AIR FORCE AF ETL 95-4-1995 MANDATORY ENERGY WATER PERFORMANCE STANDARDS FOR REPLACED OR MODIFIED EQUIPMENT《替代或改造设备的强制能源 水性能标准》.pdf
《AIR FORCE AF ETL 95-4-1995 MANDATORY ENERGY WATER PERFORMANCE STANDARDS FOR REPLACED OR MODIFIED EQUIPMENT《替代或改造设备的强制能源 水性能标准》.pdf》由会员分享,可在线阅读,更多相关《AIR FORCE AF ETL 95-4-1995 MANDATORY ENERGY WATER PERFORMANCE STANDARDS FOR REPLACED OR MODIFIED EQUIPMENT《替代或改造设备的强制能源 水性能标准》.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、DEPARTMENT OF THE AIR FORCE HEADQUARTERS AIR FORCE CIVL ENGINEER SUPPORT AGENCY ._ .-u 3 1 OCT 1995 FROM: HQ AFCESNCES 139 Barnes Drive Tyndall AFB FL 32403-5319 SUBJECT: Engineering Technical Letter (ETL) 954: Mandatory EnergyMcater Performance Standards for Replaced or Modified Equipment 1. Purpos
2、e. This ETL establishes energy performance standards for replacing, upgrading, or modifying equipment. These standards are designed to achieve the maximum practicable improvements in energy efficiency, cost effectiveness, and water conservation. 2. Application. Requirements of this ETL are mandatory
3、 for all facilities equipment on Air Force installations. 2.1. Authority. This ETL incorporates the new requirements of the 1994 edition of 1 O CFR 435 and the Energy Policy Act of 1992 (Public Law 102-486). 2.2. Effective Date: Immediately. Expires five years from date of issue. 3. Reference Public
4、ations. 3.1. 1 O CFR 435, Energy Conservation Performance Standards for New Buildings, 1 January 1994 (refer to Attachments 3 through 6, this ETL). 3.2. ETL 94-5, Fire Protection Engineering Criteria and Technical Guidance - Emergency Lighting and Marking of Exits. 4. Specific Requirements. Replace,
5、 upgrade, or modify equipment in accordance with the following minimum requirements, as specified in 1 O CFR 435. 4.1. Lighting. 4.1.1. Work Areas. For work areas larger than 450 ft2, check lighting levels and set IAW Attachment 3, page 1. At least one lighting control must be used for each task or
6、group of tasks within each 450 ft2. 4.1.2. Individual Fluorescent Fixtures. Replacement %foot fluorescent fixtures must meet the following criteria: 0 nominal lamp wattage c35 W 0 minimum CRI = 69 APPROVED FOR PUBLIC RELEASE: DISTRIBUTION UNLIMITED Provided by IHSNot for ResaleNo reproduction or net
7、working permitted without license from IHS-,-,- AF ETL 95-4 3515789 0582395 920 minimum average lamp efficacy = 75.0 T-8 32-watt electronic ballast systems are authorized, and tandem wiring is recommended where applicable. Do not use 40-watt fixtures as replacements. Avoid using incandescent lightin
8、g in office areas (use compact fluorescent lamps). Include all task lighting in calculations to determine proper lighting levels. NOTE: Recommend using reflectors to reduce the number of tubes needed to achieve required light levels. U-shaped fluorescent tubes are not recommended due to their high c
9、ost and limited availability. 4.1.3. Exit Lights. Refer to ETL 94-5 for specific guidance. 4.1.3.1. Repair. Use retrofit kits containing LED lights ONLY. 4.1.3.2. Replacement. Do not use incandescent lighting for replacements. Use LED lights ONLY. 4.1.4. Exterior Lighting. Exterior lights must have
10、photoelectric cells or attached timing devices. Refer to Attachment 3, sheet 3, for required lighting levels. 4.1.5. Fluorescent Lamp Ballasts. Fluorescent lamp ballasts must have a ballast efficacy factor not less than specified in Attachment 3, sheet 2. The power factor for these ballasts must be
11、equal to or greater than 90 percent. 4.2. Motors. Motors will meet minimum efficiency standards IAW Attachment 4. Do not rewind motors except under emergency conditions. Replacement motors should achieve the highest efficiency and lowest energy consumption when meeting facility load requirements. Ev
12、aluate using motors with variable speed drives as replacements whenever possible. NOTE: Recommend using Motor Mastep computer software for a listing of manufacturers of motors suitable for normal operations. Motor Mastep is included in the Construction Criteria Base (CCB). 4.3. HVAC Systems. Validat
13、e current HVAC system operation to determine proper loading and sizing of equipment for optimal use. Replacement equipment will meet minimum energy efficiency standards in Attachment 5. 4.4. Service Water Heating Systems. Water heaters and water storage tanks shall meet criteria in Attachment 6. Lav
14、oratories in public restrooms, except those for the disabled, shall be equipped with flow-limiting devices that limit maximum flow to either: 0.5 gpm; 0.75 gpm, if the device also limits the period of water discharge; or 2.5 gpm if equipped with a self-closing valve. Provided by IHSNot for ResaleNo
15、reproduction or networking permitted without license from IHS-,-,- AF ETL 95-4 3515789 0582396 867 Maximum hot water discharge in showers used for other than safety reasons will be 2.75 gpm. Output temperature must not exceed 43e C (1 loQ F). 4.5. Water Systems. Apply water system conservation measu
16、res in accordance with the following Corps of Engineers Guide Specifications (CEGS): 0 CEGS 15400 for general purpose plumbing; 0 CEGS 15405 for hospitals. These guide specifications contain all current requirements to meet federal mandates and Executive Orders. 5. Point of Contact: Mr. Freddie L. B
17、eason, HQ AFCESNCESE, DSN 523-6361, commercial (904) 283-6361, FAX 523-6219. 6 Atch Director of Technical Support 1. Distribution List 2. ETLIndex 3. Lighting Criteria 4. Motor Criteria 5. HVAC Criteria 6. Service Hot Water Criteria Provided by IHSNot for ResaleNo reproduction or networking permitte
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAFETL9541995MANDATORYENERGYWATERPERFORMANCESTANDARDSFORREPLACEDORMODIFIEDEQUIPMENT 替代 改造 设备 强制

链接地址:http://www.mydoc123.com/p-427222.html