1、Price $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office 2014 Standard for Reverberation Room Qualification and Testing Procedures for Determining Sound Power of HVAC Equipment AHRI Standard 22
2、0 Price $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products,
3、 components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appro
4、priate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from
5、 risk. Note: This standard supersedes ANSI/AHRI Standard 220-2012. This standard describes the methodology for determination of Sound Power Levels of broad-band, and/or discrete-frequency noise, and narrow-band noise sources in reverberation rooms. It is based on ANSI S12.51/ISO 3741. The method des
6、cribed herein requires reverberation room pre-qualification through test and the use of the Comparison Method to determine Sound Power Levels. This standard specifies the physical environment, procedures and equipment to qualify the reverberation room by test. Pre-qualifying the room ensures adequat
7、e modal density with the use of one source location to obtain acceptable accuracy and repeatability of results. The Reference Sound Source (RSS) used for the Comparison Method relies on ANSI/AHRI Standard 250 to accurately calibrate the RSS at all frequencies of interest. The use of the Comparison M
8、ethod reduces a number of potential sources of data collection and calculation errors. The standard contains information on instrumentation, installation and operation of the source, procedures for determining the number of microphone positions or length of traverse, and procedures for the calculati
9、on of Sound Power Levels. This standard is more restrictive than ANSI Standard S12.51/ISO 3741, which allows the user to test using either the Direct Method or the Comparison Method and also allows the user to employ a space with general characteristics. The intent of ANSI S12.51/ISO 3741 is to have
10、 a room that shall provide a “good” environment for testing, with the understanding that if the end result has a variation that is too high the user can increase the number of measurement locations to improve the spatial averaging and thus lower the variation. This is not practical for sources that
11、are difficult to move. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions. 2 Section 4. Requirements for Qualification of Reverberation Rooms 3 Section 5. Reverberation Room Qualification Procedures 5 Section 6. Sound Power Testing Requirements and Calcul
12、ations . 8 Section 7. Information to BBe Recorded . 12 Section 8. Test Report 12 Section 9. Conformance Conditions 13 TABLES Table 1. Maximum Standard Deviations of Sound Power Level Reproducibility Determined in Accordance wtwith this Standard . 1 Table 2. Broadband Standard Deviation Limits 3 Tabl
13、e 3. Discrete Frequency Standard Deviation Limits 3 Table 4. Test Frequencies for Discrete Frequency Qualification . 7 Table 5. One-third Octave Band Frequency Range 8 Table 6. Background Correction Limits by One-third Octave Band 10 Table 7. One-third Octave Band Numbers and A-Weighting Factors 11
14、APPENDICES Appendix A. References Normative . 14 Appendix B. References Informative . 14 Appendix C. Sample Calculation Results Informative . 15 TABLES FOR APPENDICES Table C1. One-third Octaves . 15 Table C2. UUT Lw. 15 AHRI STANDARD 220-2014 1 REVERBERATION ROOM QUALIFICATION AND TESTING PROCEDURE
15、S FOR DETERMINING SOUND POWER OF HVAC EQUIPMENT Section 1. Purpose 1.1 Purpose. The purpose of this standard is to provide the methodology for the determination of Sound Power Levels of noise sources that emit Broadband Sound and/or Discrete Frequency Sounds/Tones in reverberation rooms. The method
16、described herein requires reverberation room pre-qualification through test and the use of the Comparison Method to determine Sound Power Levels. This standard specifies the physical environment, procedures, and equipment used to qualify the reverberation room by test. Pre-qualifying the room ensure
17、s adequate modal density with the use of one source locations to obtain acceptable accuracy and repeatability of results. The Reference Sound Source (RSS) used for the Comparison Method relies on ANSI/AHRI Standard 250 to accurately calibrate the RSS at all frequencies of interest. Sound rating valu
18、es are often useful for applications and design, therefore it is important to acquire data and qualify measurement rooms in One-third Octave Bands. The use of the Comparison Method reduces a number of potential sources of error. The standard contains information on instrumentation, installation and
19、operation of the source, procedures for determining the number of microphone positions or length of traverse, and procedures for the calculation of Sound Power Level. Measurements made in conformity with this standard will, with very few exceptions, result in standard deviations equal to or less tha
20、n specified in Table 1. The frequencies covered in this standard range from the 50 Hz to the 10,000 Hz One-third Octave Band (63 Hz to 8000 Hz Octave Bands). The 50 to 80 Hz one-third octave band sound for HVAC equipment affects product applications and often cannot be ignored. The product specific
21、AHRI standard will specify the frequency range of interest for qualification, calculation, and reporting. This standard is based on ANSI S12.51/ISO 3741 but provides additional exceptions and extensions. Table 1. Maximum Standard Deviations of Sound Power Level Reproducibility Determined in Accordan
22、ce with this Standard One-third Octave Band Center Frequency, Hz One-third Octave Band Maximum Standard Deviation of Reproducibility, R0, dB 50 - 80 4.0 100 - 160 3.0 200 - 315 2.0 400 - 5000 1.5 6000 - 10000 3.0 1.1.1 Intent. This standard is intended for the guidance of the industry, including man
23、ufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to HVAC products where sound power is determined by measurement using the Comparison Method
24、 in a reverberation room that meets the qualification requirements as defined in Section 4 of this standard. AHRI STANDARD 220-2014 _ 2 Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Terminology website (https:/www.ashrae.org/resources-p
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI2202014REVERBERATIONROOMQUALIFICATIONANDTESTINGPROCEDURESFORDETERMININGSOUNDPOWEROFHVACEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-422509.html