《AASHTO M 176M M 176-2007 Standard Specification for Porous Concrete Pipe《多孔混凝土管标准规范[替代 ASTM C654 REV A ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C6.pdf》由会员分享,可在线阅读,更多相关《AASHTO M 176M M 176-2007 Standard Specification for Porous Concrete Pipe《多孔混凝土管标准规范[替代 ASTM C654 REV A ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C654 ASTM C6.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Standard Specification for Porous Concrete Pipe AASHTO Designation: M 176M/M 176-07 (2012)1ASTM Designation: C 654M-05a and C 654-05a American Association of State Highway and Transportation Officials 444 North Capitol Street N.W., Suite 249 Washington, D.C. 20001 TS-4a M 176M/M 176-1 AASHTO Standar
2、d Specification for Porous Concrete Pipe AASHTO Designation: M 176M/M 176-07 (2012)1ASTM Designation: C 654M-05a and C 654-05a 1. SCOPE 1.1. This specification covers porous nonreinforced concrete pipe for use in underdrains. 1.2. This specification is applicable for orders in either SI units (M 176
3、M) or in inch-pound units (M 176). SI units and inch-pound units are not necessarily equivalent. Inch-pound units are shown in brackets in the text for clarity, but they are the applicable values when the material is ordered to M 176. 2. REFERENCED DOCUMENTS 2.1. AASHTO Standards: M 6, Fine Aggregat
4、e for Hydraulic Cement Concrete M 80, Coarse Aggregate for Hydraulic Cement Concrete M 85, Portland Cement M 154M/M 154, Air-Entraining Admixtures for Concrete M 240M/M 240, Blended Hydraulic Cement M 262, Concrete Pipe and Related Products M 295, Coal Fly Ash and Raw or Calcined Natural Pozzolan fo
5、r Use in Concrete M 302, Slag Cement for Use in Concrete and Mortars T 280, Concrete Pipe, Manhole Sections, or Tile 2.2. ASTM Standard: C 989, Standard Specification for Slag Cement for Use in Concrete and Mortars C 1116/C 1116M, Standard Specification for Fiber-Reinforced Concrete 3. TERMINOLOGY 3
6、.1. DefinitionsFor definitions of terms relating to concrete pipe, see M 262. 4. CLASSIFICATION 4.1. Pipe manufactured according to this specification shall be of two classes identified as “Standard-Strength Porous Nonreinforced Concrete Pipe” and “Extra-Strength Porous Nonreinforced Concrete Pipe.”
7、 2014 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 176M/M 176-2 AASHTO 5. BASIS OF ACCEPTANCE 5.1. The acceptability of the pipe shall be determined by the results of the strength and porosity or r
8、ate of infiltration tests, and by inspection to determine whether the pipe conform to this specification as to design and freedom from defects. 5.2. The pipe shall be acceptable under the strength tests when they have met the requirements as prescribed in Section 10. 5.3. Acceptance as to Infiltrati
9、on PropertiesPipe shall be acceptable under the infiltration test when all test pipe conform to the test requirements as prescribed in Section 10. 6. MATERIALS 6.1. ConcreteThe concrete shall consist of cementitious materials, aggregates, and water. 6.2. Cementitious Materials: 6.2.1. CementCement s
10、hall conform to the requirements of M 85 or shall be portland blast-furnace slag cement or slag modified portland cement, or portland-pozzolan cement conforming to the requirements of M 240M/M 240, except that the pozzolan constituent in the Type IP portland-pozzolan cement shall be fly ash and shal
11、l not exceed 25 percent by weight. 6.2.2. Fly AshFly ash shall conform to the requirements of M 295, Class F or Class C. 6.2.3. Ground Granulated Blast-Furnace Slag (GGBFS)GGBFS shall conform to the requirements of grade 100 or 120 of ASTM C 989. 6.2.4. Allowable Combinations of Cementitious Materia
12、lsThe combination of cementitious materials used in the concrete shall be one of the following: 6.2.4.1. Portland cement only, 6.2.4.2. Portland blast-furnace slag cement only, 6.2.4.3. Slag modified portland cement only, 6.2.4.4. Portland-pozzolan cement only, 6.2.4.5. A combination of portland cem
