《ANSI American Society of Sanitary Engineering 1047-2011 Performance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1047-2011 Performance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies.pdf(40页珍藏版)》请在麦多课文档分享上搜索。
1、ASSE Standard #1047-2011ASSE Board Approved: August 2011 ANSI Approved: August 2011 An American National StandardPerformance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention AssembliesASSE InternationalReduced Pressure Detector Fire Protection Backflow Prevention Assemb
2、lies iASSE 1047-2011General InformationNeither this standard, nor any portion thereof, may be reproduced without the written consent of ASSE International.Instructions for receiving authorization to display the ASSE Seal are available from ASSEs International Office. Organizations wishing to adopt o
3、r list any ASSE Standard should print the ASSE Standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.ASSE InternationalMokena, IllinoisCopyright 2011, 2009, 2005, 1999, 1993, 1990All rights reserved.ii Reduced Pressure Detector Fire Prote
4、ction Backflow Prevention AssembliesASSE 1047-2011Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies iiiASSE 1047-2011ForewordThis foreword shall not be considered a part of the standard. However, it is offered to provide background information.ASSE Product Standards are develo
5、ped in the interest of consumer safety.The recognition of probable sources or causes of contamination of a potable water supply system and the application of essential devices, or means, to prevent the entrance of contaminants to the potable water system, causing it to become unfit for human consump
6、tion, is vital to the maintenance of its continued potability.This standard focuses on those devices, known as Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies (RPDF), which will fulfill this protective need. This standard was retitled during the 1999 revision to add “fire pr
7、otection” to better describe the devices primary use.Typically installed but not limited to fire protection systems, the devices described are primarily designed for two functions. The protection of the public water supply from contaminants found in fire sprinkler systems is a primary function for a
8、 backflow preventer. These assemblies are also designed to detect low rates of flow up to 2.00 GPM (0.13 L/s) within the sprinkler system caused by leakage or unauthorized use. This standard also allows provisions for alarm signaling devices to be included in the assembly.Although many of the materi
9、al specifications are detailed within Section 4.1 of this standard, it is the responsibility of the manufacturer and installer to comply with the relevant jurisdictional requirements. The working group, which developed this standard revision, was set up within the framework of the Product Standards
10、Committee of ASSE International.Recognition is made of the time volunteered by members of this working group and of the support of the manufacturers who participated in meetings for this standard.This standard does not imply ASSEs endorsement of a product which conforms to these requirements.Complia
11、nce with this standard does not imply acceptance by any code body.It is recommended that these devices be installed consistent with local codes by qualified and trained professionals.iv Reduced Pressure Detector Fire Protection Backflow Prevention AssembliesASSE 1047-2011This standard was promulgate
12、d in accordance with procedures developed by the American National Standards Institute (ANSI).This edition was approved by the ASSE Board of Directors on August 9, 2011 as an ASSE standard.Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies vASSE 1047-2011Joseph FugeloProduct St
13、andards Committee ChairmanLabov Co.Philadelphia, PennsylvaniaRand AckroydRand Technical Consulting, LLCNewburyport, MassachusettsWilliam Briggs Jr.MGJ AssociatesNew York, New YorkMaribel CamposICC Evaluation ServicesWhittier, CaliforniaJudson CollinsJulyco ProfessionalsMannford, OklahomaRon GeorgePl
14、umb-Tech Design and(b) Reduced Pressure Detector Assembly Type II (RPDA-II).The RPDA and RPDA-II assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position, and separated by an intermediate chamber (or zone) in which there is a hydraulicall
15、y operated relief means for venting to atmosphere, internally force loaded to a normally open position. These assemblies are designed to operate under continuous pressure conditions. The assembly shall include two (2) properly located, tightly closing shut-off valves per Section 1.3.2.7 and properly
16、 located test cocks per Section 1.3.2.5. The assemblies also include a bypass line which provides a visual or audible indication of system leakage or unauthorized use of water.This standard also applies to Manifold Reduced Pressure Detector Assemblies consisting of two (2) or more complete RPDA or R
17、PDA-II assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold RPDA or RPDA-II assembly. Manifold Reduced Pressure Principle Backflow Assemblies shall include line-sized shut-off valves on ea
18、ch inlet and outlet of the assemblies making up the manifold.1.2.2 Size RangeConnection pipe sizes shall be in accordance with Table 1.2 Reduced Pressure Detector Fire Protection Backflow Prevention AssembliesASSE 1047-2011Table 1Rated Water Flow and Maximum Allowable Pressure Loss for Various Sizes
19、Size of DeviceRated FlowRPDA and(b) 3.6, Allowable Pressure Loss at Rated Flow.If the orientation of either of the checks changes from the primary to an alternate orientation, the assembly shall also be tested to all of the following sections: (a) 3.5, Hydrostatic Backpressure Test of Checks;(b) 3.1
20、0, Drip Tightness of First Check;(c) 3.11, Drip Tightness of Second Check; and(d) 3.12, Drip Tightness of Bypass Check (For RPDA-II Assemblies).If the orientation of the relief valve changes from the primary to an alternate orientation, the assembly shall also be tested to all of the following secti
21、ons:(a) 3.8, Relief Valve Opening Test;(b) 3.9, Sensitivity of Differential Pressure Relief Valve Test;(c) 3.13, Relief Valve Discharge Test with Atmospheric Supply Pressure;(d) 3.14, Relief Valve Discharge with Positive Supply Pressure; and(e) 3.15, Backpressure/Backsiphonage Test.2.2 Samples Teste
22、dThe testing agency shall select one (1) of each type and model and size for the full test.2.3 DrawingsAssembly and installation drawings and any other data which are needed to enable a testing agency to determine compliance with this standard shall accompany assemblies when submitted for examinatio
23、n and performance testing under this standard.2.4 RejectionFailure of one (1) assembly shall result in a rejection of that type and model and size.2.5 Manifold AssemblyA manifold assembly shall be tested per Sections 3.2, Hydrostatic Test of Complete Assembly, and 3.6, Allowable Pressure Loss at Rat
24、ed Flow. The individual assemblies that make up the manifold shall meet all of the test sections of the standard in their intended orientation based on the nominal pipe size for each individual assembly.Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies 7ASSE 1047-2011Section I
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10472011PERFORMANCEREQUIREMENTSFORREDUCEDPRESSUREDETECTORFIREPROTECTIONBACKFLOWPREVENTIONASSEMBLIESPDF

链接地址:http://www.mydoc123.com/p-430858.html