1、 AHRI STANDARD 740-2015 2016 Standard for Performance Rating of Refrigerant Recovery Equipment and Recovery/Recycling Equipment AHRI Standard 740 Price $10.00 (M) $20.00 (NM) Copyright 2016, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent a
2、nd Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products b
3、e designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted i
4、ndustry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 740-2015. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification Pro
5、gram includes Recovery, Recovery/Recycling and Recycling Equipment including System Dependent Equipment. Certified Ratings The following Certified Ratings are verified by tests at Rating Conditions specified in Section 4: 1. Push/Pull Liquid Recovery rate, kg/min 2. Liquid recovery rate, kg/min 3. V
6、apor recovery rate, kg/min 4. High Temperature Vapor Recovery Rate, kg/min 5. Final recovery vacuum level, kPa 6. Recycle Flow Rate, kg/min 7. Refrigerant loss, kg 8. Residual Trapped Refrigerant, kg 9. Quantity of refrigerant processed at rated conditions, kg 10. Moisture content, ppm by wt. 11. Ch
7、loride ions, pass/fail 12. Acid content, ppm by wt. 13. High boiling residue, % by vol. 14. Particulates/solids, pass/fail 15. Non-condensables, % by vol. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose . 1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Test Requirements 3 Section 5. Ratin
8、g Requirements 3 Section 6. Minimum Data Requirements for Published Ratings . 3 Section 7. Operating Requirements . 8 Section 8. Marking and Nameplate Data 9 Section 9. Conformance Conditions 9 TABLES Table 1. Performance Ratings for Refrigerant Recovery Equipment and Recovery/Recycling Equipment 4
9、Table 2. Contaminant Removal Ratings for Refrigerant Recovery Equipment and Recovery/Recycling Equipment . 4 Table 3. Standard Contaminated Refrigerant Samples . 5 Table 4. AHRI Categories of Refrigerants . 7 Table 5. Maximum Levels of Contaminants Permissible in Refrigerant Processed Through Equipm
10、ent Advertised as “Recycling” Equipment 8 APPENDICES SECTION PAGE Appendix A. References - Normative 10 TABLE OF CONTENTS (continued) Appendix B. References - Informative 10 Appendix C. Methods of Testing for Performance Rating of Refrigerant Recovery Equipment and Recovery/Recycling Equipment - Nor
11、mative . 11 Appendix D. Particulate Used In Standard Contaminated Refrigerant Sample Normative. 20 TABLES FOR APPENDICES Table D1. Weight Percentage in Various m Size Ranges for Particle Size Analysis 20 FIGURES FOR APPENDICES Figure C1. Test Apparatus for Self-contained Equipment . 13 Figure C2. Sy
12、stem Dependent Equipment Test Apparatus 14 AHRI STANDARD 740-2016 1 PERFORMANCE RATING OF REFRIGERANT RECOVERY EQUIPMENT AND RECOVERY/RECYCLING EQUIPMENT Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for refrigerant Recovery Equipment and Recovery/Recycling Equipment:
13、definitions; test requirements, rating requirements, minimum data requirements for Published Ratings, operating requirements, marking and nameplate data; and conformance conditions. It establishes methods of testing for rating and evaluating the performance of refrigerant Recovery Equipment and Reco
14、very/Recycling Equipment for contaminant or purity levels, capacity, speed, purge loss to minimize emission into the atmosphere of designated refrigerants and to assure that Recovery Equipment and Recovery/Recycling Equipment meets the minimum purity requirements for refrigerants in Section 7.8. 1.1
15、.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to equi
16、pment for recovering and/or recycling, as per ASHRAE Standard 34, single refrigerants, azeotropes, zeotropic blends, and their normal contaminants from refrigerant systems. This standard defines the test apparatus, test gas mixtures, sampling procedures and analytical techniques that will be used to
17、 determine the performance of refrigerant Recovery Equipment and Recovery/Recycling Equipment. 2.1.1 Equipment shall be as defined in Sections 3.2.1 and 3.2.2. 2.1.2 Refrigerants used to evaluate equipment within the scope of this standard shall be pure halogenated hydrocarbons, hydrocarbons and ble
18、nds containing halogenated hydrocarbons or hydrocarbons that are listed in AHRI Standard 700 and either are defined as ozone depleting substances (ODS) under 40 CFR 82.3 or have been designated as acceptable or acceptable with use restrictions by the U.S. EPA Significant New Alternatives Policy (SNA
19、P) program. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the current edition of ASHRAE Terminology website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Clearing Re
20、frigerant. Procedures used to remove Trapped Refrigerants from the refrigerant Recovery Equipment and Recovery/Recycling Equipment before switching from one refrigerant to another. 3.2 Equipment Classification. 3.2.1 Self-contained Equipment. Recovery Equipment or Recovery/Recycling Equipment that i
21、s capable of refrigerant extraction without the assistance of components contained within an air-conditioning or refrigeration system. 3.2.2 System Dependent Equipment. Refrigerant Recovery Equipment, which requires for its operation the assistance of components contained in an air-conditioning or r
22、efrigeration system. AHRI STANDARD 740-2016_ 2 3.3 High Temperature Vapor Recovery Rate. For equipment within the scope of this standard having at least one designated refrigerant (see Section 8.2) with a boiling point in the range of -50 to +10C, the rate will be measured for R-22, or the lowest bo
23、iling point refrigerant if R-22 is not a designated refrigerant. 3.4 Published Ratings. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen for its application. These values apply to all units of like nominal size and
24、 type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI7402016PERFORMANCERATINGOFREFRIGERANTRECOVERYEQUIPMENTANDRECOVERYRECYCLINGEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-422574.html