1、STD-AR1 330-ENGL 1998 0352320 OCILLLBD 3TL II 1998 STANDARD for AIR-CONDITIONING requirements for testing and rating; performance requirements; marking and nameplate daw, and conformance conditions. 1.1.1 This standard is intended for the guidance of the industry, including manufacturers, engineers,
2、 installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made residential, commercial and industrial ground source closed- loop heat pumps, as defined in Secti
3、on 3. 2.1.1 Energy Source. This standard applies only to electrically-driven, mechanical compression type systems. 2.1.2 Alternative Applications. Equipment designed for rating under this standard may not be suitable for alternative applications covered in related AF Standards 320 and 325. 2.2 Exclu
4、sions. This standard does not apply to individual assemblies for separate use. Section 3. Definitions 3.1 Dejnitions. Ali tem in this document will follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air- conditioning and Repigeration unless
5、 otherwise defined this section. 3.2 Coefficient of Performance (COP). A ratio of the heating capacity in watts w, excluding supplementaq resistance heat, to the power input in watts Wl at any given set of rating conditions expressed in watts/watt WW. (The international community uses the term EER a
6、s equivalent to cooling COP.) 3.2.1 Standard Coeficient of Perfmance. A ratio of the capacity to power input obtained at Standard Rating Heating Conditions. 3.3 Energy Eflciency Ratio PER). A ratio of the cooling capacity in Bhh wl to the power input in watts Wl at any given set of rating conditions
7、, expressed in I3tuNV.h WW. 3.3.1 Standard Energy Eflciency Ratio. A ratio of the capacity to power input values obtained at Standard Rating Conditions. 3.4 Ground Source Closed-Loop Heat Pump. A ground source closed-loop heat pump typically uses fluid circulated through a subsurface piping loop as
8、a heat source/heat sink. The heat exchange loop may be placed in horizontal trenches or vertical bores, or submerged in a body of surface water. The temperature of the fluid is related to climatic and operating history conditiod and usuaily varies from 25 “F to 100F -3.9“C to 37.7“CI. Rated efficien
9、cies include an aliowance for power to circulate the fluid. A ground source closed-loop heat pump consists of one or more factory-made assemblies which normally include an indoor conditioning coil With air moving means, compressor(s) and refngerant- to-fluid heat exchanger(s), including means to pro
10、vide both cooling and heating, cooling only or heating only functions. When such equipment is provided in more than one assembly, the separate assemblies shall be designed to be used together, and the requirements of rating outlined in the standard are based upon the use of matched assemblies. 3.4.1
11、 Functions. Ground source closed-loop heat pumps shall provide the function of air-circulating, cooling and heating with controlled temperature, and may include the functions of water heating, air- cleaning, dehumidifjmg or humi-ng. Models designated as “cooling only“ units need not include the heat
12、ing function, and models designated as “heating only“ units need not include the cooling function provided the following are met on the cortesponding model: 1. The components of the air-conditioning refngerant system (cooling system) are substantially the same on the heat pump system. 2. Switches, t
13、hermostats andor other controls of electrical components required for the reverse cycle can be altered or deleted as required to provide heating or cooling only. 1 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking
14、 permitted without license from IHS-,-,-AR1 STANDARD 330-1 998 3. All other chassis components, fans, motors, pumps, housings, etc., must be substantially the same between both versions. 3.5 PublishedRating. A statement of the assigned values of those performance characteristics, under stated rating
15、 conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term “published rating“ includes the rating of ail performance characteristics shown on the heat pu
16、mp or published in specications, advertising or other literature controlled by the manufacturer, at stated rating conditions. 3.5.1 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.5.2 Application Rating. A rating based on tests performed at application rating cond
17、itions (other than Standard Rating Conditions). 3.6 Rating Conditions. Any set of operating conditions under which a single level of performance results, and which causes only that level of performance to occur. 3.6.1 Standard Rating Conditions. Rating conditions used as the basis of comparison of p
18、erformance characteristics. 3.7 “Shall, “should, I “liecommended“ or !lt Is Recommended Ir “Shall,“ “should,“ “recommended“ or “it is recommended“ shall be interpreted as follows: 3.7.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance w
19、ith the standard is claimed. 3.7.2 Should, Recommended or It Is Recommended. “Should,“ “recommended“ or lit is recommended“ is used to inicate provisions which are not mandatory but which are desirable as good practice. Section 4. Classification 4.1 Classjcation. Normally, ground source closed-loop
20、heat pumps within the mpe of this standard may be classied as shown in Table 1. Section 5. Testing and Rating Requirements 5.1 StanhdRating. Standad ratings shall be established at the Standard Rating Conditions specified in 5.1.3. All standard ratings shall be verified by tests conducted in accorda
21、nce with ASHRAE Standard 37, and with the test methods and procedures as described in this standard except that the totai cooling and heating capacity shall be the average of the air-enthalpy method and the water coil method. Table 1. Classification of Ground Source Ciosed-Loop Heat Pumps Types of G
22、round Source C1osed:Loop Heat Pumps ARI Type+ I Designation Single Package Split System Split System with No Indoor Fan + A suffix of “O“ following any of the above classifications indicates equipment not intended for use with field- * Denotes cooling mode function. installed duct systems (see 5.1.3
23、.6). 2 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-. AR1 STANDARD 330-1 998 Standard Ratings relating to cooling or heating capacities shall be net values, including th
24、e effects of circulating-fan heai, but not including supplementary hat. Standard Input Ratings shall be the total power input to the compressor(s) and fan(s), plus controls and other items included as part of the model number). Standard Ratings of units which do not have indoor air- circulating fans
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI3301998GROUNDSOURCECLOSEDLOOPHEATPUMPS 地下 资源 闭环 蒸汽 PDF

链接地址:http://www.mydoc123.com/p-429435.html