13、ent and fly ash, 6.2.4.6. A combination of portland cement and ground granulated blast-furnace slag, or 6.2.4.7. A combination of portland cement, fly ash (not to exceed 25 percent of the total cementitious weight), and ground granulated blast-furnace slag (not to exceed 25 percent of the total ceme
14、ntitious weight). Note 1The user of this specification is advised that porous pipe may experience leaching detrimental to durability when subjected to drainage of soft or acid waters (less than 50 ppm hardness or less than 6.0 pH). Type V portland cement should be specified where high sulfate resist
15、ance is required, and Type II or IIA portland cement should be specified where the pipe will be exposed to moderate sulfate conditions. More than 3000 mg/L ppm of chiefly sodium or magnesium sulfates, or both, may be considered high sulfate content. 2014 by the American Association of State Highway
16、and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 176M/M 176-3 AASHTO 6.3. AggregatesAggregates shall conform to M 6 and M 80 except that the requirement for gradation shall not apply. 6.4. Admixtures and BlendsAdmixtures and blends shall only be
17、used with the approval of the owner. 6.5. Synthetic FibersPolypropylene fibers are permitted, at the owners option, in concrete pipe as a nonstructural manufacturing material. Only Type III synthetic fibers designed and manufactured specifically for use in concrete and conforming to the requirements
18、 of ASTM C 1116/C 1116M shall be accepted. 7. DESIGN 7.1. Design TableDesign requirements shall be in accordance with Tables 1 and 2 and Figure 1. Wall thickness used shall be not less than the value shown, except as affected by the tolerance herein specified. Table 1Physical and Dimensional Require
19、ments of Porous Concrete Pipe Internal Designated Diameter, D Minimum Wall Thickness, T Minimum Laying LengthaMinimum Socket Depth, Ls Minimum Strength Three- Edge-Bearing Minimum Infiltration mm in. mm in. mm in. mm in. kN/m lbf/ft (L/s)/m (gal/min)/ft 100 4 25 1 600 24 25 1 14.5 1000 0.8 4 150 6 2
20、5 1 600 24 25 1 16.0 1100 1.0 6 200 8 32 11/4 600 24 32 11/419.0 1300 1.5 8 250 10 35 11/8600 24 35 11/820.5 1400 2.0 10 300 12 38 11/2600 24 38 11/222.0 1500 2.5 12 375 15 44 13/4600 24 44 13/425.5 1750 3.0 15 450 18 50 2 600 24 50 2 29.0 2000 3.5 18 525 21 57 21/4600 24 57 21/432.0 2200 4.0 21 600
21、 24 63 21/2600 24 63 21/235.0 2400 4.5 24 aNormally, the minimum laying length is 600 mm 24 in. in length, but if the owner has no objections, then 450-mm 18-in. length pipe up to 300 mm 12 in. in diameter shall be acceptable. Table 2Physical and Dimensional Requirements of Extra-Strength Porous Con
22、crete Pipe Internal Designated Diameter, D Minimum Wall Thickness, T Minimum Laying LengthaMinimum Socket Depth, Ls Minimum Strength Three- Edge-Bearing Minimum Infiltration mm in. mm in. mm in. mm in. kN/m lbf/ft (L/s)/m (gal/min)/ft 150 6 32 11/4600 24 32 11/432.0 2200 1.0 6 200 8 38 11/2600 24 38
23、 11/238.0 2600 1.5 8 250 10 41 15/8600 24 41 15/841.0 2800 2.0 10 300 12 50 2 600 24 50 2 44.0 3000 2.5 12 375 15 57 21/4600 24 57 21/446.5 3200 3.0 15 450 18 63 21/2600 24 63 21/246.5 3200 3.5 18 a Normally, the minimum laying length is 600 mm 24 in. in length, but if the owner has no objections, t
24、hen 450-mm 18-in. length pipe up to 300 mm 12 in. in diameter shall be acceptable. 2014 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 176M/M 176-4 AASHTO Note: See Tables 1 and 2 for values of D, T,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AASHTOM176MM1762007STANDARDSPECIFICATIONFORPOROUSCONCRETEPIPE 多孔 混凝土 标准规范 替代 ASTMC654REVAASTMC654ASTMC654ASTMC654ASTMC654ASTMC654ASTMC654ASTMC654ASTMC6PDF

链接地址:http://www.mydoc123.com/p-417686.html