AHRI 270-2015 Sound Performance Rating of Outdoor Unitary Equipment (Addendum 1 March 2016).pdf
《AHRI 270-2015 Sound Performance Rating of Outdoor Unitary Equipment (Addendum 1 March 2016).pdf》由会员分享,可在线阅读,更多相关《AHRI 270-2015 Sound Performance Rating of Outdoor Unitary Equipment (Addendum 1 March 2016).pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、 2015 Standard for Sound Performance Rating of Outdoor Unitary Equipment AHRI Standard 270 AHRI STANDARD 270-2015 WITH ADDENDUM 1, Sound Performance Rating of Outdoor Unitary Equipment March 2016 Note: This addendum is not ANSI approved and is currently going through the process to become so. Addend
2、um 1 (dated March 2016) of AHRI Standard 270-2015, “Changes to AHRI Standard 270-2015” is provided as follows. The following changes have been incorporated (deletions are shown by strikethroughs, additions are shown by shading) into the already published 2015 version of AHRI Standard 270 to avoid co
3、nfusion. The changes include: 1) The last sentence of Section 4.3.2 was removed. 4.3.2 Outdoor-side Air Quantity. All tests shall be made at the outdoor-side air quantity specified by the manufacturer where the fan drive is adjustable, or, where the fan drive is direct-connected, they shall be deter
4、mined at the outdoor air quantity inherent to the unit when operated with all of the air resistance elements associated with inlet louvers and any duct work and attachments normally supplied as part of the unit. Once established, the outdoor air circuit shall remain unchanged for all tests prescribe
5、d herein, except for the reduced ambient conditions operation (Refer to Section 5.5). 2) Edits to the second paragraph of Section 4.3.3. For convenience, the standard (cooling) condition temperatures the sound test temperatures for Unitary Air-conditioners, VRF systems and Air-source Unitary Heat Pu
6、mps are listed below. 3) Edits to Section 5.1.2. 5.2.1 Overall A-weighted Sound Power Level, LwA, dB (100 Hz to 10,000 Hz are required, 50 Hz to 10,000 Hz are optional)Overall A-weighted Sound Power Level, LwA, dB covering the range of 100 Hz to 10,000 Hz (or optionally from 50 Hz to 10,000 Hz) 4) S
7、ection 5.5 was removed. 5.5 Reduced Ambient Conditions Operation. For those units designed to automatically operate with lower noise levels during reduced ambient conditions, Standard Ratings shall also be determined with the unit operating at these lower sound levels per Section 4.3, except that th
8、e temperature entering and surrounding the outdoor portion of the unit shall be 26.5C dry-bulb (and 19.5C wet bulb when condensate is rejected to the air stream). Price $10.00 (M) $20.00 (NM) Copyright 2015, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered Unite
9、d States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommende
10、d that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-a
11、rt and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 270-2008. Foreword This standard references the sound intensity test method defined in
12、ANSI/AHRI Standard 230, as an alternate method of test to the reverberation room test method defined in ANSI/AHRI Standard 220 for determination of sound power ratings. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions . 1 Section 4. Test Requirements .
13、3 Section 5. Rating Requirements . 5 Section 6. Minimum Data Requirements for Published Ratings 6 Section 7. Marking and Nameplate Data . 7 Section 8. Conformance Conditions. 7 TABLES Table 1. Reproducibility in the Determination of Non-ducted Equipment Sound Power Levels5 APPENDICES Appendix A. Ref
14、erences Normative 8 Appendix B. References Informative 10 AHRI STANDARD 270-2015 1 SOUND PERFORMANCE RATING OF OUTDOOR UNITARY EQUIPMENT Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for outdoor unitary equipment: definitions; test requirements; rating requirements; mi
15、nimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject
16、 to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to the outdoor sections of factory-made air-conditioning and heat pump equipment as defined in ANSI/AHRI Standard 210/240, ANSI/AHRI Standard 340/360 (cooling capacity ratings of equal to or less than
17、40.0 kW), ANSI/AHRI Standard 1230, ANSI/AHRI Standard 1160 (I-P), and ANSI/AHRI Standard 1161 (SI). Products covered include: Air-source Unitary Heat Pumps, Heat Pump Pool Heaters, Unitary Air-conditioners and Variable Refrigerant Flow (VRF) Systems. Section 3. Definitions All terms in this document
18、 will follow the standard industry definitions in the ASHRAE Terminology website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Air-source Unitary Heat Pump. One or more factory-made assemblies which normally include an
19、indoor conditioning coil(s), compressor(s), and outdoor coil(s), including means to provide a heating function. They shall provide the function of air heating with controlled temperature and may include the functions of air-cooling, air-circulating, air-cleaning, dehumidifying or humidifying. When s
20、uch equipment is provided in more than one assembly, the separated assemblies shall be designed to be used together, and the requirements of rating outlined in the standard are based upon the use of matched assemblies. 3.2 Heat Pump Pool Heater. A factory-made assembly, which contains the air moving
21、 device, compressor, refrigerant-to-water heat exchanger and air-to-refrigerant heat exchanger using ambient air as the heat source. They shall provide the function of heating pool water to achieve a controlled temperature, but may include the functions of pool water cooling, air-heating, air coolin
22、g, air-circulating, air-cleaning, or dehumidifying. Models may consist of more than one assembly to be used together for the purpose of cooling and heating air. Models with separated assemblies shall be designed to be used together, and the requirements of rating outlined in this standard are based
23、upon the use of matched assemblies. 3.3 Hertz (Hz). A unit of frequency equal to one cycle per second. 3.4 Octave Band. A band of sound covering a range of frequencies such that the highest is twice the lowest. The Octave Bands used in this standard are those defined in ANSI/ASA Standard S1.11. 3.5
24、One-third Octave Band. A band of sound covering a range of frequencies such that the highest frequency is the cube root of two times the lowest. The One-third Octave Bands used in this standard are those defined in ANSI/ASA Standard S1.11. 3.6 Published Rating. A statement of the assigned values of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI2702015SOUNDPERFORMANCERATINGOFOUTDOORUNITARYEQUIPMENTADDENDUM1MARCH2016PDF

链接地址:http://www.mydoc123.com/p-422515.html