ARI 350-2008 Sound Performance Rating of Non-Ducted Indoor Air-Conditioning Equipment.pdf
《ARI 350-2008 Sound Performance Rating of Non-Ducted Indoor Air-Conditioning Equipment.pdf》由会员分享,可在线阅读,更多相关《ARI 350-2008 Sound Performance Rating of Non-Ducted Indoor Air-Conditioning Equipment.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、 2008 Standard for Sound Performance Rating of Non-Ducted Indoor Air-Conditioning Equipment ARI Standard 350 Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Price
2、 $10.00 (M) $20.00 (NM) Copyright 2008, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, compon
3、ents or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate
4、for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk.
5、Note: This standard supersedes ARI Standard 350-2000 and differs in the following ways. a. Published Ratings include the following: Octave band Sound Power Levels, dB (125 Hz to 8,000 Hz are required, 63 Hz is optional) Overall A-Weighted Sound Power Level, dB (100 Hz to 10,000 Hz are required, 50 H
6、z to 10,000 Hz are optional) Sound Quality Indicator (SQI) per ARI Standard 1140 (optional) One-third octave band Sound Power Levels, dB (optional) b. The frequency range of interest has been expanded to include the 63 Hz Octave Band (comprised of the 50, 63 and 80 Hz One-Third Octave Bands) as opti
7、onal data. c. All Sound Power Levels are determined from one-third octave band sound pressure level measurements. d. This standard references ARI Standard 220 for reverberation room qualification and testing, replacing ANSI Standard S12.31 and ANSI Standard S12.32, which were withdrawn. Copyright Ai
8、r-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section 2. Scope 1 Section 3. Definitions1 Section 4. Test Requirements .
9、2 Section 5. Rating Requirements 4 Section 6. Minimum Data Requirements for Published Ratings 5 Section 7. Marking and Nameplate Data 6 Section 8. Conformance Conditions .6 TABLES Table 1. One-Third Octave Band Numbers and A-Weighting Factors 5 FIGURES Figure 1. Location of Equipment in the Test Roo
10、m 3 APPENDICES Appendix A. References Normative .7 Appendix B. References Informative .7 Appendix C. Example Calculation of Octave Band Sound Power Levels Informative .8 Appendix D. Example Calculation of A-Weighted Sound Power Levels Informative 9 Appendix E. Expected Size of Measurement Errors Inf
11、ormative 10 Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 350-2008 TABLES FOR APPENDICES Table C1. Example Calculation of Octave Band Sound Power L
12、evels, Lwi .8 Table D1. Example Calculation of A-Weighted Sound Power Levels, LwA .9 Table E1. Maximum Standard Deviations of Sound Power Level Reproducibility Determined in Accordance with this Standard 10 Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license
13、 with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 350-2008 1 Sound Performance Rating of Non-Ducted Indoor Air-Conditioning Equipment Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Non-Ducted Indoor Air-Conditi
14、oning Equipment: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, con
15、tractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to the indoor portions of factory-made non-ducted air-conditioning equipment as defined in ARI Standards 210/240, 340/360, 310/38
16、0 and 440. Section 3. Definitions All terms in this document shall follow the standard industry definitions established in the current edition of ASHRAE Terminology of Heating, Ventilation, Air-Conditioning and Refrigeration, unless otherwise defined in this section. 3.1 Hertz (Hz). A unit of freque
17、ncy equal to one cycle per second. 3.2 Non-Ducted Indoor Air-Conditioning Equipment. Air-conditioning units without ducts. 3.3 Octave Band. A band of sound covering a range of frequencies such that the highest is twice the lowest. The Octave Bands used in this standard are those defined in ANSI Stan
18、dard S1.11. 3.4 One-Third Octave Band. A band of sound covering a range of frequencies such that the highest frequency is the cube root of two times the lowest. The One-Third Octave Bands used in this standard are those defined in ANSI Standard S1.11. 3.5 Published Rating. A statement of the assigne
19、d values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes th
20、e rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated rating conditions. 3.5.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard
21、 Rating Conditions). 3.5.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI S
22、TANDARD 350-2008 2 3.6 Rating Conditions. Any set of operating conditions under which a single level of performance results, and which cause only that level of performance to occur. 3.6.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3
23、.8 Reference Sound Source (RSS). A portable, aerodynamic sound source that produces a known stable broadband sound. 3.7 “Shall” or “Should”. “Shall” or “should” shall be interpreted as follows: 3.7.1 Shall. Where “shall” or “shall not” is used for a provision specified, that provision is mandatory i
24、f compliance with the standard is claimed. 3.7.2 Should. “Should” is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.9 Sound Power Level, Lw. Ten times the logarithm to the base ten of the ratio of the sound power radiated by the source to a reference
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI3502008SOUNDPERFORMANCERATINGOFNONDUCTEDINDOORAIRCONDITIONINGEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-429436.html