Point. Refrigerant vapor saturation
17、 temperature at a specified pressure. 3.3 Low Pressure Centrifugal Liquid Chiller. A Centrifugal Liquid Chiller that typically has a portion of the refrigerating system below atmospheric pressure (100 kPa) when operated at typical conditions for comfort cooling applications. 3.4 Non-Condensable Gase
18、s. Gases which do not condense at normal operating temperatures and pressures in centrifugal water-chiller condensers, such as nitrogen and oxygen. 3.5 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be ch
19、osen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of all performance characteristics shown on the unit or published in specification, advertising
20、 or other literature controlled by the manufacturer, at stated Rating Conditions. 3.5.1 Application Rating. A rating based on tests performed at Application Rating Conditions (other than Standard Rating Conditions). 3.5.2 Standard Rating. A rating based on tests performed at Standard Rating Conditio
21、ns. 3.6 Purge Equipment. A device which will separate Non-Condensable Gases from refrigerant and remove them from the refrigeration system. 3.6.1 Automatically Regenerated Media. Media that is recycled at the purge system to remove entrained refrigerant and return this refrigerant to the chiller. Th
22、e regeneration process is initiated automatically by the purge control system. 3.6.2 Manually Regenerated Media. Media that is recycled at the purge system to remove entrained refrigerant and return this refrigerant to the chiller. The regeneration process is setup and initiated by an operator. 3.6.
23、3 Refrigerant Holding Capacity. The amount of refrigerant, designated by the manufacturer, at which the media on the purge device needs to be replaced or regenerated. 3.6.4 Replaceable Media. Media that is removed from the system and replaced with new or recycled media. The media from the system is
24、processed to ensure refrigerant is not released to the atmosphere. 3.7 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIARI5802001NONCONDENSIBLEGASPURGEEQUIPMENTFORUSEWITHLOWPRESSURECENTRIFUGALLIQUIDCHILLERS 低压 离心 液体

链接地址:http://www.mydoc123.com/p-431084.html