《ANSI American Society of Sanitary Engineering 1048-2011 Performance Requirements for Double Check Detector Fire Protection Backflow Prevention Assemblies.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1048-2011 Performance Requirements for Double Check Detector Fire Protection Backflow Prevention Assemblies.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、ASSE Standard #1048-2011ASSE Board Approved: August 2011 ANSI Approved: August 2011 An American National StandardPerformance Requirements for Double Check Detector Fire Protection Backflow Prevention AssembliesASSE InternationalDouble Check Detector Fire Protection Backflow Prevention Assemblies iAS
2、SE 1048-2011General InformationNeither this standard, nor any portion thereof, may be reproduced without the written consent of the ASSE International.Instructions for receiving authorization to display the ASSE Seal are available from ASSEs International Office. Organizations wishing to adopt or li
3、st any ASSE Standard should print the ASSE Standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.ASSE InternationalMokena, IllinoisCopyright 2011, 2009, 2005, 1999, 1993, 1990All rights reserved.ii Double Check Detector Fire Protection Ba
4、ckflow Prevention AssembliesASSE 1048-2011Double Check Detector Fire Protection Backflow Prevention Assemblies iiiASSE 1048-2011ForewordThis foreword shall not be considered a part of the standard. However, it is offered to provide background information.ASSE Product Standards are developed in the i
5、nterest of consumer safety.The recognition of probable sources or causes of contamination of a potable water supply system and the application of essential devices, or means, to prevent the entrance of contaminants to the potable water system, causing it to become unfit for human consumption, is vit
6、al to the maintenance of its continued potability.This standard focuses on those devices, known as Double Check Detector Fire Protection Backflow Prevention Assemblies (RPDF), which will fulfill this protective need. This standard was retitled during the 1999 revision to add “fire protection” to bet
7、ter describe the devices primary use.Typically installed but not limited to fire protection systems, the devices described are primarily designed for two functions. The protection of the public water supply from contaminants found in fire sprinkler systems is a primary function for a backflow preven
8、ter. These assemblies are also designed to detect low rates of flow up to 2.00 GPM (0.13 L/s) within the sprinkler system caused by leakage or unauthorized use. This standard also allows provisions for alarm signaling devices to be included in the assembly.Although many of the material specification
9、s are detailed within Section 4.1 of this standard, it is the responsibility of the manufacturer and installer to comply with the relevant jurisdictional requirements. The working group, which developed this standard revision, was set up within the framework of the Product Standards Committee of ASS
10、E International.Recognition is made of the time volunteered by members of this working group and of the support of the manufacturers who participated in meetings for this standard.This standard does not imply ASSEs endorsement of a product which conforms to these requirements.Compliance with this st
11、andard does not imply acceptance by any code body.It is recommended that these devices be installed consistent with local codes by qualified and trained professionals.iv Double Check Detector Fire Protection Backflow Prevention AssembliesASSE 1048-2011This standard was promulgated in accordance with
12、 procedures developed by the American National Standards Institute (ANSI).This edition was approved by the ASSE Board of Directors on August 9, 2011 as an ASSE standard.Double Check Detector Fire Protection Backflow Prevention Assemblies vASSE 1048-2011Joseph FugeloProduct Standards Committee Chairm
13、anLabov Co.Philadelphia, PennsylvaniaRand AckroydRand Technical Consulting, LLCNewburyport, MassachusettsWilliam Briggs Jr.MGJ AssociatesNew York, New YorkMaribel CamposICC Evaluation ServicesWhittier, CaliforniaJudson CollinsJulyco ProfessionalsMannford, OklahomaRon GeorgePlumb-Tech Design and(b) D
14、ouble Check Detector Assembly Type II (DCDA-II).The DCDA and DCDA-II assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position. These assemblies are designed to operate under continuous pressure conditions. The assembly shall include two (
15、2) properly located, tightly closing shut-off valves per Section 1.3.2.6 and properly located test cocks per Section 1.3.2.4. The assemblies also include a bypass line which provides a visual or audible indication of system leakage or unauthorized use of water.This standard also applies to Manifold
16、Double Check Detector Assemblies consisting of two (2) or more complete DCDA or DCDA-II assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold DCDA or DCDA-II assembly. Manifold Double Check
17、 Backflow Prevention Assemblies shall include line-sized shut-off valves on each inlet and outlet of the assemblies making up the manifold. 1.2.2 Size RangeConnection pipe sizes shall be in accordance with Table 1.2 Double Check Detector Fire Protection Backflow Prevention AssembliesASSE 1048-2011Ta
18、ble 1Rated Water Flow and Maximum Allowable Pressure Loss for Various SizesSize of DeviceRated FlowRPDA and(b) 3.6, Allowable Pressure Loss at Rated Flow.If the orientation of either of the checks or the bypass check(s) changes from the primary to an alternate orientation, the assembly shall also be
19、 tested to all of the following sections:(a) 3.5, Hydrostatic Backpressure Test of Checks;(b) 3.7, Bypass Flow Detection;(c) 3.8, Drip Tightness of First Check;(d) 3.9, Drip Tightness of Second Check; and(e) 3.10, Drip Tightness of Bypass Check (for DCDA-II Assemblies).2.2 Samples TestedThe testing
20、agency shall select one (1) of each type and model and size for the full test.2.3 DrawingsAssembly drawings and other data which are needed to enable a testing agency to determine compliance with this standard shall accompany assemblies when submitted for examination and performance testing under th
21、is standard.2.4 RejectionFailure of one (1) assembly shall result in a rejection of that type and model and size.2.5 Manifold AssemblyA manifold assembly shall be tested per Sections 3.2, Hydrostatic Test of Complete Assembly, and 3.6, Allowable Pressure Loss at Rated Flow. The individual assemblies
22、 that make up the manifold shall meet all of the test sections of the standard in their intended orientation based on the nominal pipe size for each individual assembly.Double Check Detector Fire Protection Backflow Prevention Assemblies 7ASSE 1048-2011Section III3.0 Performance Requirements and Com
23、pliance TestingNOTE: A failure due to dirt or debris is not cause for rejection. It is permissible to clean, but not replace fouled discs or seats during any test.3.1 Independence of Components3.1.1 PurposeThe purpose of this test is to determine that the shut-off valves and check valves operate wit
24、hout interfering with each other.3.1.2 ProcedureVerify that the shut-off valves and the check valves do not interfere with one another through their full range of travel.3.1.3 CriteriaAny interference of one (1) component with another component shall result in a rejection of the assembly.3.2 Hydrost
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10482011PERFORMANCEREQUIREMENTSFORDOUBLECHECKDETECTORFIREPROTECTIONBACKFLOWPREVENTIONASSEMBLIESPDF

链接地址:http://www.mydoc123.com/p-430859.html