ARI GUIDELINE W-2005 SELECTING SIZING & SPECIFYING PACKAGED AIR-TO-AIR ENERGY RECOVERY VENTILATION EQUIPMENT《空气对空气能量恢复通风设备选择胶料规范》.pdf
《ARI GUIDELINE W-2005 SELECTING SIZING & SPECIFYING PACKAGED AIR-TO-AIR ENERGY RECOVERY VENTILATION EQUIPMENT《空气对空气能量恢复通风设备选择胶料规范》.pdf》由会员分享,可在线阅读,更多相关《ARI GUIDELINE W-2005 SELECTING SIZING & SPECIFYING PACKAGED AIR-TO-AIR ENERGY RECOVERY VENTILATION EQUIPMENT《空气对空气能量恢复通风设备选择胶料规范》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 4100 N. FAIRFAX DR., SUITE 200 ARLINGTON, VIRGINIA 22203 2005 GUIDELINE for SELECTING, SIZING, or the tilt angle is reversed, effectively stopping heat transfer. 5.1.4.4 Cold Corner Damper or Traversing Defrost. For Plate Heat Exchangers, outdoor air is prevented from entering a portion of the Air-
2、to-Air Heat Exchanger to enable the exhaust air energy to defrost that section of the component. 5.2 Condensation Removal. Means of removing condensate may be required. If so, observe applicable codes for piping and trapping of condensate drain(s). Copyright Air-Conditioning and Refrigeration Instit
3、ute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI GUIDELINE W-2005 5 Section 6. System Balancing 6.1 Balancing Considerations. 6.1.1 Energy Impacts. Equal (balanced) Supply and Exhaust Airflows provide the maximum energy
4、recovery for a given AAERVE. The system should be balanced as closely as possible as long as other conditions, such as requirements for building pressurization, are met. 6.1.2 Conditions Impact. Unequal airflows will influence the conditions of the supply air. Example: Reducing the Supply Airflow as
5、 compared to the exhaust will improve the supply air psychrometric conditions, but reduce the energy recovered from the exhaust air. On the other hand, reducing the Exhaust Airflow as compared to the supply will degrade the supply air psychrometric conditions. Again, energy recovered will be reduced
6、. 6.1.3 Variable Air Flow. On systems that vary total system airflow and/or outdoor air (demand control ventilation, variable air volume, etc.) provisions should be made to control both Supply and Exhaust Airflows in concert. In no case should the airflows be lower than needed to provide the require
7、d outdoor air ventilation rate per ASHRAE standards or local codes. 6.1.4 Building or Zone Pressurization. Requirements for building or zone pressurization should be considered when designing and/or balancing the system. 6.2 Balancing Methods. Provisions should be made for adjusting the airflows to
8、required rates. The methods listed below can be used independently or in combination. 6.2.1 Dampers. Dampers may be used to balance airflows to the space to insure proper air distribution to individual zones or connected air-handling equipment. Dampers may also be used to balance AAERVE Supply and E
9、xhaust Airflows. 6.2.2 Blower Settings. Methods such as multiple speed motors, adjustments in blower sheaves, etc., may be used to adjust airflows. 6.2.3 Variable Speed. Variable frequency drives, electronically commutated motors, and similar variable speed technologies may be used to adjust airflow
10、s. 6.2.4 Unitized. Operation of the main unitary blower can impact the AAERVE Supply and Exhaust Airflows. Methods should be provided to balance these flows and unitary airflow. 6.2.5 Integrated. Operation of the main unitary blower can impact the AAERVE Supply and Exhaust Airflows. Methods should b
11、e included to balance these flows. 6.2.6 Measurement of Flows. Methods should be provided to measure Supply and Exhaust Airflows for the purpose of balancing. Methods can include static pressure across the component, conventional velocity methods in the duct, or other airflow measuring devices. 6.2.
12、7 Outdoor Air Correction Factor (OACF). Consider the impact of OACF to ensure that the correct amount of outside air is introduced to meet the ventilation requirements for the building. Example: If the outdoor air is being measured at the outside air inlet and the OACF = 1.1, the measured air volume
13、 should be 110% of the required (ventilation design) Supply Airflow. This will ensure that the specified level of outdoor air is being introduced into the building (even with the OACF impact from the Air-to-Air Heat Exchanger). 6.3 Equal and Unequal Air Flows. The amount of outside air and exhaust a
14、ir required may be the result of the building design. Many facilities have exhaust air removed from a variety of sources, other than the AAERVE. In order to maintain a proper air balance in the building, this may result in the need to exhaust less air than the outdoor air requirement. In this case,
15、Effectiveness will be increased by definition (because the percentage of energy extracted from the reduced Exhaust Airflow is increased), however, the conditions of the supply air will be less favorable and the Effectiveness of the building system will be reduced (due to induced exfiltration without
16、 benefit of energy recovery). If the exhaust air is greater than the outdoor air intake, Effectiveness would again be increased by definition; supply air conditions would improve, but again, building system Effectiveness would be reduced (in this case due to induced infiltration without benefit of e
17、nergy recovery). Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI Guideline W-2005 6 Section 7. Economizer Operation 7.1 Economizer Operation. Some applications and some
18、 codes may require that Economizer operation be provided in conjunction with AAERVE. Note: Full Economizer requires up to 100% of the air-conditioning system airflow. 7.1.1 Bypass Economizer. 7.1.1.1 Unitized and Integrated Systems. Outdoor air is brought into the conditioned space without crossing
19、the component, thus not recovering energy. This can be accomplished by utilizing dampers, bypass duct and dampers, or by moving the Air-to-Air Heat Exchanger out of the outdoor airstream. 7.1.1.2 Coupled Systems. A system is added to introduce outdoor air into the conditioned space without crossing
20、the Air-to-Air Heat Exchanger which utilizes the Economizer on the air-conditioning unit. 7.1.2 Wheel Economizer. A System that introduces outdoor air into the conditioned space while crossing a Rotary Heat Exchanger without energy recovery. The component is stopped during the economizer period when
21、 energy recovery is not desired. All of the outdoor air crosses the component, thus limiting the outdoor air amount to the components airflow capacity at the application static pressure. Typically, full 100% outside air economizer function can be provided with this method only for 100% outdoor air s
22、ystems. 7.2 Modulation. All the above methods can be controlled to provide partial or modulated economizer function. 7.3 Exhaust Air Relief. Barometric relief or power exhaust is often provided in conjunction with Economizers. The exhaust fan in the AAERVE may be able to provide or assist with this
23、function. This should be considered in the design. Section 8. Design Considerations and Air-Conditioning Equipment Selection 8.1 General. The following should be considered when selecting and applying an AAERVE: a. Building design b. Building codes c. Building locale (climate consideration) d. Build
24、ing operation e. Building air-conditioning system f. Building outdoor air requirements g. Building outdoor air intake location h. Building inside air conditions i. Building structure limitations 8.1.1 Building Design. The type of building will determine the type of AAERVE required for the applicatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARIGUIDELINEW2005SELECTINGSIZINGSPECIFYINGPACKAGEDAIRTOAIRENERGYRECOVERYVENTILATIONEQUIPMENT 空气 能量 恢复

链接地址:http://www.mydoc123.com/p-429486.html