ANSI American Society of Sanitary Engineering 1035-2008 Performance Requirements for Laboratory Faucet Backflow Preventers (ANSI Approved September 2009 Includes Errata April 2008).pdf
《ANSI American Society of Sanitary Engineering 1035-2008 Performance Requirements for Laboratory Faucet Backflow Preventers (ANSI Approved September 2009 Includes Errata April 2008).pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1035-2008 Performance Requirements for Laboratory Faucet Backflow Preventers (ANSI Approved September 2009 Includes Errata April 2008).pdf(23页珍藏版)》请在麦多课文档分享上搜索。
1、Laboratory Faucet Backflow Preventers 1ASSE Standard 1035 - 2008Performance Requirements forLaboratory FaucetBackflow PreventersAmerican Society of Sanitary EngineeringASSE Standard #1035-2008ASSE Board Approved: April, 2008ANSI Approved: September, 2009An American National StandardLaboratory Faucet
2、 Backflow Preventers iASSE Standard 1035 - 2008American Society of Sanitary EngineeringWestlake, OhioCopyright 2008, 2002, 1993, 1981All rights reserved.Neither this standard, nor any portion thereof, may be reproduced without the written consent of the American Society of Sanitary Engineering.No pr
3、oduct may be said to be ASSE approved unless the manufacturer has applied to ASSE, has had his product tested according to the applicable ASSE standard, and when the product has passed the test, displays the ASSE Seal on the product.Instructions for receiving the authorization to display the Seal ar
4、e available from ASSEs International Office. Organizations wishing to adopt or list any ASSE standard should print the ASSE standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.General Informationii Laboratory Faucet Backflow PreventersA
5、SSE Standard 1035 - 2008Laboratory Faucet Backflow Preventers iiiASSE Standard 1035 - 2008This foreword shall not be considered a part of the standard, however, it is offered to provide background information.ASSE standards are developed in the interest of consumer safety.The American Society of San
6、itary Engineering for Plumbing and Sanitary Research is dedi-cated to the preservation of public health and safety through “Prevention Rather than Cure”.Preventing potable water in plumbing systems from becoming contaminated or polluted is an important objective of ASSEs Standards Program. The progr
7、am addresses the development and promulgation of standards embracing performance criteria for manufactured plumbing components designed to safeguard public health and safety.Recognizing the probable sources or causes of contamination or pollution of a potable water system which can cause it to becom
8、e unfit or undesirable for human consumption is vital to the maintenance of its continued potability.Backflow prevention is essential for all laboratory water outlets because of the serious con-tamination potential existing there due to the real and/or potential cross connections present in laborato
9、ries. For this reason, this standard was developed to cover devices designed es-pecially for this service.This standard is one of a series of ASSE Backflow Preventer Standards, each of which cov-ers a different type of backflow protection device, each tailored to the protective requirements essentia
10、l to the specific system conditions in which it is installed and the degree of hazard involved.Although many of the material specifications are detailed within Section IV of this Standards, it is the responsibility of the manufacturer to comply with the requirements of the Safe Drink-ing Water Act,
11、United States Public Law 93-523.The working group which developed this standard revision, was set up within the framework of the Product Standards Committee of the American Society of Sanitary Engineering.Recognition is made of the time volunteered by members of this working group and of the support
12、 of the manufacturers who also participated in the meetings for this standard.This standard does not imply ASSEs endorsement of a product which conforms to these requirements.Compliance with this standard does not imply acceptance by any code body.Forewordiv Laboratory Faucet Backflow PreventersASSE
13、 Standard 1035 - 2008It is recommended that these devices be installed consistent with local codes by qualified and trained professionals.This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI).Laboratory Faucet Backflow Preventers vA
14、SSE Standard 1035 - 2008Edward LyczkoProduct Standards Committee ChairmanCleveland ClinicCleveland, OhioRand H. AckroydRand EngineeringNewburyport, MassachusettsGunnar O. CollinsCollins Backflow Specialists, Inc.Palatine, IllinoisJudson W. CollinsJULYCO ProfessionalsMannford, OklahomaShannon M. Corc
15、oran ASSE Standards CoordinatorWestlake, OhioA. Richard EmmersonGeneral InterestBuffalo Grove, IllinoisRon GeorgeRon George Design & ConsultingNewport, MichiganCharles GrossInternational Association of Plumbingand Mechanical OfficialsWalnut, CaliforniaSteven HazzardASSE Staff EngineerWestlake, Ohio2
16、007-08 Product Standards Committee John F. Higdon, P.E.Apollo Valves/Conbraco Industries, Inc.Pageland, South CarolinaValentine Lehr, P.E.Lehr AssociatesNew York, New YorkChuck LottPrecision Plumbing Products, Inc.Portland, OregonPeter MarzecUnited Association ofPlumbers and PipefittersWashington, D
17、.C.Brad NollWilkins, A Division of Zurn Industries, Inc.Paso Robles, CaliforniaThomas C. Pitcherello State of New JerseyBordentown, New JerseyShabbir RawalpindiwalaKohler CompanyKohler, WisconsinTsan-Liang Su, Ph.D.Center for Environmental SystemsStevens Institute of TechnologyHoboken, New Jerseyvi
18、Laboratory Faucet Backflow PreventersASSE Standard 1035 - 2008Table of ContentsSection I . 11.0 General . 11.1 Application 11.2 Scope . 11.3 Reference Standards 2Section II . 32.0 Test Specimens 32.1 Samples Submitted for Test 32.2 Samples Tested 32.3 Drawings 32.4 Rejection 3Section III 43.0 Perfor
19、mance Requirements and Compliance Testing 43.1 Hydrostatic Testing of Complete Device . 4Figure 1 43.2 Deterioration at Extremes of Manufacturers Temperature and Pressure Range . 53.3 Back Pressure of Downstream Check 53.4 Tightness of Checks . 53.5 Atmospheric Vent Valve Leakage . 63.6 Backflow Thr
20、ough the Inlet Check 6Figure 2 73.7 Backflow Through Outlet Check . 73.8 Atmospheric Vent Valve Leakage . 7Figure 3 8Figure 4 8Figure 5 83.9 Back Siphonage Back Pressure . 8Figure 6 93.10 Flow and Pressure Loss . 9Section IV 104.0 Detailed Requirements . 104.1 Materials . 104.2 Markings 114.3 Instal
21、lation and Mainenance Instructions 11Section V 125.0 Definitions. 12Laboratory Faucet Backflow Preventers 1ASSE Standard 1035 - 2008Performance Requirements for Laboratory Faucet Backflow PreventersSection I1.0 General 1.1 ApplicationLaboratory Faucet Backflow Preventers are designed to protect the
22、potable water supply from pollutants or contaminants which enter the system by backflow due to back siphonage or back pressure.1.2 Scope1.2.1 DescriptionThis standard applies only to those devices classified as backflow preventers that are designed for installation on laboratory faucets on the disch
23、arge side of the last shut-off valve. These devices are not for use under constant pressure conditions. These devices consist of two independently acting check valves, force loaded or biased to a normally closed position, and between the check valves a means for automatically venting to atmosphere,
24、force loaded or biased to normally open position. 1.2.2 Working PressureThe devices shall be designed for a minimum working pressure of not less than 125.0 psi (861.9 kPa).1.2.3 Temperature RangeThe devices shall be designed for flow temperatures between 33.0 F to 180.0 F (0.6 C to 82.2 C).1.2.4 Min
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10352008PERFORMANCEREQUIREMENTSFORLABORATORYFAUCETBACKFLOWPREVENTERSANSIAPPROVEDSEPTEMBER2009INCLUDESERRATAAPRIL2008PDF

链接地址:http://www.mydoc123.com/p-430855.html